Permit Application Status

B1000160


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000160
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
RETAIL TENANT SPACE IN PREVIOUSLY UNFINISHED SPACE.
02/26/2010
03/18/2010
12/29/2010
07/06/2010
Locations
Contacts
MEYER BROTHERS BUILDING COMPANY, Address:200 NE MISSOURI RD  
MEYER BROTHERS BUILDING COMPANY, Address:200 NE MISSOURI RD  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/14/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Correction

Codes Administration - 2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employess shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
Correction

Codes Administration - The existing corridor wall is a one-hour fire-resistive assembly. This is not indicated on the plans.
Correction

Codes Administration - Door 103 to the existing corridor is require to be rated for a minimum of 20 minutes.
Correction

Codes Administration - The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will be verified by the city inspection staff.
Correction

Fire Department- All plans submitted for review on or after July 9, 2007 shall be designed to the requirements of the 2006 International Building Code, 2006 International Mechanical Code, 2006 International Plumbing Code, 2006 International Fuel Gas Code, 2006 International Fire Code, 2005 National Electric Code and the ANSI A117.1-2003 as amended and adopted by the City of Lee's Summit.
Correction

Fire Department- 2006 IFC 1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. Exception: Doors, when fully opened, and handrails, shall not reduce the required width by more than 7 inches (178 mm). Doors in any position shall not reduce the required width by more than one-half. Other nonstructural projections such as trim and similar decorative features are permitted to project into the required width 1.5 inches (38 mm) on each side.
Correction

Fire Department - Storage on the mezzanine shall not extend higher than 18" below the sprinkler heads.
Correction

Codes Administration - The plumbing plans have not been revised to reflect the new layout of the bathroom or the addition of the service sink.
Correction

