Permit Application Status

B0901120


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0901120
Building Permit - Commercial
Certificate of Occupancy
GMRI INC
NEW COMMERCIAL
OLIVE GARDEN RESTAURANT
11/02/2009
02/22/2010
01/25/2011
08/02/2010
Locations
Contacts
UNIVERSAL ELECTRIC, Address:PO BOX 3628  
GHA ARCHITECTS, Address:14110 N DALLAS PKWY, STE 100  
COMPLETE COMFORT HTG & CLG LLC, Address:714 NW 201 RD  
CRHO ARCHITECTS, Address:195 S. C STREET, STE 200  
MUNLAKE CONTRACTING, Address:1551 N COURTNEY RD  
TAYLOR MECHANICAL, INC., Address:PO BOX 2064  
GMRI INC, Address:1000 DARDEN CENTER DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/19/2010 10/29/2010
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm). Exception: Clearance shall not be required from gypsum wallboard attaced to noncombustible structures provided that a smooth, cleanable, nonabsorbant and noncumbustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inces (457 mm) in all directions from the hood.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Fire Department- If the dumpster enclosure is to be covered, sprinkler protection shall be extended to protect it.
Correction

Codes Administration - I have included a 2 inch domestic water tap and meter setup to the permit for this project. I am not sure if the 1 inch irrigation tap is to be part of the permit to the general contractor or if it is the responsiblility of the irrigation contractor.
Correction

Codes Administration - The irrigation plans show a one inch meter located along Chipman Rd. Per conversations with the Public Works Department, I don't believe it is possible to tap this main due to its size.
Correction

Codes Administration - The domestic water service for this building is shown to run across the north end of the lot to the west. Water services are not allowed to run across other properties.
Correction

Codes Administration - The City of Lee's Summit requires a reduced-pressure principle backflow assembly on all commercial domestic water services. I am unable to locate this on the plans.
Correction

Codes Administration - Sheet C5.1 shows backflow protection on the fire line at the tap and the plumbing plans show backflow protection at the building entrance.
Correction

Codes Administration - Per conversations with the Water Department, unprotected exterior drains are not allowed to connect to the sanitary sewer system.
Correction

Fire Department- 2006 IFC 503.3 Marking. Where required by the fire code official, approved signs or other approved notices shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs or notices shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Correction

Codes Administration - Per the minor plat, the address for this property is 650 NW Blue Pkwy. The permit has been addressed accordingly.
Correction

