Permit Application Status

B1000302


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000302
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
TENANT INFILL IN PREVIOUSLY UNOCCUPIED SPACE. DEMISING FRAMING PERMITED PREVIOUSLY UNDER B1000198
04/07/2010
06/14/2010
02/01/2011
08/09/2010
Locations
Contacts
ALLEGHENY DESIGN MANAGEMENT INC, Address:1154 PARKS INDUSTRIAL DR  
DWAYNE MANN, Address:103 WOODVIEW CT  
MATTHEW DIX INC, Address:28710 FLINT ST  
SHAWNEE HEATING AND COOLING, Address:10666 WIDMER  
C.D. MCCLAIN ELECTRICAL, Address:PO BOX 1494  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/02/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the evenet of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building requried to have two or more exits. 3. Exterior egress componenets at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2006 IBC 1008.1.9 - Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds. Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Gourp A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equiped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side.
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - The doors shown on the floor plan on Sheet A2.1 do not match the information on the Door Schedule on Sheet A1.1. Doors 03 and 04 are not on the schedule and the schedule has doors 08 and 09 which are not on the plan.
Correction

Fire Department- 2006 IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet (1829 mm) wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equipped with panic hardware and doors must swing in the direction of egress.
Correction

Fire Department- Correct discrepancies between the door schedule and plans.
Correction

