Permit Application Status

B1000113


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000113
Building Permit - Commercial
Certificate of Occupancy
CHANGE OF TENANT
CLOTHES MENTOR - TENANT FINISH
02/11/2010
03/04/2010
08/31/2010
03/19/2010
Locations
Contacts
REDLINE ELECTRIC LLC, Address:11918 A HWY  
VANUM CONSTRUCTION, Address:1400 KANSAS AVE  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/29/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Fire Department- Provide a Code Analysis.
Correction

Fire Department- All existing exit and emergency lighting shalll be maintained and operable.
Correction

Codes Administration - The plans do not provide details for the construction of the new walls.
Correction

Codes Administration - The plans do not provide any information on the electrical work to be performed.
Correction

Codes Administration - 2006 IBC 1109.12.1 - Dressing, fitting and locker rooms. Where dressing rooms, fitting rooms or locker rooms are provided, at least 5 percent, but not less than one, of each type of use in each cluster provided shall be accessible.
Correction

Codes Administration - Information is not provided on the new door being installed at the new office.
Correction

Codes Administration - Per the IBC, an office space is not required to be accessible but the path to that office is required to be accessible. The door to the new office space does not meet the clear floor space requirements.
Correction

Fire Department- Fire alarm notification appliances shall be extended/relocated in the space from the building fire alarm system.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $61.28 $61.28 Paid 03/04/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Passed 03/05/2010
Correction
Resolved
03/05/2010
WALL FRAMING + IN-WALL SYSTEMS FITTING; UTILITY OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Occupancy Inspection - Codes Commercial Passed 03/18/2010
Correction
Resolved
03/18/2010
Receive Fire Department approval RESOLVE REMAINING ISSUES DIRECTLY W/ CH. JIM EDEN
Correction
Resolved
03/18/2010
CODES ADMINISTRATION INSPECTION IDENTIFY ADDRESS NUMBER ON PERMANENT METAL TAG HANG ADDRESS TAG FROM GAS SERVICE ENTRY PIPE
Documents & Images
Date Uploaded File Type Document Name
08/13/2015 Activity Document DOC081315-001
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home