Permit Application Status

B1000011


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000011
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
MCALISTERS DELI TENANT FINISH
01/04/2010
01/21/2010
07/20/2010
03/31/2010
Locations
Contacts
ODOM & ASSOCIATES, Address:7701 WINDCREST DR, SUITE B  
ROYAL CONSTRUCTION AND MANAGEMENT, Address:PO BOX 547  
ACCU-TEMP INC, Address:200-A EAST SOUTH ST  
ACCU-TEMP INC, Address:200-A EAST SOUTH ST  
WESTHUES ELECTRIC INC., Address:4813 RAYTOWN RD  
ACCU-TEMP INC, Address:200-A EAST SOUTH ST  
ACCU-TEMP INC, Address:200-A EAST SOUTH ST  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/19/2010 10/29/2010
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - 2006 IMC 1003.3.1 - Grease interceptors and automatic grease removal devices required. A grease interceptor or automatic grease removal device shall be required to receive the drainage from fixtures and equipment with grease-laden waste located in food preparation areas, such as in restaurants, hotel kitchens, hospitals, school kitchens, bars, factory cafeterias and clubs. Fixtures and equipment shall include pot sinks, prerinse sinks; soup kettles or similar devices; wok stations; floor drains or sinks into which kettles are drained; automatic hood wash units and dishwashers without prerinse sinks. Grease interceptors and automatic grease removal devices shall receive waste only from fixtures and equipment that allow fats, oils or grease to be discharged.
Correction

Codes Administration - The plans indicate that the demising walls are to be constructed by the landlord. An application for this work has not been submitted or permitted.
Correction

Codes Administration - The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff.
Correction

