Permit Application Status

B0901235


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0901235
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
NEW RETAIL TENANT FINISH, SALE OF SHOES AND ACCESSORIES
12/04/2009
01/04/2010
10/03/2010
04/13/2010
Locations
Contacts
TEMP CON INC, Address:15670 S. KEELER  
DAVIS WINCE, Address:1466 MANNING PKWY  
BRIGHT PLUMBING, Address:220 NW COMMERCE CT  
HEARTLAND RETAIL CONSTRUCTION, Address:4956 MEMCO LANE  
COMERCIAL PERMITS, INC, Address:2620 63RD ST  
C M MOSE AND SON INC, Address:6603 E ROYAL ST  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/06/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $3,165.12 $3,165.12 Paid 01/04/2010
89 Sewer Tap Fees $240.00 $240.00 Paid 01/04/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 01/07/2010
Correction
Resolved
01/07/2010
None UNDERSLAB COMPLETE
All Rough Inspection - Commercial Partial 01/12/2010
Correction
Partial Correction
01/12/2010
FRAMING & ELECTRICAL ROUGH-IN AT SALES AREA EXTERIOR WALLS ADDITIONAL DISPLAY WALLS TO BE CONSTRUCTED SUBSEQUENTLY. N, E, & S WALLS OK TO COVER WHEN READY
All Rough Inspection - Commercial Passed 01/19/2010
Correction
Resolved
01/19/2010
FRAMING & ELECTRICAL ROUGH-IN AT SALES AREA EXTERIOR WALLS INCLUDING DISPLAY WALLS N, E, & S WALLS OK TO COVER WHEN READY
Correction
Resolved
01/19/2010
WALL FRAMING + IN-WALL SYSTEMS IPC 305.8: INSTALL SHIELD PLATES AT STUDS & TRACKS. SHIELD PLATES SHALL COVER THE AREA OF THE PIPE WHERE PVC OR COPPER PIPING IS LESS THAN 1-1/2" FROM FACE OF FRAMING. OK TO COVER WHEN READY AFTER SHIELD PLATES DONE
Electrical Service Inspection Passed 01/19/2010
Above Ceiling Inspection Partial 01/22/2010
Correction
Partial Correction
01/22/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS 102; 104; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
All Rough Inspection - Commercial Passed 02/03/2010
Correction
Resolved
02/03/2010
FRAMING & ELECTRICAL ROUGH-IN AT SALES AREA EXTERIOR WALLS INCLUDING DISPLAY WALLS WITH 4' REVISION TOP EXTENSIONS N, E, & S WALLS OK TO COVER WHEN READY
Rough Framing Inspection - Commercial Partial 02/04/2010
Correction
Partial Correction
02/04/2010
FRAMING OF HANGING SOFFIT STRUCTURE @ SE CORNER HANGING FROM BOTTOM CHORD OF BAR JOIST NOT APPROVED UNLESS A/E DOCUMENTS ANALYSIS THEREOF. LIGHT GUAGE FRAMING OK RESOLVE SUPPORT ISSUE
Gas Service Inspection - Commercial Passed 02/10/2010
Correction
Resolved
02/10/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Gas Piping Inspection - Commercial Failed 02/10/2010
Correction
Corrective Action Required
02/10/2010
SUPPORT OF ROOFTOP GAS PIPING IF VARIANCE IS TO BE ALLOWED BY A/E FORWARD DOCUMENTATION TO INSPECTOR. ALSO, PER IFGC 415: MAXIMUM SUPPORT SPACING FOR 1/2" PIPE IS 6'; MAX SUPPORT SPACING FOR 3/4" & 1' PIPE IS 8' BLOCKS NOT PER DRAWING CONFIRM VARIANCE WITH A/E
Correction
Corrective Action Required
02/10/2010
PROTECTION OF ROOFTOP GAS PIPING FROM CORROSION IFGC 404.8 MUST BE PAINTED OR OTHERWISE PROTECTED
Rough Framing Inspection - Commercial Passed 02/10/2010
Correction
Resolved
02/10/2010
FRAMING OF HANGING SOFFIT STRUCTURE @ SE CORNER
