Permit Application Status

B0901191


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0901191
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
SAINT LUKES 3RD CORE INFILL. SPACE WILL BE UTILIZED AS A PHARMACY AND MEETING/TRAINING ROOMS.
11/17/2009
12/23/2009
06/21/2010
05/24/2010
Locations
Contacts
SHAW ELECTRIC COMPANY, Address:3600 FULLER AVE  
P1 GROUP INC, Address:16210 WEST 108TH ST  
P1 GROUP INC, Address:16210 WEST 108TH ST  
P1 GROUP INC, Address:16210 WEST 108TH ST  
P1 GROUP INC, Address:16210 WEST 108TH ST  
ACI BOLAND, Address:11229 NALL SUITE 140  
J.E. DUNN CONSTRUCTION. INC, Address:1570 NE DOUGLAS RD  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/19/2010 10/29/2010
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department: Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators, and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Documentation shall be provided of the pressure test of at least 150 psi for a minimum of 24 hours on installers letterhead.
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

Codes Administration - 2006 IBC 1008.1.2 - Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2. Group I-3 occupancies used as a place of detention. 3. Critical or intensive care patient rooms within suites of health care facilities. 4. Doors within or serving a single dwelling unit in Groups R-2 and R-3. 5. In other than Group H occupancies, revolving doors complying with Section 1008.1.3.1. 6. In other than Group H occupancies, horizontal sliding doors complying with Section 1008.1.3.3 are permitted in a means of egress. 7. Power-operated doors in accordance with Section 1008.1.3.2. 8. Doors serving a bathroom within an individual sleeping unit in Group R-1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force of interior side-swinging doors without closers shall not exceed a 5-pound force. For other side-swinging, sliding and folding doors, the door latch shall relase when subjected to a 15-pound force. The door shall be set in motion when subjected to a 30-pound force. The door shall swing to a full-open position when subjected to a 15-pound force. Forces shall be applied to the latch side.
Correction

Codes Administration - 2006 IBC 1008.1.9 - Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds. Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Gourp A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equiped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side.
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Correction

Fire Department- 2006 IFC 1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building.
Correction

Fire Department- IFC 907.4.1 Location. Manual fire alarm boxes shall be located not more than 5 feet (1524 mm) from the entrance to each exit. Additional manual fire alarm boxes shall be located so that travel distance to the nearest box does not exceed 200 feet (60 960 mm).
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $7,910.32 $7,910.32 Paid 12/23/2009
Road and Bridge Escrow $4,223.67 $4,223.67 Paid 01/27/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Framing Inspection - Commercial Partial 01/04/2010
Correction
Partial Correction
01/04/2010
PREPARATION TO TOP-OUT WALLS {013; CORRIDOR WALL ALONG (C) LINE; 072 SOUTH WALL} TOP-OUT CONTINGENT ON APPROVAL OF M/E/P BOX-AROUNDS YET TO BE RESOLVED AND FRAMED;
Rough Framing Inspection - Commercial Request Complete 12/30/2009 1/4/2010 01/04/2010
All Rough Inspection - Commercial Partial 01/08/2010
Correction
Partial Correction
01/08/2010