Codes Administration - The Toilet Accessory Schedule on Sheet A101 does not include the newly added Item K, which appears to be a service sink.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $260.62 $260.62 Paid 03/18/2010
89 Sewer Tap Fees $60.00 $60.00 Paid 03/18/2010
0120 Building Permit Fee $196.56 $196.56 Paid 04/22/2010
89 Sewer Tap Fees $30.00 $30.00 Paid 04/22/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Inspection - Commercial Not Ready 03/24/2010
Correction
Corrective Action Required
03/24/2010
ADDRESS LABELING OF RTU
Correction
Corrective Action Required
03/24/2010
REQUIRED ELECTRICAL RECEPTACLE OUTLET NEC 210.63: REQUIRED AT ROOFTOP WITHIN 7.5 METERS HVAC AND/OR REFRIG EQPMT AT ROOFTOP
Gas Piping Inspection - Commercial Partial 03/24/2010
Correction
Corrective Action Required
03/24/2010
PROTECTION OF METALLIC PIPE (OR TUBING) AGAINST CORROSION IFGC 404.8 EXPOSED ROOFTOP PIPING PAINT OR OTHER APPROVED
Gas Service Inspection - Commercial Passed 03/24/2010
Correction
Resolved
03/24/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
All Rough Inspection - Commercial Not Ready 04/21/2010
Correction
Corrective Action Required
04/21/2010
WALL FRAMING + IN-WALL SYSTEMS
Correction
Corrective Action Required
04/21/2010
READINESS FOR INSPECTION LSCO SEC 7-142; IBC 106: NO INSPECTIONS WITHOUT PERMIT DRAWINGS PERMIT DRAWINGS NOT FOUND ON SITE
All Rough Inspection - Commercial Partial 04/22/2010
Correction
Partial Correction
04/22/2010
WALL FRAMING + IN-WALL SYSTEMS SOUTH DEMISING WALL EXCEPT E 3'; NORTH DEMISING WALL EXCEPT W 12'; OK TO COVER WHEN READY WALLS LISTED BELOW:
Correction
Resolved
04/22/2010
READINESS FOR INSPECTION
All Rough Inspection - Commercial Passed 05/04/2010
Correction
Resolved
05/04/2010
WALL FRAMING + IN-WALL SYSTEMS SOUTH DEMISING WALL + NORTH DEMISING WALL OK TO COVER WHEN READY WALLS LISTED BELOW:
Underslab Plumbing Inspection - Commercial Passed 05/04/2010
Correction
Resolved
05/04/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY OK TO COVER WHEN READY FOLLOWING SEGMENTS:
Underslab Electrical Inspection - Commercial Passed 05/04/2010
Correction
Resolved
05/04/2010
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
All Rough Inspection - Commercial Partial 05/11/2010
Correction
Partial Correction
05/11/2010
WALL FRAMING + IN-WALL SYSTEMS SOUTH DEMISING WALL; NORTH DEMISING WALL INCLUDING WEST 12'; OK TO COVER WHEN READY WALLS LISTED BELOW:
Rough Framing Inspection - Commercial Request Complete 5/11/2010 5/11/2010 05/11/2010
All Rough Inspection - Commercial Partial 05/12/2010
Correction
Partial Correction
05/12/2010
WALL FRAMING + IN-WALL SYSTEMS SOUTH DEMISING WALL; NORTH DEMISING WALL; CROSSWALL @ 101 WEST; OK TO COVER WHEN READY WALLS LISTED BELOW:
All Rough Inspection - Commercial Passed 05/21/2010
Correction
Resolved
05/21/2010
WALL FRAMING + IN-WALL SYSTEMS SOUTH DEMISING WALL; NORTH DEMISING WALL; CROSSWALL @ 101 WEST; 102; 103 OK TO COVER WHEN READY WALLS LISTED BELOW:
Above Ceiling Inspection Passed 05/27/2010
Correction
Resolved
05/27/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS
All Rough Inspection - Commercial Passed 06/03/2010
Correction
Resolved
06/03/2010
WALL FRAMING + IN-WALL SYSTEMS SOUTH DEMISING WALL; NORTH DEMISING WALL; CROSSWALL @ 101 WEST; 102; 103 2ND FLOOR MEZZANINE/STORAGE WALL OK TO COVER WHEN READY WALLS LISTED BELOW:
Rough Framing Inspection - Commercial Request Complete 6/2/2010 6/3/2010 06/03/2010
Electrical Service Inspection Passed 06/17/2010
Correction
Resolved
06/17/2010
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE 277/480V 3P 4W > 45KVA XFMR> 120/208V 3P 4W 150A
Final Inspection - Commercial Partial 06/25/2010
Correction
Resolved
06/25/2010
ADDRESS LABELING OF RTU
Correction
Partial Correction
06/25/2010
REQUIRED ELECTRICAL RECEPTACLE OUTLET
Occupancy Inspection - Codes Commercial Failed 06/25/2010
Correction
Resolved
06/25/2010
Receive Fire Department approval PER CPT JOE DIR 6/24/2010
Correction
Corrective Action Required
06/25/2010
INSTALLATION OF FIXTURES SUBJECT TO APPROVAL WHEN COMPLETED
Correction
Partial Correction
06/25/2010
DESIGNATION OF ELECTRICAL SERVICE PANELS AFFIX PERMANENT LABELS IN PROGRESS
Correction
Corrective Action Required
06/25/2010
OCCUPANCY APPROVAL STATUS OK TO SET UP FOR BUSINESS NO PUBLIC BEFORE APPROVAL
Gas Piping Inspection - Commercial Passed 06/25/2010
Correction
Resolved
06/25/2010
PROTECTION OF METALLIC PIPE (OR TUBING) AGAINST CORROSION
Occupancy Inspection - Codes Commercial Passed 07/02/2010
Correction
Resolved
07/02/2010
INSTALLATION OF FIXTURES TERMINATIONS SUBJECT TO APPROVAL WHEN COMPLETED DISPLAY CABINET INSTALL IN PROGRESS BY OCCUPANT
Correction
Resolved
07/02/2010
DESIGNATION OF ELECTRICAL SERVICE PANELS
Correction
Resolved
07/02/2010
OCCUPANCY APPROVAL STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home