Gas Piping Inspection - Commercial Failed 03/04/2010
Correction
Corrective Action Required
03/04/2010
SUPPORT OF ROOFTOP GAS PIPING IF VARIANCE IS TO BE ALLOWED BY A/E FORWARD DOCUMENTATION TO INSPECTOR. BLOCKS NOT PER DRAWING CONFIRM VARIANCE WITH A/E
Correction
Corrective Action Required
03/04/2010
SUPPORT SPACING FOR ROOFTOP GAS PIPING PER IFGC 415: MAXIMUM SUPPORT SPACING FOR 1/2" PIPE IS 6'; MAX SUPPORT SPACING FOR 3/4" & 1" PIPE IS 8' CHECK / ADJUST SPACING
Rough Electrical Inspection - Commercial Partial 03/05/2010
Correction
Partial Correction
03/05/2010
COURTESY VISIT TO DISCUSS EGRESS LIGHTING
Above Ceiling Inspection Partial 03/19/2010
Correction
Resolved
03/19/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS 102; 104; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Correction
Partial Correction
03/19/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 101; 104; 106 OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Occupancy Inspection - Codes Commercial Failed 03/31/2010
Correction
Resolved
03/31/2010
Receive Fire Department approval PER CPT JOE DIR 3/31/2010
Correction
Corrective Action Required
03/31/2010
DISPLAY OF "NO SMOKING SIGN" AFFIX AT PUBLIC ENTRY DOOR OR SIDELIGHT
Correction
Corrective Action Required
03/31/2010
ROOFTOP GAS PIPING 1) ENSURE ALL BLOCKS IN CONTACT WITH ROOF SURFACE 2) ENSURE ALL WOOD BLOCKS HAVE SLIP SHEETS (ATTACH IF THIN) 3) WHERE BLOCKS ARE STACKED, FASTEN TOGETHER UNIT HEATER BRANCH ISSUES BELOW:
Correction
Corrective Action Required
03/31/2010
CONVENIENCE RECEPTS AT RTU's INCLUDING TESTING OF GFCI PROTECTION TO BE VERIFIED AT RE-INSPECTION
Correction
Corrective Action Required
03/31/2010
FINAL CLEANUP OF ROOFTOP FROM SUITE ROOF AREA CLEAR/CLEAN ALL DEBRIS AND UNUSED MATERIAL
Correction
Corrective Action Required
03/31/2010
RECEPTACLE NEAR ELECT GEAR AT REAR TESTS HOT/NEUTRAL REVERSE
Occupancy Inspection - Codes Commercial Failed 04/02/2010
Correction
Corrective Action Required
04/02/2010
INSTALLATION OF LIGHTED SIGN PER NEC 600-3: SUBJECT TO NATIONAL 2005 ELECTRICAL CODE. IF INTERNALLY LIGHTED > 12V MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN. SUBJECT TO APPROVAL. WHEN INSTALLED
Occupancy Inspection - Codes Commercial Passed 04/07/2010
Correction
Resolved
04/07/2010
DISPLAY OF "NO SMOKING SIGN"
Correction
Resolved
04/07/2010
ROOFTOP GAS PIPING
Correction
Resolved
04/07/2010
CONVENIENCE RECEPTS AT RTU's
Correction
Resolved
04/07/2010
FINAL CLEANUP OF ROOFTOP
Correction
Resolved
04/07/2010
RECEPTACLE NEAR ELECT GEAR AT REAR
Correction
Resolved
04/07/2010
INSTALLATION OF LIGHTED SIGN
Rough Electrical Inspection - Commercial Passed 04/09/2010
Correction
Resolved
04/09/2010
COURTESY VISIT TO DISCUSS EGRESS LIGHTING
Above Ceiling Inspection Passed 04/09/2010
Correction
Resolved
04/09/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS
Gas Piping Inspection - Commercial Passed 04/09/2010
Correction
Resolved
04/09/2010
SUPPORT OF ROOFTOP GAS PIPING
Correction
Resolved
04/09/2010
PROTECTION OF ROOFTOP GAS PIPING FROM CORROSION
Correction
Resolved
04/09/2010
SUPPORT SPACING FOR ROOFTOP GAS PIPING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home