Summary
B1000048
Building Permit - Commercial
Certificate of Occupancy
CHANGE OF TENANT
UPTOWN RESALE - TENANT FINISH
01/22/2010
02/04/2010
09/28/2010
04/05/2010
Locations
Contacts
TEMP CON INC, Address:15670 S. KEELER  
WALTON CONSTRUCTION CO., INC., Address:3252 ROANOKE  
TEMP CON INC, Address:15670 S. KEELER  
TEMP CON INC, Address:15670 S KEELER ST  
TEMP CON INC, Address:15670 S KEELER ST  
DMA ELECTRIC, Address:7468 W 162ND TR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/01/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Fire Department- Provide an exit sign from the retail area to the second exit.
Correction

Fire Department- Provide remote reset/alarm/test for the duct detector.
Correction

Codes Administration - I am unable to locate details for the construction of the ceilings in the restrooms.
Correction

Codes Administration - As the space has two existing meters which serves this space, the meters shall be clearly marked to indicate that they both serve this space.
Correction

Codes Administration - 2006 IBC 1014.2.2 Exc. 2 - Means of egress are not prohibited through stockrooms in Group M occupancies when all of the following are met: 2.1 The stock is of the same hazard classification as that found in the main retail area: 2.2 Not more than 50 percent of the exit access is through the stockroom: 2.3 The stockroom is not subject to locking from the egress side: and 2.4 There is a demarcated, minimum 44-inch-wide aisle defined by full or partial height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstruction.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $334.18 $334.18 Paid 02/04/2010
89 Sewer Tap Fees $60.00 $60.00 Paid 02/04/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 02/11/2010
Correction
Resolved
02/11/2010
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
Underslab Plumbing Inspection - Commercial Not Ready 02/11/2010
Correction
Corrective Action Required
02/11/2010
READINESS FOR INSPECTION WORK REQUESTED FOR INSP NOT COMPLETED
Underslab Plumbing Inspection - Commercial Passed 02/12/2010
Correction
Resolved
02/12/2010
READINESS FOR INSPECTION
Correction
Resolved
02/12/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
All Rough Inspection - Commercial Passed 02/19/2010
Correction
Resolved
02/19/2010
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY
Rough Framing Inspection - Commercial Request Complete 2/18/2010 2/19/2010 02/19/2010
Above Ceiling Inspection Partial 02/25/2010
Correction
Partial Correction
02/25/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS BORDER ONLY AT SHOWROOM; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Passed 03/01/2010
Correction
Resolved
03/01/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 03/12/2010
Correction
Corrective Action Required
03/12/2010
Receive Fire Department approval PHONE 816-969-1317 COORDINATE W/ CPT JOE DIR RE. OUTSTANDING ISSUES
Correction
Corrective Action Required
03/12/2010
Receive Water Utilities Approval
Correction
Corrective Action Required
03/12/2010
ROOFTOP INSPECTION NO ACCESS PRESENTLY
Correction
Corrective Action Required
03/12/2010
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL. PER NEC 600-3
Correction
Corrective Action Required
03/12/2010
STRIPING OF EGRESS PATH @ STORAGE ROOM SUBJECT TO APPROVAL. WHEN COMPLETED
Correction
Corrective Action Required
03/12/2010
NO SMOKING SIGN/STICKER MUST BE AFFIXED AT ENTRANCE
Correction
Corrective Action Required
03/12/2010
USE / OCCUPANCY APPROVAL STATUS OK FOR FIXTURING/STOCKING NO PUBLIC UNTIL APPROVED
Occupancy Inspection - Codes Commercial Failed 03/16/2010
Correction
Resolved
03/16/2010
Receive Fire Department approval COORDINATE W/ CPT JOE DIR RE OUTSTANDING ISSUES
Correction
Resolved
03/16/2010
Receive Water Utilities Approval NO ISSUES FOUND PER BEN HASKAMP 3/12/2010
Correction
Resolved
03/16/2010
ROOFTOP INSPECTION RTU'S TO BE NUMBERED REFLECT #s IN ELEC PANEL
Correction
Partial Correction
03/16/2010
STRIPING OF EGRESS PATH @ STORAGE ROOM PREMATURE TRAFFIC LETTERING TOBE RE-PAINTED DUE TO DAMAGE FROM
Correction
Resolved
03/16/2010
NO SMOKING SIGN/STICKER
Correction
Partial Correction
03/16/2010
USE / OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Issue Temporary C of O Complete 3/15/2010 3/16/2010 03/16/2010
Occupancy Inspection - Codes Commercial Passed 04/02/2010
Correction
Resolved
04/02/2010
INSTALLATION OF LIGHTED SIGN
Correction
Resolved
04/02/2010
STRIPING OF EGRESS PATH @ STORAGE ROOM
Correction
Resolved
04/02/2010
USE / OCCUPANCY APPROVAL STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home