Fire Department- 2006 IFC 903.3.7 Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $4,268.38 $4,268.38 Paid 02/22/2010
84 Water Meters $1,450.32 $1,450.32 Paid 02/22/2010
85 Water Taps $19,380.00 $19,380.00 Paid 02/22/2010
89 Sewer Tap Fees $900.00 $900.00 Paid 02/22/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 03/19/2010
Correction
Partial Correction
03/19/2010
PREPARATION TO POUR GRADE BEAM + INTEGRAL COLUMN FOOTINGS E WALL FROM (2)/(C.2) TO (2)/(F) + N WALL FROM (F)/(2) TO (F)/(5.9) INCL RR's & OFC; OK TO POUR WHEN READY SECTIONS DESCRIBED BELOW:
Footing Inspection - Commercial Partial 03/23/2010
Correction
Partial Correction
03/23/2010
PREPARATION TO POUR GRADE BEAM + INTEGRAL COLUMN FOOTINGS N SIDE FROM (F)/(2) TO (F)/(5.9) INCL RR's & OFC; E SIDE COMPLETE; S SIDE COMPLETE; S 10' OF WEST SIDE; OK TO POUR WHEN READY SECTIONS DESCRIBED BELOW:
Footing Inspection - Commercial Partial 03/26/2010
Correction
Partial Correction
03/26/2010
PREPARATION TO POUR GRADE BEAM + INTEGRAL COLUMN FOOTINGS N SIDE FROM (F)/(2) TO (F)/(5.9) INCL RR's & OFC; E SIDE COMPLETE; S SIDE COMPLETE; S 10' OF WEST SIDE; INTERIOR WALL & COLUMN FOOTINGS COMPLETE FROM (1) TO (5.7); OK TO POUR WHEN READY SECTIONS DESCRIBED BELOW:
Footing Inspection - Commercial Partial 03/30/2010
Correction
Partial Correction
03/30/2010
PREPARATION TO POUR GRADE BEAM + INTEGRAL COLUMN FOOTINGS N SIDE FROM (F)/(2) TO (F)/(5.9) INCL RR's & OFC; E SIDE COMPLETE; S SIDE COMPLETE; S 10' OF WEST SIDE; INTERIOR WALL & COLUMN FOOTINGS COMPLETE FROM (1) TO (5.7); EXTERIOR COLUMN FOOTINGS + REMAINING WALL FTGS EXCEPT @ SERVICE YARD; OK TO POUR WHEN READY SECTIONS DESCRIBED BELOW:
Underslab Plumbing Inspection - Commercial Partial 04/01/2010
Correction
Resolved
04/01/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Correction
Corrective Action Required
04/01/2010
UNDER-SLAB GREASE WASTE PIPING SUBJECT TO APPROVAL BEFORE COVERING
Concrete Walls and Columns Inspection Partial 04/01/2010
Correction
Partial Correction
04/01/2010
PREPARATION TO POUR C.I.P. CONCRETE COLUMNS OUTSIDE EAST WALL; OK TO POUR WHEN READY COLUMNS @ LOCATIONS BELOW
Concrete Walls and Columns Inspection Partial 04/02/2010
Correction
Partial Correction
04/02/2010
PREPARATION TO POUR C.I.P. CONCRETE COLUMNS 5 OUTSIDE EAST WALL; OUTSIDE SW CORNER; OK TO POUR WHEN READY COLUMNS @ LOCATIONS BELOW
Underslab Electrical Inspection - Commercial Partial 04/06/2010
Correction
Partial Correction
04/06/2010
UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP 4" PVC DATACOMM CONDUIT ALONG (D.1); OK TO COVER WHEN READY FOLLOWING PORTIONS:
Water Service Inspection Partial 04/07/2010
Correction
Partial Correction
04/07/2010
WATER SERVICE INSTALLATION FROM BUILDING ENTRY TO 200' N/NW; OK TO COVER WHEN READY SEGMENTS LISTED BELOW:
Underslab Electrical Inspection - Commercial Partial 04/07/2010
Correction
Partial Correction
04/07/2010
UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP 4" PVC DATACOMM CONDUIT ALONG (D.1); SPACES 103, 106, 107; OK TO COVER WHEN READY FOLLOWING PORTIONS:
Underslab Plumbing Inspection - Commercial Passed 04/09/2010
Correction
Resolved
04/09/2010
WATER SERVICE ENTRY COPPER SWEEP IS KINKED REPLACE WITH NEW LENGTH
Correction
Resolved
04/09/2010
UNDER-SLAB GREASE WASTE PIPING OK TO COVER WHEN READY
Water Service Inspection Partial 04/12/2010
Correction
Partial Correction
04/12/2010
