Permit Application Status

B1000257


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000257
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
OUTPATIENT CLINIC TENANT FINISH
03/26/2010
04/22/2010
10/19/2010
08/23/2010
Locations
Contacts
P1 GROUP INC, Address:16210 WEST 108TH ST  
J E DUNN CONSTRUCTION, Address:1001 LOCUST  
P1 GROUP INC, Address:16210 WEST 108TH ST  
P1 GROUP INC, Address:16210 WEST 108TH ST  
SHAW ELECTRIC COMPANY, Address:3600 FULLER AVE  
CATES SHEET METAL IND INC, Address:15555 W 108TH ST  
ACI BOLAND, Address:11229 NALL SUITE 140  
P1 GROUP INC, Address:16210 WEST 108TH ST  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/03/2010 10/29/2010
Correction

Fire Department- 2006 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
Correction

Fire Department: Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators, and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Documentation shall be provided of the pressure test of at least 150 psi for a minimum of 24 hours on installers letterhead.
Correction

Fire Department- 2006 IFC 1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building. Exception: Approved temporary means of egress systems and facilities.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $742.28 $742.28 Paid 04/22/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Plumbing Inspection - Commercial Request Complete 5/18/2010 5/18/2010 05/18/2010
All Rough Inspection - Commercial Partial 05/28/2010
Correction
Partial Correction
05/28/2010
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY TOP 5' OF TOP-OUT WALLS
All Rough Inspection - Commercial Partial 06/09/2010
Correction
Partial Correction
06/09/2010
WALL FRAMING + IN-WALL SYSTEMS TOP 5' OF TOP-OUT WALLS; ALL EXCEPT HALL 213 S WALL, EXAM 212 W WALL, JAN 133 N WALL -- WHERE OPENINGS HAVE YET TO BE CONSTRUCTED; OK TO COVER WHEN READY FOLLOWING WALL AREAS:
All Rough Inspection - Commercial Partial 06/11/2010
Correction
Partial Correction
06/11/2010
WALL FRAMING + IN-WALL SYSTEMS TOP 5' OF TOP-OUT WALLS; ALL WALLS EXCEPT HALL 213 S WALL, EXAM 212 W WALL, JAN 133 N WALL -- WHERE OPENINGS HAVE YET TO BE CONSTRUCTED OR FILLED-IN OK TO COVER WHEN READY FOLLOWING WALL AREAS:
Rated Assembly Inspection Not Ready 06/11/2010
Correction
Corrective Action Required
06/11/2010
READINESS FOR INSPECTION WORK REQUESTED FOR INSP NOT COMPLETED
All Rough Inspection - Commercial Partial 06/14/2010
Correction
Partial Correction
06/14/2010
WALL FRAMING + IN-WALL SYSTEMS ALL WALLS EXCEPT HALL 213 S WALL & EXAM 212 W WALL WHERE OPENINGS HAVE YET TO BE CONSTRUCTED OR FILLED-IN OK TO COVER WHEN READY FOLLOWING WALL AREAS:
Rated Assembly Inspection Partial 06/14/2010
Correction
Resolved
06/14/2010
READINESS FOR INSPECTION
Correction
Partial Correction
06/14/2010
GWB AT UL FIRE-RATED WALLS THEN OK TO TAPE, MUD, & FIRE-CAULK; TO BE RE-INSPECTED BEFORE CEILING GRID IS INSTALLED. SOILED HOLDING 131 TIGHTEN/SECURE UPPER 30"
Above Ceiling Inspection Partial 06/30/2010
Correction
Partial Correction
06/30/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 1) 133: SUPPORT SPRINKLER PIPE FROM STRUCTURE -- NOT FROM DUCT 2) 131: FIRE WALL REVISION REQUIRES 5/8" TYPE X ON ROOM FACE 3) 129 WEST WALL: 1/2" x 4" OPENING NOT FIRE-SEALED OK TO COVER WHEN READY EXCEPT FOLLOWING LOCATION
Above Ceiling Inspection Passed 07/07/2010
Correction
Resolved
07/07/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 07/07/2010
Correction
Partial Correction
07/07/2010
WALL FRAMING + IN-WALL SYSTEMS ALL WALLS EXCEPT BELOW -- INCLUDING IN-FILL OF EXSTG DOOR @ EXAM 212 W WALL YET TO BE COMPLETED & INSPECTED: HALL 213 S WALL WHERE OPENING HAS YET TO BE CONSTRUCTED OK TO COVER WHEN READY FOLLOWING WALL AREAS:
Occupancy Inspection - Codes Commercial Partial 07/09/2010
Correction
Partial Correction
07/09/2010
FINAL INSPECTION OF ROOM 213B ONLY NO PATIENTS/PUBLIC ALLOWED UNTIL APPROVED. OK FOR INSTALLATION OF MAMMOGRAPHY EQUIPMENT
Occupancy Inspection - Codes Commercial Partial 07/16/2010
Correction
Resolved
07/16/2010
FINAL INSPECTION OF ROOM 213B ONLY OK FOR INSTALLATION OF MAMMOGRAPHY EQUIPMENT
Correction
Partial Correction
07/16/2010
USE / OCCUPANCY APPROVAL STATUS PHASE I SPACES; OK FOR USE/OCCUPANCY FOLLOWING SPACES:
All Rough Inspection - Commercial Partial 08/02/2010
Correction
Partial Correction
08/02/2010
WALL FRAMING + IN-WALL SYSTEMS ALL PHASE 1 WALLS; 158 NEW NORTH ALCOVE; 160; 168; OK TO COVER WHEN READY FOLLOWING WALL AREAS:
Above Ceiling Inspection Passed 08/11/2010
Correction
Resolved
08/11/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS PHASE 1; PHASE 2 SPACES 158N; 160; 168 OK TO COVER WHEN READY AREAS DESCRIBED BELOW:
Occupancy Inspection - Codes Commercial Passed 08/19/2010
Correction
Resolved
08/19/2010
USE / OCCUPANCY APPROVAL STATUS PHASE 1 SPACES; PHASE 2 SPACES OK FOR USE/OCCUPANCY FOLLOWING SPACES:
Correction
Resolved
08/19/2010
Receive Fire Department approval ISSUES OUTSIDE PERMIT WORK AREA TO BE RESOLVED DIRECTLY WITH FIRE DEPARTMENT BY JE DUNN. NO ISSUES IN PERMIT AREA
All Rough Inspection - Commercial Passed 08/20/2010
Correction
Resolved
08/20/2010
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY
Rated Assembly Inspection Passed 08/20/2010
Correction
Resolved
08/20/2010
GWB AT UL FIRE-RATED WALLS
Underground Plumbing Inspection - Commercial Passed 08/20/2010
Correction
Resolved
08/20/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING PIPING AT ROOMS 212; 213; 213A; 213B; 214A; OK TO COVER WHEN READY FOLLOWING SEGMENTS:
Alarm Test Passed 8/18/2010 at 12:00 AM 12/21/2010
Occupancy Inspection - Fire Temporary C of O 8/19/2010 at 12:00 AM 12/21/2010
Corrective Action Required
12/21/2010
strobe notification needed in restroom IC66 illuminated exit sign needed for the ultra sound corridor.
Corrective Action Required
12/21/2010
Occupancy Inspection - Fire Passed 12/21/2010 at 12:00 AM 12/21/2010
Corrective Action Required
12/21/2010
Documents & Images
Date Uploaded File Type Document Name
12/21/2010 Letter Fire Loss Reduction Form
12/21/2010 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home