PREPARATION TO TOP-OUT WALLS {013; CORRIDOR WALL ALONG (C) LINE; 072 SOUTH WALL} TOP-OUT CONTINGENT ON APPROVAL OF M/E/P BOX-AROUNDS YET TO BE RESOLVED AND FRAMED; S WALLS OF 009, 011, 013;
Rated Assembly Inspection Partial 01/08/2010
Correction
Partial Correction
01/08/2010
GWB AT UL RATED WALLS {CORRIDOR 070 W WALL FROM (8.8) TO (11.8); 072 S WALL N FACE FROM (C.2) TO (D)} TOP-OUT CONTINGENT ON APPROVAL OF M/E/P BOX-AROUNDS YET TO BE RESOLVED AND FRAMED; OK TO COVER WHEN READY WALL SEGMENTS BELOW:
Rough Framing Inspection - Commercial Passed 01/08/2010
Correction
Resolved
01/08/2010
PREPARATION TO TOP-OUT WALLS SEE IN-WALL INSPECTION RECORDED @ "ALL-ROUGH"
Rated Assembly Inspection Partial 01/13/2010
Correction
Partial Correction
01/13/2010
GWB AT UL RATED WALLS {CORRIDOR 070 W WALL FROM (8.8) TO (11.8) + (12.4) TO (12.9) ; 072 S WALL N FACE FROM (C.2) TO (D)} TOP-OUT CONTINGENT ON APPROVAL OF M/E/P BOX-AROUNDS YET TO BE RESOLVED AND FRAMED; OK TO COVER WHEN READY WALL SEGMENTS BELOW:
All Rough Inspection - Commercial Partial 01/15/2010
Correction
Partial Correction
01/15/2010
PREPARATION TO TOP-OUT WALLS 013; CORRIDOR WALL ALONG (C) LINE; 072 SOUTH WALL; S WALLS OF 009, 011, 013, 010, 012, 014, 072; W WALL OF 012; E WALL OF 001, 002, 003; OK TO ONE-SIDE GWB AT WALLS DESCRIBED BELOW:
Rough Framing Inspection - Commercial Request Complete 1/14/2010 1/15/2010 01/15/2010
Rated Assembly Inspection Partial 01/22/2010
Rough Framing Inspection - Commercial Partial 01/22/2010
Correction
Partial Correction
01/22/2010
PREPARATION TO TOP-OUT WALLS SEE IN-WALL INSPECTION RECORDED @ "ALL-ROUGH"
Rough Framing Inspection - Commercial Request Complete 1/21/2010 1/22/2010 01/22/2010
All Rough Inspection - Commercial Partial 01/25/2010
Correction
Partial Correction
01/25/2010
PREPARATION TO TOP-OUT WALLS ALL INTERIOR WALLS OK FOR ONE-SIDE GWB TOP-OUT
Rated Assembly Inspection Partial 01/25/2010
Correction
Partial Correction
01/25/2010
GWB AT UL RATED WALLS {CORRIDOR 070 W WALL FROM (8.8) TO (11.8) + (12.4) TO (12.9) ; 072 S WALL N FACE FROM (C.2) TO (D)} TOP-OUT CONTINGENT ON APPROVAL OF M/E/P BOX-AROUNDS YET TO BE RESOLVED AND FRAMED; TOP-OUT ON (7) FROM (A) TO (B.7) N FACE; OK TO COVER WHEN READY WALL SEGMENTS BELOW:
All Rough Inspection - Commercial Partial 01/29/2010
Correction
Resolved
01/29/2010
PREPARATION TO TOP-OUT WALLS ALL INTERIOR WALLS OK FOR ONE-SIDE GWB TOP-OUT
Correction
Partial Correction
01/29/2010
WALL FRAMING + IN-WALL SYSTEMS 002; 003; 004; 005; 006; 008; 009; 010; 011; 011A; 012; 013; 014; 071; 073; 075; 076; 077; 078; 079; 080; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rated Assembly Inspection Partial 02/03/2010
Correction
Partial Correction
02/03/2010
GWB AT UL RATED WALLS ON (7) FROM (A) TO (B.7) BOTH FACES; ON (12.9) FROM (A) TO (B.8) SOUTH FACE ONLY; 072 S WALL N FACE FROM (C.2) TO (D)} TOP-OUT; OK TO COVER WHEN READY WALL SEGMENTS BELOW:
All Rough Inspection - Commercial Partial 02/03/2010
Correction
Partial Correction
02/03/2010
WALL FRAMING + IN-WALL SYSTEMS 002; 003; 004; 005; 006; 008; 009; 010; 011; 011A; 012; 013; 014; 071; 073; 075; 076; 077; 078; 079; 080; CORR 064+070 W WALL FROM (7) TO (12.6) CORR FACE ONLY; ELEV LOBBY 001 WALLS + HANGING SOFFITS; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 02/09/2010
Correction
Partial Correction
02/09/2010
WALL FRAMING + IN-WALL SYSTEMS 002; 003; 004; 005; 006; 008; 009; 010; 011; 011A; 012; 013; 014; 071; 073; 075; 076; 077; 078; 079; 080; CORR 064+070 W WALL FROM (7) TO (12.6) CORR FACE ONLY; ELEV LOBBY 001 WALLS + HANGING SOFFITS;(12.9)TO(7) INSIDE CORRWALL.(3A070-3A064-3A000B); OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rated Assembly Inspection Partial 02/09/2010