Codes Administration - The grease drain indicated on the plumbing plans has been installed. A permit for the installation of a grease intercepter has not been applied for.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,978.20 $1,978.20 Paid 01/21/2010
89 Sewer Tap Fees $420.00 $420.00 Paid 01/21/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 01/27/2010
Correction
Resolved
01/27/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Correction
Resolved
01/27/2010
UNDER-SLAB GREASE WASTE PIPING WITHIN THIS SUITE OK TO COVER WHEN READY
Underslab Plumbing Inspection - Commercial Passed 01/28/2010
Underslab Electrical Inspection - Commercial Passed 01/28/2010
Correction
Resolved
01/28/2010
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
All Rough Inspection - Commercial Partial 02/03/2010
Correction
Partial Correction
02/03/2010
None - WEST WALL - OKAY TO ROCK - NORTH WALL - OKAY TO ROCK FROM EAST WALL TO MOP SINK LOCATION. West & North Walls
Correction
Partial Correction
02/03/2010
None - CONDUIT & J-BOXES (GROUNDED) FROM EAST WALL TO MOP SINK LOCATION. North Wall
All Rough Inspection - Commercial Partial 02/09/2010
Correction
Partial Correction
02/09/2010
IN WALL ROUGH ROOM 109 INCOMPLETE- LEFT OF MOP SINK-WEST REAR WALL AT COOLER. ALL OTHER WALL/ROOMS APPROVED ROUGH ELECTRICAL PARTIAL
Correction
Partial Correction
02/09/2010
ROUGH FRAMING PARTIAL FRAMING - REAR COOLER WALL AT (DOOR NEEDS MOVED) AND PANEL WALL INCOMPLETE. OTHER WALLS APPROVED IN WALL
Correction
Corrective Action Required
02/09/2010
Piping Support (IRC) SUPPORT AND PROTECT DWV AND PEX WATER PIPING AS PER CODE: NAIL PLATE PROTECTION AND SUPPORT PEX 36" VERTICAL IN WALL DO NOT COVER - WALLS WITH PLUMBING
All Rough Inspection - Commercial Partial 02/10/2010
Correction
Partial Correction
02/10/2010
ROUGH FRAMING PARTIAL FRAMING - REAR COOLER WALL AT (DOOR NEEDS MOVED) AND PANEL WALL INCOMPLETE. OTHER WALLS APPROVED IN WALL
Correction
Partial Correction
02/10/2010
Piping Support (IRC)
All Rough Inspection - Commercial Not Ready 02/19/2010
All Rough Inspection - Commercial Passed 02/23/2010
Correction
Resolved
02/23/2010
IN WALL ROUGH
Correction
Resolved
02/23/2010
ROUGH FRAMING
Correction
Resolved
02/23/2010
Piping Support (IRC)
Correction
Resolved
02/23/2010
WALL FRAMING + IN-WALL SYSTEMS OKTO COVER ALL WHEN READY INCLUDING N WALL W END
Correction
Resolved
02/23/2010
None
Correction
Resolved
02/23/2010
None
Above Ceiling Inspection Partial 03/10/2010
Correction
Partial Correction
03/10/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS KITCHEN 105; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Gas Service Inspection - Commercial Failed 03/10/2010
Correction
Corrective Action Required
03/10/2010
GAS PIPING PRESSURE TEST PRESSURIZE PIPING SYSTEM TO HOLD STEADY AT >= 10 PSI PRESSURE DECREASED DURING MONITORING PERIOD
Gas Piping Inspection - Commercial Failed 03/10/2010
Correction
Corrective Action Required
03/10/2010
PROTECTION OF ROOF MEMBRANE SLIP SHEETS NOT PLACED UNDER WOOD BLOCKS
Correction
Corrective Action Required
03/10/2010
PROTECTION OF EXTERIOR EXPOSED GAS PIPING FROM CORROSION OTHERWISE PROTECED FROM CORROSION ROOFTOP PIPING MUST BE PAINTED OR
Correction
Corrective Action Required
03/10/2010
ROOFTOP GAS PIPING SUPPORT BLOCKS IFGC 407 ENSURE ALL IN CONTACT WITH ROOF SURFACE
Electrical Service Inspection Passed 03/11/2010
Correction
Resolved
03/11/2010
ELECTRICAL SERVICE INSTALLATION ENSURE PANEL FRONT IS IN PLACE BEFORE SERVICE ACTIVATION. 400A / 480V / 3P RELEASE SERVICE
Gas Piping Inspection - Commercial Failed 03/15/2010
Correction
Corrective Action Required
03/15/2010
ROOFTOP GAS PIPING SUPPORT BLOCKS 1) ENSURE ALL IN CONTACT WITH ROOF SURFACE 2) CHECK SUPPORT SPACING: 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING IFGC 407 & 415
Gas Service Inspection - Commercial Passed 03/15/2010
Correction
Resolved
03/15/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE PRIOR TO OCCUPANCY INSPECTION APPLY PERMANENT ADDRESS TAG TO LOAD SIDE ENTRY PIPE (NOT ON METER). PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Above Ceiling Inspection Partial 03/17/2010
Correction
Partial Correction
03/17/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS KITCHEN 101; 102; 105; 106; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 03/19/2010
Correction
Partial Correction
03/19/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS KITCHEN 101; 102; 103 EXCEPT N-S CENTER 4' BELOW DIFFUSER YET TO BE INSTALLED AND CEILING SUPPORT TO BE CORRECTED; 105; 106; 113; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 03/23/2010
Correction
Partial Correction
03/23/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS KITCHEN 101; 102; 103 EXCEPT 4' ADJACENT TO DIFFUSER YET TO BE INSTALLED; 105; 106; 113; FROM KITCHEN TO REAR DOOR OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Occupancy Inspection - Codes Commercial Failed 03/25/2010
Correction
Corrective Action Required
03/25/2010
Receive Fire Department approval
Correction
Resolved
03/25/2010
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Corrective Action Required
03/25/2010
ROOFTOP INSPECTION CLEAR/CLEAN ALL DEBRIS AND UNUSED MATERIAL
Correction
Resolved
03/25/2010
UL LISTING OF LIGHTED SIGNS UL SHOP-LABELED PER NEC 600.3
Correction
Corrective Action Required
03/25/2010
ADDRESS LABELING OF ELECTRICAL SERVICE
Correction
Resolved
03/25/2010
ADDRESS LABELING OF GAS SERVICE
Correction
Corrective Action Required
03/25/2010
"NO SMOKING SIGNS" TO BE AFFIXED AT PUBLIC ENTRANCE DOORS
Correction
Corrective Action Required
03/25/2010
GLAZING OF OFFICE DOOR VISION PANEL MUST BE ETCHED "TEMPERED"
Correction
Corrective Action Required
03/25/2010
BACKFLOW PREVENTION AT WATER-FED EQUIPMENT LOCAL DEVICES REQUIRED COFFEE; TEA; ICE; STEAMER
Correction
Corrective Action Required
03/25/2010
USE / OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FOR BUSINESS NO PUBLIC ENTRY
Occupancy Inspection - Codes Commercial Failed 03/29/2010
Correction
Corrective Action Required
03/29/2010
Receive Fire Department approval SEE INSPECTION REPORT PROVIDED CONTACT CPT JOE DIR PHONE 816-969-1317
Correction
Resolved
03/29/2010
ROOFTOP INSPECTION
Correction
Resolved
03/29/2010
ADDRESS LABELING OF ELECTRICAL SERVICE
Correction
Resolved
03/29/2010
"NO SMOKING SIGNS"
Correction
Resolved
03/29/2010
GLAZING OF OFFICE DOOR VISION PANEL ETCHED "TEMPERED"
Correction
Resolved
03/29/2010
BACKFLOW PREVENTION AT WATER-FED EQUIPMENT
Correction
Partial Correction
03/29/2010
USE / OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Above Ceiling Inspection Passed 03/29/2010
Correction
Resolved
03/29/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS
Gas Piping Inspection - Commercial Passed 03/29/2010
Correction
Resolved
03/29/2010
PROTECTION OF ROOF MEMBRANE
Correction
Resolved
03/29/2010
PROTECTION OF EXTERIOR EXPOSED GAS PIPING FROM CORROSION
Correction
Resolved
03/29/2010
ROOFTOP GAS PIPING SUPPORT BLOCKS
Occupancy Inspection - Codes Commercial Passed 03/30/2010
Correction
Resolved
03/30/2010
Receive Fire Department approval PER CPT JOE DIR 3/30/2010
Correction
Resolved
03/30/2010
USE / OCCUPANCY APPROVAL STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home