WATER SERVICE INSTALLATION SDR 9 CTSPF 3408 TUBING FROM BUILDING ENTRY TO 200' N/NW; CONNECTION OF SDR 9 TUBING TO TYPE K COPPER ENTRY TUBING; OK TO COVER WHEN READY SEGMENTS LISTED BELOW:
Water Service Inspection - Commercial Request Complete 4/12/2010 4/12/2010 04/12/2010
Underslab Electrical Inspection - Commercial Passed 04/13/2010
Correction
Resolved
04/13/2010
UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP 4" PVC DATACOMM CONDUIT ALONG (D.1); SPACES 103, 106, 107; 112; 113; 114; 115; 116; 117; 118; 119; 120; 121; 123; 126; 128 OK TO COVER WHEN READY FOLLOWING PORTIONS:
Underground Electrical Inspection - Commercial Request Complete 4/12/2010 4/13/2010 04/13/2010
Water Service Inspection - Commercial Request Complete 4/15/2010 4/15/2010 04/15/2010
Water Service Inspection Passed 04/16/2010
Correction
Resolved
04/16/2010
WATER SERVICE INSTALLATION SDR 9 CTSPF 3408 TUBING FROM BUILDING ENTRY TO 200' N/NW; CONNECTION OF SDR 9 TUBING TO TYPE K COPPER ENTRY TUBING; FINAL 10' COPPER INTO METER WELL OK TO COVER WHEN READY SEGMENTS LISTED BELOW:
Water Service Inspection - Commercial Request Complete 4/16/2010 4/16/2010 04/16/2010
Footing Inspection - Commercial Passed 04/19/2010
Correction
Resolved
04/19/2010
PREPARATION TO POUR GRADE BEAM + INTEGRAL COLUMN FOOTINGS
Correction
Resolved
04/19/2010
PREPARATION TO POUR WALL FOOTINGS @ SERVICE YARD OK TO POUR WHEN READY
Underground Plumbing Inspection - Commercial Passed 04/21/2010
Correction
Resolved
04/21/2010
GREASE INTERCEPTOR + INLET & OUTLET PIPING CONNECTED TO SAN SEWER OK TO COVER WHEN READY
Underground Plumbing Inspection - Commercial Request Complete 4/21/2010 4/21/2010 04/21/2010
Rough Framing Inspection - Commercial Not Ready 04/22/2010
Correction
Corrective Action Required
04/22/2010
EXTERIOR SHEAR WALL SHEATHING INSPECTION POSTPONED DUE TO RAIN
Rough Framing Inspection - Commercial Request Complete 4/21/2010 4/22/2010 04/22/2010
Rough Framing Inspection - Commercial Partial 04/23/2010
Correction
Partial Correction
04/23/2010
EXTERIOR SHEAR WALL SHEATHING OK TO COVER WHEN READY CMU AREA @ NW CORNER
Rough Framing Inspection - Commercial Request Complete 4/26/2010 4/27/2010 04/27/2010
Rough Framing Inspection - Commercial Partial 04/28/2010
Correction
Partial Correction
04/28/2010
INSTALLATION OF ROOF SHEATHING
Rough Framing Inspection - Commercial Request Complete 4/27/2010 4/28/2010 04/28/2010
Rough Framing Inspection - Commercial Partial 04/29/2010
Correction
Resolved
04/29/2010
INSTALLATION OF ROOF SHEATHING NO ISSUES FOUND
Rough Framing Inspection - Commercial Request Complete 4/28/2010 4/29/2010 04/29/2010
Rough Framing Inspection - Commercial Passed 05/05/2010
Correction
Resolved
05/05/2010
FASTENING OF EXTERIOR WALL SHEATHING OK TO COVER WHEN READY
Correction
Resolved
05/05/2010
EXTERIOR SHEAR WALL SHEATHING OK TO COVER WHEN READY CMU AREA @ NW CORNER
Footing Inspection - Commercial Passed 05/05/2010
Correction
Resolved
05/05/2010
PREPARATION TO POUR GRADE BEAM + INTEGRAL COLUMN FOOTINGS INCLUDING AT SO ENTRANCE ON LINES (3); (5); (A)
All Rough Inspection - Commercial Partial 05/07/2010
Correction
Partial Correction
05/07/2010
WALL FRAMING + IN-WALL SYSTEMS DENSSHIELD AREA @ BOTTOM 12" OF EXTERIOR WALLS @ 101, 102, 103; OK TO COVER WHEN READY WALL SURFACES BELOW:
Correction
Corrective Action Required
05/07/2010
PROTECTION OF COPPER PIPING ISOLATE DISSIMILAR METALS WITH NON-CONDUCTIVE MATERIAL WHERE IN CONTACT WITH DISSIMILAR METAL
Correction
Corrective Action Required
05/07/2010