Correction
Partial Correction
02/09/2010
GWB AT UL RATED WALLS ON (7) FROM (A) TO (B.7) BOTH FACES; ON (12.9) FROM (A) TO (B.8) SOUTH FACE ONLY; 072 S WALL N FACE FROM (C.2) TO (D)} TOP-OUT; ON 7(3A070)LOWER SECTIONSCREW PATT 12.9; OK TO COVER WHEN READY WALL SEGMENTS BELOW:
All Rough Inspection - Commercial Partial 02/16/2010
Correction
Partial Correction
02/16/2010
WALL FRAMING + IN-WALL SYSTEMS 002; 003; 004; 005; 006; 008; 009; 010; 011; 011A; 012; 013; 014; 071; 073; 075; 076; 077; 078; 079; 080; CORR 064+070 W WALL FROM (7) TO (12.6) CORR FACE ONLY; ELEV LOBBY 001 WALLS + HANGING SOFFITS;(12.9)TO(7) INSIDE CORRWALL.(3A070-3A064-3A000B); OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Partial Correction
02/16/2010
WALL FRAMING + IN WALL SYSTEMS IN WALL FROM 7 LINE TO 13.1 LINES APPROVED FOR 1ST LAYER. OKAY TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rated Assembly Inspection Partial 02/16/2010
Correction
Partial Correction
02/16/2010
GWB AT UL RATED WALLS ON (7) FROM (A) TO (B.7) BOTH FACES; ON (12.9) FROM (A) TO (B.8) SOUTH FACE ONLY; 072 S WALL N FACE FROM (C.2) TO (D)} TOP-OUT; ON 7(3A070)LOWER SECTIONSCREW PATT 12.9; N SIDE OF 12 LINE OK TO COVER WHEN READY WALL SEGMENTS BELOW:
Rough Framing Inspection - Commercial Request Complete 2/12/2010 2/16/2010 02/16/2010
Rated Assembly Inspection Partial 02/19/2010
Correction
Partial Correction
02/19/2010
GWB AT UL RATED WALLS ON (7) FROM (A) TO (B.7) BOTH FACES; ON (12.9) FROM (A) TO (B.8) SOUTH FACE ONLY; 072 S WALL N FACE FROM (C.2) TO (D)} TOP-OUT; ON 7(3A070)LOWER SECTIONSCREW PATT 12.9; N SIDE OF 12 LINE; 060/062/066 S&E&N WALLS; 068 N&S WALLS; 072 S WALL; OK TO COVER WHEN READY WALL SEGMENTS BELOW:
All Rough Inspection - Commercial Partial 02/22/2010
Correction
Partial Correction
02/22/2010
WALL FRAMING + IN WALL SYSTEMS IN WALL FROM 7 LINE TO 13.1 LINES APPROVED FOR 1ST LAYER; CORR 00A BOTH FACES @ BOTH WALLS; OKAY TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rated Assembly Inspection Partial 03/03/2010
Correction
Partial Correction
03/03/2010
GWB AT UL RATED WALLS ON (7) FRM (A) TO (B.7) BOTH FACES; ON (12.9) FRM (A) TO (B.8) S FACE ONLY; ON 7(3A070)LOWER SECTION SCREW PATT 12.9; N SIDE OF (12); 060/062/066 S&E&N WALLS; 068 N&S WALLS; 072 S WALL; CORR 20 N WALL BOTH FACES; OK TO COVER WHEN READY WALL SEGMENTS BELOW:
Above Ceiling Inspection Partial 03/10/2010
Correction
Partial Correction
03/10/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 002; 003; 004; 005; 006; 008; 009; 010; 011; 011A; 012; 013; 014; 075; 076; 078; 079; 080; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 03/11/2010
Correction
Partial Correction
03/11/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 001; 002-006; 008-011; 011A; 012-014; 060; 062; 064; 066; 070; 071; 072; 075; 076; 078-080; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 03/18/2010
Correction
Partial Correction
03/18/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 00A; 001; 002-006; 008-011; 011A; 012-014; 020; 060; 062; 064; 066; 070; 071; 072; 075; 076; 078-080; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 03/18/2010
Occupancy Inspection - Codes Commercial Not Ready 04/13/2010
Correction
Corrective Action Required
04/13/2010
Receive Fire Department approval
Rated Assembly Inspection Passed 04/13/2010
Correction
Resolved
04/13/2010
