Permit Application Status

B1000309


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000309
Building Permit - Commercial
Final Completion
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
DAY DREAM OASIS SALON & SPA TENANT FINISH
04/08/2010
04/20/2010
10/17/2010
05/17/2010
Locations
Contacts
DAY DREAM OASIS SALON, Address:611 SW 3RD ST  
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/17/2010 10/29/2010
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - The project cost has not been provided.
Correction

Codes Administration - Footnote i of Table 403.3 requires that the required exhaust system capture the contaminants and odors produced in nail salons at their source. The exhaust systems provided in the areas of the manicure and pedicure stations do not meet this requirement.
Correction

Fire Department- Existing Life Safety features subject to inspection
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $30.00 $30.00 Paid 04/20/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Mechanical Inspection Not Ready 04/26/2010
Correction
Corrective Action Required
04/26/2010
Receive Fire Department approval
Correction
Corrective Action Required
04/26/2010
TESTING OF ELECTRICAL RECEPTACLES
Correction
Corrective Action Required
04/26/2010
LABELING OF ELECTRICAL CIRCUIT BREAKERS NEC 408.4: EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE" SERVICE PANEL
Correction
Corrective Action Required
04/26/2010
RESTROOM WATER CLOSET SEAT
Correction
Corrective Action Required
04/26/2010
NAIL/PEDICURE STATION EXHAUST SYSTEM
Final Mechanical Inspection Failed 04/27/2010
Correction
Corrective Action Required
04/27/2010
Receive Fire Department approval PER CHIEF BRIAN AUSTERMAN PHONE 816-969-1316
Correction
Partial Correction
04/27/2010
TESTING OF ELECTRICAL RECEPTACLES ALL TESTED OK EXCEPT 1 SOUTH OF RECEPTION DESK
Correction
Corrective Action Required
04/27/2010
LABELING OF ELECTRICAL CIRCUIT BREAKERS NEC 408.4: EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE" SERVICE PANEL LABELING IN PROGRESS
Correction
Resolved
04/27/2010
RESTROOM WATER CLOSET SEAT
Correction
Corrective Action Required
04/27/2010
NAIL/PEDICURE STATION EXHAUST SYSTEM EXHAUST FPM TO BE VERIFIED
Correction
Corrective Action Required
04/27/2010
REQUIRED HANDRAILS AT COMMERCIAL STAIR REQ'D BOTH SIDES OF STAIR STAIR TO LOWER LEVEL
Correction
Corrective Action Required
04/27/2010
WATER HEATER TEMPERATURE/PRESSURE RELIEF DISCHARGE PIPING IPC 504.6 TERMINATION > 6" ABOVE FLOOR OR WASTE RECEPTOR
Final Mechanical Inspection Failed 04/28/2010
Correction
Resolved
04/28/2010
Receive Fire Department approval PER CHIEF BRIAN AUSTERMAN
Correction
Resolved
04/28/2010
TESTING OF ELECTRICAL RECEPTACLES
Correction
Resolved
04/28/2010
NAIL/PEDICURE STATION EXHAUST SYSTEM EXHAUST DRAW APPROVED
Correction
Corrective Action Required
04/28/2010
REQUIRED HANDRAILS AT COMMERCIAL STAIR ADD CONFORMING HANDRAIL AT NORTH SIDE OF STAIR PER PAGES 213-218 OF 2006 IBC PROVIDED. REQ'D BOTH SIDES OF STAIR STAIR TO LOWER LEVEL
Final Inspection - Commercial Failed 04/28/2010
Correction
Partial Correction
04/28/2010
USE / OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Final Mechanical Inspection Passed 05/14/2010
Correction
Resolved
05/14/2010
LABELING OF ELECTRICAL CIRCUIT BREAKERS SERVICE PANEL
Correction
Resolved
05/14/2010
REQUIRED HANDRAILS AT COMMERCIAL STAIR STAIR TO LOWER LEVEL
Correction
Resolved
05/14/2010
WATER HEATER TEMPERATURE/PRESSURE RELIEF DISCHARGE PIPING WATER HEATER RELOCATED
Final Inspection - Commercial Passed 05/14/2010
Correction
Resolved
05/14/2010
USE / OCCUPANCY APPROVAL STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home