PROTECTION OF PVC & COPPER PIPING FROM PENETRATION IPC 305.8: INSTALL SHIELD PLATES AT STUDS & PLATES/TRACKS. SHIELD PLATES SHALL COVER THE AREA OF THE PIPE WHERE THE MEMBER IS NOTCHED OR BORED AND SHALL EXTEND A MINIMUM OF 2" ABOVE SOLE PLATES & BELOW TOP PLATES. CHECK ALL. WHERE < 1-1/2" FROM FACE OF FRAMING TO RECEIVE GWB
All Rough Inspection - Commercial Partial 05/10/2010
All Rough Inspection - Commercial Passed 05/11/2010
Correction
Resolved
05/11/2010
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY
Correction
Resolved
05/11/2010
PROTECTION OF COPPER PIPING
Correction
Resolved
05/11/2010
PROTECTION OF PVC & COPPER PIPING FROM PENETRATION
Above Ceiling Inspection Not Ready 05/12/2010
Correction
Corrective Action Required
05/12/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS
Above Ceiling Inspection Partial 05/14/2010
Correction
Resolved
05/14/2010
TRUSS JOIST & I-JOIST PRIMARY ROOF & CEILING FRAMING NO ISSUES FOUND
Above Ceiling Inspection Partial 05/17/2010
Correction
Corrective Action Required
05/17/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS PRE-INSPECTION ONLY-WALK THROUGH ONLY
Above Ceiling Inspection Partial 05/20/2010
Correction
Corrective Action Required
05/20/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ROOM #-101;102;103;104;105;106;107;108; HARD CEILING ONLY
Gas Service Inspection - Commercial Failed 05/21/2010
Correction
Corrective Action Required
05/21/2010
Gas Test Pressure (IRC) CANCELLED
Above Ceiling Inspection Partial 05/24/2010
Correction
Partial Correction
05/24/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ROOM #-101;102;103;104;105;106;107;108; MENS, WOMENS RESTROOMS, MECHANICAL ROOM. MANAGER OFFICE. HARD CEILING ONLY
Gas Service Inspection - Commercial Failed 05/24/2010
Correction
Partial Correction
05/24/2010
Gas Test Pressure (IRC) HOLDING 15LBS- REVISE PLANS --1/2" FLEX USED TO FIREPLACE- PLANS SHOWS 3/4". PARTIAL INSPECTION ONLY
Hood/Duct Inspection Partial 06/10/2010
Correction
Partial Correction
06/10/2010
COMMERCIAL KITCHEN GREASE DUCT FABRICATION IMC 506 SHOP WELDS LIGHT TESTED PINHOLES WELDED
Gas Service Inspection - Commercial Passed 06/10/2010
Correction
Resolved
06/10/2010
Gas Test Pressure (IRC)
Correction
Resolved
06/10/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE PRESSURE HELD STEADY AT ~10 PSI FOR >=10 MIN
Gas Piping Inspection - Commercial Partial 06/14/2010
Correction
Partial Correction
06/14/2010
PRESSURE TEST OF COOK LINE PIPING NO ISSUES FOUND ON VISUAL INSPECTION PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Hood/Duct Inspection Not Ready 06/17/2010
Correction
Resolved
06/17/2010
COMMERCIAL KITCHEN GREASE DUCT FABRICATION IMC 506 SHOP WELDS LIGHT TESTED PINHOLES WELDED
Correction
Corrective Action Required
06/17/2010
COMMERCIAL KITCHEN GREASE DUCT INSTALLATION CONFIGURATION TRAPS GREASE AT VERTICAL DUCT
Hood/Duct Inspection Not Ready 06/18/2010
Correction
Corrective Action Required
06/18/2010
READINESS FOR INSPECTION JOB SITE SHUT DOWN DUE TO GAS LINE LEAK
Hood/Duct Inspection Passed 06/21/2010
Correction
Resolved
06/21/2010
COMMERCIAL KITCHEN GREASE DUCT INSTALLATION SEALING OF DETECTED LIGHT LEAKS IN PROGRESS. OK TO APPLY WRAP WHEN READY. VISUAL INSP + LIGHT TEST PERFORMED 6/21/2010
Correction
Resolved
06/21/2010
READINESS FOR INSPECTION
Hood/Duct Inspection Passed 06/25/2010
Correction
Resolved
06/25/2010
APPLICATION OF GREASE DUCT FIRE-RESISTANT WRAP NO ISSUES FOUND
Electrical Service Inspection Passed 06/29/2010
Correction
Resolved
06/29/2010
