Permit Application Status

B1000158


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000158
Building Permit - Commercial
Final Completion
RED SUMMIT FAIR LLC
ALTERATION COMMERCIAL
WHITE BOX
02/26/2010
03/18/2010
09/14/2010
06/21/2010
Locations
Contacts
MEYER BROTHERS BUILDING COMPANY, Address:200 NE MISSOURI RD  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
MEYER BROTHERS BUILDING COMPANY, Address:200 NE MISSOURI RD  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/14/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - The existing corridor wall is a one-hour fire-resistive assembly. This is not indicated on the plans.
Correction

Codes Administration - Door 103 to the existing corridor is required to be rated for a minimum of 20 minutes.
Correction

Codes Administration - The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will be verified by the city inspection staff.
Correction

Fire Department- All plans submitted for review on or after July 9, 2007 shall be designed to the requirements of the 2006 International Building Code, 2006 International Mechanical Code, 2006 International Plumbing Code, 2006 International Fuel Gas Code, 2006 International Fire Code, 2005 National Electric Code and the ANSI A117.1-2003 as amended and adopted by the City of Lee's Summit.
Correction

Fire Department- 2006 IFC 1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. Exception: Doors, when fully opened, and handrails, shall not reduce the required width by more than 7 inches (178 mm). Doors in any position shall not reduce the required width by more than one-half. Other nonstructural projections such as trim and similar decorative features are permitted to project into the required width 1.5 inches (38 mm) on each side.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $229.28 $229.28 Paid 03/18/2010
89 Sewer Tap Fees $60.00 $60.00 Paid 03/18/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 03/24/2010
Correction
Partial Correction
03/24/2010
WALL FRAMING + IN-WALL SYSTEMS NORTH DEMISING WALL; ABOVE DOOR HEAD ELEVATION @ EAST WALL; OK TO COVER WHEN READY WALLS LISTED BELOW:
Final Inspection - Commercial Not Ready 03/24/2010
Correction
Corrective Action Required
03/24/2010
ADDRESS LABELING OF RTU
Gas Service Inspection - Commercial Passed 03/24/2010
Correction
Resolved
03/24/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Gas Piping Inspection - Commercial Partial 03/24/2010
Correction
Corrective Action Required
03/24/2010
PROTECTION OF METALLIC PIPE AGAINST CORROSION IFGC 404.8 EXPOSED ROOFTOP PIPING PAINT OR OTHER APPROVED
All Rough Inspection - Commercial Partial 04/07/2010
Correction
Partial Correction
04/07/2010
WALL FRAMING + IN-WALL SYSTEMS NORTH DEMISING WALL; ABOVE DOOR HEAD ELEVATION @ EAST WALL; SOUTH DEMISING WALL EXCEPT W 10'; BULKHEAD INSIDE E ENTRANCE; OK TO COVER WHEN READY WALLS LISTED BELOW:
Above Ceiling Inspection Partial 04/07/2010
Correction
Partial Correction
04/07/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS SOFFIT INSIDE E ENTRANCE; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Underslab Electrical Inspection - Commercial Passed 05/04/2010
Correction
Resolved
05/04/2010
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
Underslab Plumbing Inspection - Commercial Passed 05/04/2010
Correction
Resolved
05/04/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY OK TO COVER WHEN READY FOLLOWING SEGMENTS:
Electrical Service Inspection Passed 05/12/2010
Correction
Resolved
05/12/2010
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE NOTE: LABEL METER "880 G" (NOT L 107) BEFORE REQUESTING SERVICE ACTIVATION BY KCP&L 100A; 277/480V; 3P; 4W + XFRMR
All Rough Inspection - Commercial Passed 05/14/2010
Correction
Resolved
05/14/2010
WALL FRAMING + IN-WALL SYSTEMS NORTH DEMISING WALL; ABOVE DOOR HEAD ELEVATION @ EAST WALL; SOUTH DEMISING WALL; BULKHEAD INSIDE E ENTRANCE; RESTROOM AFTER ALL FRAMING CONNECTIONS FULLY SCREWED WITHIN WIDTH OF DOORWAY OK TO COVER WHEN READY WALLS LISTED BELOW:
Above Ceiling Inspection Passed 06/07/2010
Correction
Resolved
06/07/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY
Correction
Resolved
06/07/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS
Gas Piping Inspection - Commercial Passed 06/16/2010
Correction
Resolved
06/16/2010
PROTECTION OF METALLIC PIPE AGAINST CORROSION PAINTING IN PROGRESS
Final Inspection - Commercial Failed 06/16/2010
Correction
Partial Correction
06/16/2010
RESTROOM WALL FINISH NO BASE INSTALLED NOT PER APPROVED DRAWINGS BUT CODE COMPLIANT(EPOXY)
Correction
Corrective Action Required
06/16/2010
FINAL CLEAN-UP OF ROOFTOP REMOVE ALL DEBRIS AND UNUSED MATERIALS SUITE AREA + GAS PIPE ROUTE
Correction
Corrective Action Required
06/16/2010
ELECTRICAL RECEPTACLE @ HVAC RTU UNABLE TO TEST NOT HOT
Correction
Corrective Action Required
06/16/2010
PROTECTION OF EXTERIOR EXPOSED GAS PIPING FROM CORROSION IFGC 404.8 PAINTING IN PROGRESS SUBJECT TO APPROVAL
Correction
Corrective Action Required
06/16/2010
PERMANENT LABELING OF ELECTRICAL SERVICE METER AFFIX PERMANENT PLACARD DESIGNATE ADDRESS#/SUITE
Correction
Partial Correction
06/16/2010
Receive Fire Department approval CONTACT CPT JOE DIR PHONE 816-969-1317
Correction
Corrective Action Required
06/16/2010
ADDRESS LABELING OF RTU AFFIX PERMANENT LABEL ADDRESS/SUITE DESIGNATION
Final Inspection - Commercial Failed 06/17/2010
Correction
Resolved
06/17/2010
RESTROOM WALL FINISH CHANGED FROM FRP TO EPOXY PAINT REVISED PER A/E LETTER DATED JUNE 16, 2010
Correction
Resolved
06/17/2010
Receive Fire Department approval PER CPT JOE DIR 6/17/2010
Final Inspection - Commercial Passed 06/18/2010
Correction
Resolved
06/18/2010
CLOSE PERMIT
Correction
Resolved
06/18/2010
FINAL CLEAN-UP OF ROOFTOP
Correction
Resolved
06/18/2010
ELECTRICAL RECEPTACLE @ HVAC RTU
Correction
Resolved
06/18/2010
PROTECTION OF EXTERIOR EXPOSED GAS PIPING FROM CORROSION
Correction
Resolved
06/18/2010
PERMANENT LABELING OF ELECTRICAL SERVICE METER
Correction
Resolved
06/18/2010
ADDRESS LABELING OF RTU
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home