Permit Application Status

B0901284


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0901284
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
COMPLETE TENANT FINISH FOR WOMENS CLOTHING STORE IN COLD SHELL
12/16/2009
02/08/2010
10/13/2010
04/19/2010
Locations
Contacts
MATTHEW DIX INC, Address:28710 FLINT ST  
ROZIER ELECTRIC, INC., Address:1608 SW JEFFERSON  
TRI-NORTH BUILDERS INC, Address:2625 RESEARCH PARK DR  
UNITED HEATING & COOLING, Address:301 DUCK RD  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/07/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1.Locations of alarm-initiating and notification appliances. 2. Manufacturers, model numbers and listing information for equipment, devices and materials. 3.The interface of fire safety control functions.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Correction

Codes Administration - The plans appear to have wall types D and D1 switched.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,151.75 $1,151.75 Paid 02/08/2010
89 Sewer Tap Fees $180.00 $180.00 Paid 02/08/2010
0120 Building Permit Fee ($1,151.75) ($1,151.75) $0.00 N/A
89 Sewer Tap Fees ($180.00) ($180.00) $0.00 N/A
0120 Building Permit Fee $1,151.75 $1,151.75 Paid 02/08/2010
89 Sewer Tap Fees $180.00 $180.00 Paid 02/08/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 02/12/2010
Correction
Resolved
02/12/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Underslab Electrical Inspection - Commercial Passed 02/12/2010
Correction
Resolved
02/12/2010
UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 02/19/2010
Correction
Partial Correction
02/19/2010
WALL FRAMING + IN-WALL SYSTEMS N & E FEATURE BAYS; 100 E & NE; 101; 102; 103; 104; 105; 106; 107; 108; 109; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 02/22/2010
Correction
Partial Correction
02/22/2010
WALL FRAMING + IN-WALL SYSTEMS N & E FEATURE BAYS; 100 E & NE; 101; 102; 103; 104; 105; 106; 107; 108; 109; 110; 111; 112; 113; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rated Assembly Inspection Partial 02/22/2010
Correction
Partial Correction
02/22/2010
GYPSUM WALLBOARD AT SOUTH DEMISING WALL OK TO COVER WHEN READY NORTH FACE ONLY SCREW PATTERN PER UL465
Rough Framing Inspection - Commercial Partial 02/22/2010
Correction
Partial Correction
02/22/2010
LIGHT GUAGE STEEL FRAMING WEST SOFFIT BEAM (AFTER 4 SEVERED STUDS ARE HEADERED-OFF); OK TO COVER WHEN READY FOLLOWING ELEMENTS:
All Rough Inspection - Commercial Partial 02/24/2010
Correction
Partial Correction
02/24/2010
WALL FRAMING + IN-WALL SYSTEMS N & E FEATURE BAYS; 100 E & NE; 101; 102; 103; 104; 105; 106; 107; 108; 109; 110; 111; 112; 113; STOREFRONT AREA WALLS S OF ENTRANCE; FURR-OUT FOR ELECT CONDUIT @ S WALL; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Partial 02/24/2010
Correction
Partial Correction
02/24/2010
LIGHT GUAGE STEEL FRAMING WEST SOFFIT BEAM; EAST SOFFIT BEAM; CEILING/PLATFORM FRAMING @ MGR'S OFC 110; OK TO COVER WHEN READY FOLLOWING ELEMENTS:
Above Ceiling Inspection Partial 03/01/2010
Correction
Partial Correction
03/01/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS MGR'S OFC 110; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
All Rough Inspection - Commercial Passed 03/02/2010
Correction
Resolved
03/02/2010
WALL FRAMING + IN-WALL SYSTEMS N & E FEATURE BAYS; 100 E & NE; 101; 102; 103; 104; 105; 106; 107; 108; 109; 110; 111; 112; 113; STOREFRONT AREA WALLS S OF ENTRANCE; FURR-OUT FOR ELECT CONDUIT @ S WALL; PERIMETER SOFFITS OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Above Ceiling Inspection Partial 03/05/2010
Correction
Partial Correction
03/05/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS MGR'S OFC 110; SALES AREA 100 E OF W SOFFIT BEAM EXCLUDING ALCOVE @ SE; FITTING AREA 101-108; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Passed 03/08/2010
Correction
Resolved
03/08/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS MGR'S OFC 110; SALES AREA 100 E OF W SOFFIT BEAM EXCLUDING ALCOVE @ SE; FITTING AREA 101-108; ALL WEST OF W SOFFIT BEAM OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Gas Piping Inspection - Commercial Passed 03/08/2010
Gas Service Inspection - Commercial Passed 03/08/2010
Correction
Resolved
03/08/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE. PERMANENT ADDRESS IDENTIFICATION TO BE COMPLETED PRIOR TO OCCUPANCY INSPECTION. PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Above Ceiling Inspection Partial 03/09/2010
Correction
Partial Correction