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE 1200 AMPS 3P 3 SETS OF FOUR #600 KCMIL
Concrete Walls and Columns Inspection Passed 06/29/2010
Correction
Resolved
06/29/2010
PREPARATION TO POUR C.I.P. CONCRETE COLUMNS
Above Ceiling Inspection Passed 06/29/2010
Correction
Resolved
06/29/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS
Gas Piping Inspection - Commercial Passed 06/29/2010
Correction
Resolved
06/29/2010
PRESSURE TEST OF COOK LINE PIPING
Above Ceiling Inspection Not Ready 07/06/2010
Correction
Corrective Action Required
07/06/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS INSTALL NO CEILING TILE BEFORE ABOVE-CEILING INSPECTION -- EXCEPT THOSE FEW REQUIRED FOR MOUNTING OF DEVICES. AREA REQUESTED FOR INSP ALREADY COVERED W/ TILE
Above Ceiling Inspection Passed 07/07/2010
Correction
Resolved
07/07/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY RUN L.V. CABLE HIGH IN STRUCTURE TO DESTINATION
Occupancy Inspection - Codes Commercial Not Ready 07/07/2010
Correction
Corrective Action Required
07/07/2010
ACCESS EASEMENT MUST BE RECORDED WITH THE COUNTY DOMESTIC WATER SERVICE AND FIRE LINE
Correction
Resolved
07/07/2010
UL LISTING OF EXTERIOR LIGHTED SIGNS LABELS FOUND AFFIXED
Correction
Corrective Action Required
07/07/2010
DISPLAY OF "NO SMOKING" SIGN(S) LS CODE OF ORDINANCES 17-309: SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY MUST BE AFFIXED AT PUBLIC ENTRY(IES)
Correction
Corrective Action Required
07/07/2010
APPROVAL OF JACKSON COUNTY HEALTH DEPARTMENT MUST BE OBTAINED PROVIDE DOCUMENTATION
Correction
Corrective Action Required
07/07/2010
Receive Fire Department approval
Correction
Corrective Action Required
07/07/2010
Receive Planning & Development Approval
Correction
Corrective Action Required
07/07/2010
Receive Public Works Approval
Correction
Corrective Action Required
07/07/2010
Receive Water Utilities Approval
Occupancy Inspection - Codes Commercial Not Ready 07/08/2010
Correction
Resolved
07/08/2010
REMITTANCE OF APPLICABLE LICENSE TAX PAYMENT ON RECORD PER M WEISENBORN 7/8/2010
Occupancy Inspection - Codes Commercial Not Ready 07/12/2010
Correction
Corrective Action Required
07/12/2010
Receive Fire Department approval PROVIDE DOCUMENTATION
Correction
Corrective Action Required
07/12/2010
COMMERCIAL KITCHEN HOOD PERFORMANCE TESTS IMC 507.16 REPORT VELOCITY TEST + DEMONSTRATE SMOKE CAPTURE
Correction
Corrective Action Required
07/12/2010
READINESS FOR INSPECTION CALL FOR INSPECTION AFTER ALL INTERIOR WORK IS COMPLETE. WORK REQUESTED FOR INSP NOT COMPLETED
Occupancy Inspection - Codes Commercial Not Ready 07/14/2010
Correction
Resolved
07/14/2010
Receive Water Utilities Approval PER BEN HASKAMP 7/12/2010
Correction
Corrective Action Required
07/14/2010
ROOFTOP INSPECTION
Correction
Corrective Action Required
07/14/2010
FINAL INSPECTION OF RESTROOMS
Correction
Corrective Action Required
07/14/2010
LOCAL BACKFLOW PROTECTION
Correction
Corrective Action Required
07/14/2010
ROOF MANUFACTURER INSTALLATION INSPECTION
Correction
Corrective Action Required
07/14/2010
FINISH ELECTRICAL WORK @ BUILDING EXTERIOR WALLS
Occupancy Inspection - Codes Commercial Failed 07/15/2010
Correction
Resolved
07/15/2010
DISPLAY OF "NO SMOKING" SIGN(S)
Correction
Partial Correction
07/15/2010
READINESS FOR INSPECTION WHEN COMPLETED RESTROOMS & ROOFTOP SUJECT TO APPROVAL
Correction
Corrective Action Required
07/15/2010
ROOFTOP INSPECTION SUBJECT TO APPROVAL WHEN ALL WORK COMPLETED
Correction