Fire Department- 2006 IFC -1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $659.40 $659.40 Paid 06/14/2010
89 Sewer Tap Fees $150.00 $150.00 Paid 06/14/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 06/24/2010
Correction
Partial Correction
06/24/2010
WALL FRAMING + IN-WALL SYSTEMS N & S DEMISING WALLS (SECURE ALL MC CABLE TO STRUCTURE WITHIN 12"); OK TO COVER WHEN READY WALLS LISTED BELOW:
Rough Framing Inspection - Commercial Request Complete 6/23/2010 6/24/2010 06/24/2010
Rated Assembly Inspection Not Ready 07/01/2010
Correction
Corrective Action Required
07/01/2010
READINESS FOR INSPECTION IBC 109.1, 109.5: NOT READY PROPERTY LOCKED INTERIOR NOT ACCESSIBLE
Rated Assembly Inspection Partial 07/06/2010
Correction
Partial Correction
07/06/2010
GWB AT UL-RATED WALL OK TO MUD, TAPE, AND FIRE-SEAL SOUTH DEMISING WALL NORTH FACE
Correction
Resolved
07/06/2010
READINESS FOR INSPECTION
Underslab Plumbing Inspection - Commercial Passed 07/06/2010
Correction
Resolved
07/06/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Rough Plumbing Inspection - Commercial Not Ready 07/06/2010
Correction
Corrective Action Required
07/06/2010
READINESS FOR INSPECTION IN-WALL PLUMBING NOT READY FOR INSPECTION
Rated Assembly Inspection Partial 07/07/2010
Correction
Partial Correction
07/07/2010
GWB AT UL-RATED WALL SOUTH DEMISING WALL NORTH FACE; NORTH DEMISING WALL SOUTH FACE OK TO MUD/TAPE/FIRE-SEAL
Underslab Electrical Inspection - Commercial Passed 07/07/2010
Correction
Resolved
07/07/2010
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
Rated Assembly Inspection Passed 07/14/2010
Correction
Resolved
07/14/2010
GWB AT UL-RATED WALL MUDDED; TAPED; FIRE-SEALED S DEMISING WALL N FACE + N DEMISING WALL S FACE
Rough Framing Inspection - Commercial Request Complete 7/13/2010 7/14/2010 07/14/2010
All Rough Inspection - Commercial Failed 07/15/2010
Correction
Corrective Action Required
07/15/2010
INSTALLATION OF WALL TOP TRACKS AT ROOF DECK ELEVATION NOT PER DRAWINGS SEE APPROVED DETAILS
Correction
Partial Correction
07/15/2010
WALL FRAMING + IN-WALL SYSTEMS N & S DEMISING WALLS (SECURE ALL MC CABLE TO STRUCTURE WITHIN 12"); OK TO COVER WHEN READY WALLS LISTED BELOW:
All Rough Inspection - Commercial Passed 07/16/2010
Correction
Resolved
07/16/2010
INSTALLATION OF WALL TOP TRACKS AT ROOF DECK ELEVATION
Correction
Resolved
07/16/2010
WALL FRAMING + IN-WALL SYSTEMS ALL WALLS + BULKHEAD/SOFFIT @ WEST END OF SPACE OK TO COVER WHEN READY SURFACES LISTED BELOW:
Rough Framing Inspection - Commercial Request Complete 7/16/2010 7/16/2010 07/16/2010
Rough Plumbing Inspection - Commercial Passed 07/19/2010
Correction
Resolved
07/19/2010
READINESS FOR INSPECTION
Electrical Service Inspection Passed 07/19/2010
Correction
Resolved
07/19/2010
ELECTRICAL SERVICE INSTALLATION ENSURE PANEL FRONTS ARE IN PLACE WHEN REQUESTING SERVICE ACTIVATION. 200A 3P 4W > 30KVA XFRMR RELEASE SERVICE
Gas Piping Inspection - Commercial Passed 07/26/2010
Correction
Resolved
07/26/2010
None
Gas Service Inspection - Commercial Passed 07/26/2010
Correction
Resolved
07/26/2010
None - HELD 15 PSI. RELEASE METER.
Final Plumbing Inspection - Commercial Passed 07/30/2010
Correction
Resolved
07/30/2010
None - FINAL FOR PLUMBING
Occupancy Inspection - Codes Commercial Failed 08/04/2010
Correction
Corrective Action Required
08/04/2010
USE / OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FOR BUSINESS NO PUBLIC ENTRY
Correction
Corrective Action Required
08/04/2010
IDENTIFICATION OF ELECTRICAL SERVICE PANELS AFFIX PERMANENT LABELS PER DRAWINGS
Correction
Corrective Action Required
08/04/2010
ELECTRICAL PANEL SCHEDULE BREAKERS LABELED BOTTOM-TO-TOP; SCHEDULE NUMBERED TOP-TO-BOTTOM PANEL "H" MATCH BREAKER ARRANGEMENT
Correction
Corrective Action Required
08/04/2010
ELECRTRICAL RECEPTACLE ABOVE RECEIVING DESK APPARENT REVERSE HOT/NEUTRAL
Correction
Corrective Action Required
08/04/2010
FLOOR DRAINS @ RESTROOMS REMOVE COVERING TO ALLOW FLOW
Correction
Corrective Action Required
08/04/2010
SURFACE OF RESTROOM FLOOR MUST BE NON-ABSORBENT FILL HOLES, CUTS FIRST
Correction
Corrective Action Required
08/04/2010
ROOFTOP INSPECTION GAS PIPE SUPPORTS NOT PER DRAWING + ENSURE ALL DEBRIS IS CLEANED FROM TENANT FOOTPRINT RTU RECEPTS NOT HOT + COMPLETE 860 @ RTU N-1 +
Correction
Partial Correction
08/04/2010
Receive Fire Department approval ISSUES DISCUSSED CONTACT CPT JOE DIR PHONE 816-969-1317
Occupancy Inspection - Codes Commercial Passed 08/06/2010
Correction
Resolved
08/06/2010
ROOFTOP INSPECTION
Correction
Resolved
08/06/2010
SURFACE OF RESTROOM FLOOR NON-ABSORBENT FINISH IN PROGRESS
Correction
Resolved
08/06/2010
FLOOR DRAINS @ RESTROOMS COVERING REMOVED TO ALLOW FLOW
Correction
Resolved
08/06/2010
ELECRTRICAL RECEPTACLE ABOVE RECEIVING DESK APPARENT HOT/NEUTRAL REVERSE CORRECTED
Correction
Resolved
08/06/2010
ELECTRICAL PANEL SCHEDULE PANEL "H"
Correction
Resolved
08/06/2010
IDENTIFICATION OF ELECTRICAL SERVICE PANELS PERMANENT LABELS AFFIXED
Correction
Resolved
08/06/2010
USE / OCCUPANCY APPROVAL STATUS
Correction
Resolved
08/06/2010
Receive Fire Department approval PER CPT JOE DIR 8/5/2010
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home