Permit Application Status

B1000130


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000130
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
FAJITA WILLYS TENANT FINISH
02/17/2010
03/23/2010
12/20/2010
06/25/2010
Locations
Contacts
ALLIED RETAIL CONCEPTS, Address:6200 MASTIN ST  
INTEGRITY PLUMBING SERVICES, LLC, Address:3801 SE VALLEY FORGE DR  
WESTERN LAFOLLETTE MECHANICAL, Address:956 OSAGE  
ROZIER ELECTRIC, INC., Address:1608 SW JEFFERSON  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/28/2010 10/29/2010
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1005.2 - Door encroachment. Doors opening into the path of egress travel shall not reduce the required width to less than one-half during the course of the swing. When fully open, the door shall not project more than 7 inches into the required width.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Correction

Codes Administration - I have found several locations where plywood sheathing is to be installed but I am unable to find any notation requiring it to be fire-treated.
Correction

Codes Administration - Cut sheets for the kitchen hoods have not been provided.
Correction

Codes Administration - Hood system 2 for the cheese melters, is shown to be a custom hood. It appears to be a Type II hood with an ANSL system.
Correction

Fire Department- 2006 IFC [M] 609.2 Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Correction

Fire Department- 2006 IFC904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system.
Correction

Fire Department-2006 IFC 907.14 Fire-extinguishing systems. Automatic fire-extinguishing systems shall be connected to the building fire alarm system where a fire alarm system is required by another section of this code or is otherwise installed.2006 IFC
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $747.32 $747.32 Paid 03/23/2010
89 Sewer Tap Fees $360.00 $360.00 Paid 03/23/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 04/01/2010
Correction
Resolved
04/01/2010
UNDER-SLAB GREASE WASTE PIPING OK TO COVER WHEN READY
Correction
Resolved
04/01/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
All Rough Inspection - Commercial Failed 04/14/2010
Correction
Corrective Action Required
04/14/2010
BULKHEAD/SOFFIT HANGING STRUCTURE INSIDE ENTRANCE 1) FULLY SCREW ALL FLANGE CONNECTIONS AT HANGING STRUCTURES 2) PROVIDE BACKING FOR STAND-OFFS AT ALL RECEPTACLE BOXES SEE ISSUES BELOW
Correction
Corrective Action Required
04/14/2010
TOP 4' OF N&S DEMISING WALLS HEADER SEVERED STUD ABOVE OFFICE @ N DEMISING WALL; HEADER SKEWED STUD @ S DEMISING WALL; OK TO COVER WHEN READY EXCEPT LOCATIONS BELOW
Miscellaneous Inspection Not Ready 04/14/2010
Correction
Corrective Action Required
04/14/2010
DESIGNATION OF SPECIALTY CONTRACTORS ON PERMIT NOT DESIGNATED BEFORE START OF WORK ELECTRICAL CONTRACTOR HVAC CONTRACTOR
All Rough Inspection - Commercial Partial 04/16/2010
Correction
Partial Correction
04/16/2010
WALL FRAMING + IN-WALL SYSTEMS ALL EXCEPT NEW EGRESS DOORWAY OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Resolved
04/16/2010
BULKHEAD/SOFFIT HANGING STRUCTURE INSIDE ENTRANCE
Correction
Resolved
04/16/2010
TOP 4' OF N&S DEMISING WALLS
Above Ceiling Inspection Partial 04/23/2010
Correction
Partial Correction
04/23/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS CLOUD CEILING ABOVE BAR; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Rated Assembly Inspection Partial 04/29/2010
Correction
Partial Correction
04/29/2010
GWB AT UL RATED WALLS PREP AREA BEYOND 10'-8" A.F.F. OK TO COVER WHEN READY WALL SECTIONS DESCRIBED:
Rated Assembly Inspection Passed 05/06/2010
Correction
Resolved
05/06/2010
GWB AT UL RATED WALLS OK TO APPLY FRP WHEN READY WEST WALL INTERIOR FACE PREP AREA
All Rough Inspection - Commercial Partial 05/06/2010
Correction
Partial Correction
05/06/2010
WALL FRAMING + IN-WALL SYSTEMS INCLUDING SHORT WALL AT DISPENSING OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Occupancy Inspection - Codes Commercial Not Ready 05/14/2010
Correction
Resolved
05/14/2010
UL LISTING OF LIGHTED SIGNS UL LABELS AFFIXED AS INDICATION OF LISTING
Correction
Corrective Action Required
05/14/2010
Receive Fire Department approval
Gas Service Inspection - Commercial Failed 05/18/2010
Correction