03/09/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS MGR'S OFC 110; SALES AREA 100 E OF W SOFFIT BEAM EXCLUDING ALCOVE @ SE; FITTING AREA 101-108; ALL WEST OF W SOFFIT BEAM EXCEPT ENTRANCE; RR 111; RR 112; CORRIDOR 113; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Rough Framing Inspection - Commercial Request Complete 3/8/2010 3/9/2010 03/09/2010
All Rough Inspection - Commercial Partial 03/10/2010
Correction
Partial Correction
03/10/2010
WALL FRAMING + IN-WALL SYSTEMS N & E FEATURE BAYS; 100 E & NE; 101; 102; 103; 104; 105; 106; 107; 108; 109; 110; 111; 112; 113; STOREFRONT AREA WALLS S OF ENTRANCE; FURR-OUT FOR ELECT CONDUIT @ S WALL; PERIMETER SOFFITS; FASCIA @ PERIMETER SOFFITS @ E & N ONLY OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Request Complete 3/9/2010 3/10/2010 03/10/2010
All Rough Inspection - Commercial Passed 03/11/2010
Correction
Resolved
03/11/2010
WALL FRAMING + IN-WALL SYSTEMS N & E FEATURE BAYS; 100 E & NE; 101; 102; 103; 104; 105; 106; 107; 108; 109; 110; 111; 112; 113; STOREFRONT AREA WALLS S OF ENTRANCE; FURR-OUT FOR ELECT CONDUIT @ S WALL; PERIMETER SOFFITS; FASCIA @ PERIMETER SOFFITS OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Above Ceiling Inspection Partial 03/11/2010
Correction
Partial Correction
03/11/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS MGR'S OFC 110; SALES AREA 100 E OF W SOFFIT BEAM INCLUDING ALCOVE @ SE; FITTING AREA 101-108; ALL WEST OF W SOFFIT BEAM EXCEPT ENTRANCE; RR 111; RR 112; CORRIDOR 113; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Electrical Service Inspection Not Ready 03/12/2010
Correction
Corrective Action Required
03/12/2010
READINESS FOR INSPECTION WORK REQUESTED FOR INSP NOT COMPLETED
Above Ceiling Inspection Partial 03/12/2010
Correction
Partial Correction
03/12/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS MGR'S OFC 110; SALES AREA 100 E OF W SOFFIT BEAM INCLUDING ALCOVE @ SE; FITTING AREA 101-108; ALL WEST OF W SOFFIT BEAM EXCLUDING ENTRANCE; RR 111; RR 112; CORRIDOR 113 OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Electrical Service Inspection Passed 03/15/2010
Correction
Resolved
03/15/2010
READINESS FOR INSPECTION
Correction
Resolved
03/15/2010
ELECTRICAL SERVICE INSTALLATION NOTE: BEFORE SERVICE IS ACTIVATED TIGHTEN BONDING LUG IN DISCONNECT CABINET 200A/3P/200AF RELEASE SERVICE
Above Ceiling Inspection Passed 03/15/2010
Correction
Resolved
03/15/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS MGR'S OFC 110; SALES AREA 100 E OF W SOFFIT BEAM INCLUDING ALCOVE @ SE; FITTING AREA 101-108; ALL WEST OF W SOFFIT BEAM EXCLUDING ENTRANCE; RR 111; RR 112; CORRIDOR 113; NORTHWEST ENTRANCE OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Occupancy Inspection - Codes Commercial Not Ready 04/12/2010
Correction
Partial Correction
04/12/2010
INSTALLATION OF LIGHTED SIGNS BRACKET AND LETTERS FOR WEST FACE; UL LABELING VERIFIED AT FOLLOWING ELEMENTS:
Occupancy Inspection - Codes Commercial Failed 04/13/2010
Correction
Partial Correction
04/13/2010
INSTALLATION OF LIGHTED SIGNS BRACKET AND LETTERS FOR WEST FACE; BRACKET AND LETTERS FOR NORTH FACE INSTALLATION IN PROGRESS UL LABELING VERIFIED AT FOLLOWING ELEMENTS:
Correction
Corrective Action Required
04/13/2010
Receive Fire Department approval SEE INSPECTION REPORT PROVIDED CONTACT CPT JOE DIR PHONE 816-969-1317
Correction
Corrective Action Required
04/13/2010
ELECTRICAL RECEPTACLE(S) AT WET LOCATIONS NEC 406.8; E3902.8 WEATHERPROOF COVER REQ'D ROOFTOP HVAC UNITS
Correction
Corrective Action Required
04/13/2010
IDENTIFICATION OF GAS SERVICE ENTRY FELT-TIP MARKER NOT PERMANENT APPLY PERMANENT STAMP ON METAL TAG
Correction
Corrective Action Required
04/13/2010
DISPLAY OF "NO SMOKING" SIGN(S) LS CODE OF ORDINANCES 17-309: SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY NOT YET AFFIXED AT PUBLIC ENTRY(IES)
Correction
Partial Correction
04/13/2010
USE / OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FOR BUSINESS NO PUBLIC ENTRY
Miscellaneous Inspection Passed 04/14/2010
Occupancy Inspection - Codes Commercial Passed 04/16/2010
Correction
Resolved
04/16/2010
INSTALLATION OF LIGHTED SIGNS
Correction
Resolved
04/16/2010
Receive Fire Department approval PER CPT JOE DIR 4/16/2010
Correction
Resolved
04/16/2010
ELECTRICAL RECEPTACLE(S) AT WET LOCATIONS
Correction
Resolved
04/16/2010
IDENTIFICATION OF GAS SERVICE ENTRY
Correction
Resolved
04/16/2010
DISPLAY OF "NO SMOKING" SIGN(S)
Correction
Resolved
04/16/2010
USE / OCCUPANCY APPROVAL STATUS
Rated Assembly Inspection Passed 04/16/2010
Correction
Resolved
04/16/2010
GYPSUM WALLBOARD AT SOUTH DEMISING WALL
Rough Framing Inspection - Commercial Passed 04/16/2010
Correction
Resolved
04/16/2010
LIGHT GUAGE STEEL FRAMING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home