Corrective Action Required
07/15/2010
FINAL INSPECTION OF RESTROOMS SUBJECT TO APPROVAL WHEN COMPLETED
Correction
Corrective Action Required
07/15/2010
LOCAL BACKFLOW PROTECTION REQUEST INSPECTION WHEN COMPLETE PER DRAWINGS
Correction
Corrective Action Required
07/15/2010
ROOF MANUFACTURER INSTALLATION INSPECTION PROVIDE DOCUMENTATION OF MFGR APPROVAL
Correction
Resolved
07/15/2010
FINISH ELECTRICAL WORK @ BUILDING EXTERIOR WALLS APPARENTLY COMPLETED
Correction
Partial Correction
07/15/2010
USE / OCCUPANCY APPROVAL STATUS OK FOR COMPUTER INSTALLATION, HIRING NO USE OF FOOD PREPARATION AREAS UNTIL APPROVED. OK TO SET UP FOR BUSINESS DINING & BAR AREAS ONLY
Occupancy Inspection - Codes Commercial Failed 07/19/2010
Correction
Corrective Action Required
07/19/2010
Receive Fire Department approval SEE INSPECTION REPORT PROVIDED CONTACT CPT JOE DIR PHONE 816-969-1317
Correction
Corrective Action Required
07/19/2010
Receive Planning & Development Approval TO SCHEDULE INSPECTION WHEN READY CONTACT HECTOR SOTO PHONE 816-969-1604
Correction
Resolved
07/19/2010
Receive Public Works Approval PER BOB BURNS 7/16/2010
Correction
Resolved
07/19/2010
READINESS FOR INSPECTION
Correction
Corrective Action Required
07/19/2010
FINAL INSPECTION OF RESTROOMS SUBJECT TO APPROVAL WHEN COMPLETED
Correction
Resolved
07/19/2010
ROOF MANUFACTURER INSTALLATION INSPECTION COPY OF WARRANTY PROVIDED 7/19/2010
Correction
Partial Correction
07/19/2010
USE / OCCUPANCY APPROVAL STATUS AFTER APPROVAL OF KITCHEN BY COUNTY HEALTH DEPARTMENT OK TO SET UP FOR BUSINESS THROUGHOUT BUILDING
Underground Electrical Inspection - Commercial Passed 07/19/2010
Correction
Resolved
07/19/2010
PREP TO POUR CONCRETE LIGHT POLE BASES COMPLETION OF GROUNDS @ TWO POLES @ SOUTH & SOUTHWEST VERIFIED BY G.C. NOTE: BURIED CONDUIT SERVING LIGHT POLES NOT REQUESTED FOR INSPECTION BEFORE IT WAS COVERED. OK TO POUR WHEN READY ELEVEN POLE BASES
Underground Electrical Inspection - Commercial Request Complete 7/19/2010 7/19/2010 07/19/2010
Occupancy Inspection - Codes Commercial Failed 07/20/2010
Correction
Resolved
07/20/2010
ACCESS EASEMENT DOCUMENT PROVIDED TO JB INDICATES EASEMENT RECORDED WITH JACKSON COUNTY RECORDER OF DEEDS ON 17 JUNE 2010. DOMESTIC WATER SERVICE AND FIRE LINE
Occupancy Inspection - Codes Commercial Failed 07/21/2010
Correction
Resolved
07/21/2010
ROOF MANUFACTURER INSTALLATION INSPECTION WARRANTY COPY DTD 7/12/10 RECEIVED 7/19/2010
Correction
Resolved
07/21/2010
FINAL INSPECTION OF RESTROOMS
Correction
Partial Correction
07/21/2010
USE / OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Failed 07/22/2010
Correction
Resolved
07/22/2010
LOCAL BACKFLOW PROTECTION DEVICES FOUND INSTALLED
Occupancy Inspection - Codes Commercial Failed 07/23/2010
Correction
Resolved
07/23/2010
ROOFTOP INSPECTION
Occupancy Inspection - Codes Commercial Passed 07/30/2010
Correction
Resolved
07/30/2010
APPROVAL OF JACKSON COUNTY HEALTH DEPARTMENT MUST BE OBTAINED PROVIDE DOCUMENTATION
Correction
Resolved
07/30/2010
Receive Fire Department approval SEE INSPECTION REPORT PROVIDED CONTACT CPT JOE DIR PHONE 816-969-1317
Correction
Resolved
07/30/2010
Receive Planning & Development Approval TO SCHEDULE INSPECTION WHEN READY CONTACT HECTOR SOTO PHONE 816-969-1604
Correction
Resolved
07/30/2010
COMMERCIAL KITCHEN HOOD PERFORMANCE TESTS IMC 507.16 REPORT VELOCITY TEST + DEMONSTRATE SMOKE CAPTURE
Correction
Resolved
07/30/2010
USE / OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home