Corrective Action Required
05/18/2010
GAS PIPING PRESSURE TEST PRESSURIZE PIPING SYSTEM TO HOLD STEADY AT >= 10 PSI PRESSURE DECREASED DURING MONITORING PERIOD
Gas Piping Inspection - Commercial Failed 05/18/2010
Correction
Corrective Action Required
05/18/2010
PROTECTION OF EXTERIOR EXPOSED GAS PIPING FROM CORROSION IFGC 404.8 NOT PAINTED
Correction
Corrective Action Required
05/18/2010
SUPPORT OF RIGID STEEL PIPING IFGC 407.2 & 415: 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING SPACING OF BLOCKS/HANGERS HORIZONTAL RUNS
Correction
Corrective Action Required
05/18/2010
SUPPORT OF ROOFTOP GAS PIPING SECURE SLIPSHEETS TO SUPPORT BLOCKS
All Rough Inspection - Commercial Passed 05/18/2010
Correction
Resolved
05/18/2010
WALL FRAMING + IN-WALL SYSTEMS INCLUDING SHORT WALL AT DISPENSING AND SHORT WALL @ BAR OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Electrical Service Inspection Passed 05/18/2010
Correction
Resolved
05/18/2010
ELECTRICAL SERVICE INSTALLATION 250 AMPS @ PANEL RELEASE SERVICE
Gas Piping Inspection - Commercial Failed 05/26/2010
Correction
Corrective Action Required
05/26/2010
SUPPORT OF RIGID STEEL PIPING IFGC 407.2 & 415: 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING; SUPPORT PIPING NEAR CONNECTIONS; ALL BLOCKS TO BE IN FIRM CONTACT WITH PIPE AND WITH ROOF SURFACE. SPACING OF BLOCKS/HANGERS HORIZONTAL RUNS
Gas Service Inspection - Commercial Failed 05/26/2010
Correction
Corrective Action Required
05/26/2010
GAS PIPING INSPECTION NOT APPROVED SEE BELOW
Correction
Partial Correction
05/26/2010
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY TO LOAD SIDE ENTRY PIPE (NOT ON METER). PROVIDE IDENTIFICATION PRIOR TO INSPECTION REQUEST. APPLY PERMANENT TAG
Correction
Resolved
05/26/2010
GAS PIPING PRESSURE TEST PRESSURE HELD STEADY AT >= 30 PSI FOR >=20 MIN
Above Ceiling Inspection Passed 05/26/2010
Correction
Resolved
05/26/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS
Correction
Resolved
05/26/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AFTER TEMP ELECT REMOVED
Hood/Duct Inspection Failed 05/28/2010
Correction
Corrective Action Required
05/28/2010
LIGHT TEST OF GREASE DUCT
Hood/Duct Inspection Not Ready 05/28/2010
Correction
Corrective Action Required
05/28/2010
LIGHT TEST OF GREASE DUCT NOTE: CONTRARY TO DIRECTION, G.C. ALLOWED GREASE DUCT TO BE INSTALLED WITHOUT LIGHT TEST OF SHOP WELDS; THEREFORE ALL SHOP AND FIELD WELDS MUST BE LIGHT-TESTED IN PLACE. ACT CEILING INSTALLED DUCT NOT LEFT EXPOSED
Hood/Duct Inspection Passed 06/01/2010
Correction
Resolved
06/01/2010
LIGHT TEST OF GREASE DUCT
Gas Service Inspection - Commercial Passed 06/01/2010
Correction
Resolved
06/01/2010
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY TO LOAD SIDE ENTRY PIPE (NOT ON METER). PROVIDE IDENTIFICATION PRIOR TO INSPECTION REQUEST. APPLY PERMANENT TAG
Correction
Resolved
06/01/2010
GAS PIPING INSPECTION NOT APPROVED SEE BELOW
Gas Piping Inspection - Commercial Passed 06/04/2010
Correction
Resolved
06/04/2010
SUPPORT OF ROOFTOP GAS PIPING
Correction
Resolved
06/04/2010
SUPPORT OF RIGID STEEL PIPING
Correction
Resolved
06/04/2010
PROTECTION OF EXTERIOR EXPOSED GAS PIPING FROM CORROSION
Correction
Resolved
06/04/2010
See Comment - inspected on 2 June 2010.
Miscellaneous Inspection Passed 06/04/2010
Correction
Resolved
06/04/2010
DESIGNATION OF SPECIALTY CONTRACTORS ON PERMIT
Occupancy Inspection - Codes Commercial Failed 06/04/2010
Correction
Resolved
06/04/2010
Receive Fire Department approval
Correction
Corrective Action Required
06/04/2010
Service Panels - PLANS CALL FOR A SINGLE PANEL. CHANGED TO TWO (2) PANELS. SUBMIT REVISION TO PLANS EXAMINER. - LABEL PANELS.
Correction
Corrective Action Required
06/04/2010
Receive Water Utilities Approval - RECEIVE UNDER SEPARATE COVER.
Occupancy Inspection - Codes Commercial Failed 06/08/2010
Correction
Corrective Action Required
06/08/2010
Service Panels LABEL PANELS
Correction
Resolved
06/08/2010
Receive Water Utilities Approval
Occupancy Inspection - Codes Commercial Passed 06/24/2010
Correction
Resolved
06/24/2010
Service Panels LABEL SPARES/SPACES CORRECTLY. DESIGNATE RTU'S SPECIFICALLY. MAKE "LIGHTS" AS SPECIFIC AS POSSIBLE. CHECK PANEL SCHEDULES ENSURE ALL INFO CORRECT
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home