GWB AT UL RATED WALLS ON (7) FRM (A) TO (B.7) BOTH FACES; ON (12.9) FRM (A) TO (B.8) S FACE ONLY; ON 7(3A070)LOWER SECTION SCREW PATT 12.9; N SIDE OF (12); 060/062/066 S&E&N WALLS; 068 N&S WALLS; 072 S WALL; CORR 20 N WALL BOTH FACES; OK TO COVER WHEN READY WALL SEGMENTS BELOW:
Above Ceiling Inspection Passed 04/13/2010
Correction
Resolved
04/13/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 00A; 001; 002-006; 008-011; 011A; 012-014; 020; 060; 062; 064; 066; 070; 071; 072; 075; 076; 078-080; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
All Rough Inspection - Commercial Passed 04/13/2010
Correction
Resolved
04/13/2010
WALL FRAMING + IN-WALL SYSTEMS 002; 003; 004; 005; 006; 008; 009; 010; 011; 011A; 012; 013; 014; 071; 073; 075; 076; 077; 078; 079; 080; CORR 064+070 W WALL FROM (7) TO (12.6) CORR FACE ONLY; ELEV LOBBY 001 WALLS + HANGING SOFFITS;(12.9)TO(7) INSIDE CORRWALL.(3A070-3A064-3A000B); OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Resolved
04/13/2010
WALL FRAMING + IN WALL SYSTEMS IN WALL FROM 7 LINE TO 13.1 LINES APPROVED FOR 1ST LAYER; CORR 00A BOTH FACES @ BOTH WALLS; OKAY TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Passed 04/13/2010
Correction
Resolved
04/13/2010
PREPARATION TO TOP-OUT WALLS SEE IN-WALL INSPECTION RECORDED @ "ALL-ROUGH"
Miscellaneous Inspection Partial 04/14/2010
Correction
Partial Correction
04/14/2010
PRE-FINAL OBSERVATIONS
Occupancy Inspection - Codes Commercial Failed 04/16/2010
Correction
Partial Correction
04/16/2010
Receive Fire Department approval NO OPERATION BEFORE APPROVAL. OK FOR CONTENTS
Correction
Resolved
04/16/2010
OPERATION OF EMERGENCY ELECTRICAL RECEPTACLES TESTED FOR CURRENT WITH NORMAL POWER OFF
Correction
Corrective Action Required
04/16/2010
ROOM SIGNAGE INCLUDING ACCESSIBLE YET TO BE AFFIXED
Correction
Resolved
04/16/2010
PADDING OF PIPING UNDER SINKS NOT REQUIRED BY ANSI DUE TO SETBACK >= 8"
Correction
Resolved
04/16/2010
ELECTRICAL PANEL SCHEDULES "SPARES" TO BE DESIGNATED COMPLETED
Correction
Corrective Action Required
04/16/2010
ACCESS TO FIRE DAMPER @ SPACE 013 ACCESS PANEL LOCATION NOT AT F.D. LOCATION
Correction
Resolved
04/16/2010
DUCT HANGERS @ SPACE 077 EXCESS ALL-THREAD LENGTH ENDS CUT OFF
Correction
Corrective Action Required
04/16/2010
USE / OCCUPANCY APPROVAL STATUS SEE FIRE DEPARTMENT ISSUES REGARDING ELEVATORS. OKTO SET UP FOR OPERATION NOTAPPROVED FOR OPERATION
Miscellaneous Inspection Passed 04/16/2010
Correction
Resolved
04/16/2010
PRE-FINAL OBSERVATIONS
Occupancy Inspection - Codes Commercial Passed 05/21/2010
Correction
Resolved
05/21/2010
Receive Fire Department approval
Correction
Resolved
05/21/2010
OPERATION OF EMERGENCY ELECTRICAL RECEPTACLES
Correction
Resolved
05/21/2010
ROOM SIGNAGE
Correction
Resolved
05/21/2010
PADDING OF PIPING UNDER SINKS
Correction
Resolved
05/21/2010
ELECTRICAL PANEL SCHEDULES
Correction
Resolved
05/21/2010
ACCESS TO FIRE DAMPER @ SPACE 013
Correction
Resolved
05/21/2010
DUCT HANGERS @ SPACE 077
Correction
Resolved
05/21/2010
USE / OCCUPANCY APPROVAL STATUS
Rated Assembly Inspection Partial 09/07/2010
Correction
Partial Correction
09/07/2010
None - OKAY TO TAPE BOTH SIDES. NEITHER SIDE FIREBLOCKED. Dividing Wall
Above Ceiling Inspection Passed 09/22/2010
Correction
Resolved
09/22/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 00A; 001; 002-006; 008-011; 011A; 012-014; 020; 060; 062; 064; 066;68A; 070; 071; 072; 075; 076; 078-080; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Rated Assembly Inspection Passed 09/30/2010
Correction
Resolved
09/30/2010
None Dividing Wall
Occupancy Inspection - Codes Commercial Passed 09/30/2010
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home