Permit Application Status

B0901101


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0901101
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
NEW SALON AND SPA IN PREVIOUSLY UNOCUPIED SPACE
10/26/2009
11/25/2009
09/04/2010
03/12/2010
Locations
Contacts
EXCEL CONSTRUCTION, Address:8041 W 47TH ST SUITE 100  
INTEGRITY PLUMBING SERVICES, LLC, Address:3801 SE VALLEY FORGE DR  
REES MASILIONIS TURLEY, Address:908 BROADWAY 6TH FLR  
KR LAMMING ELECTRIC LLC, Address:PO BOX 11788  
UNITED HEATING & COOLING, Address:301 DUCK RD  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/18/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Codes Administration - Per conversations with RED Devlopment, an exit sign will be located in the corridor directly across from the door from Beauty Brands. The exit sign shall be self luminating, have an arrow indicating the direction of egress travel and be located between 6 and 8 feet above the floor.
Correction

Codes Administration - Footnote i of Table 403.3 requires that the required exhaust system capture the contaminants and odors produced in nail salons at their source. The exhaust systems provided in the areas of the manicure and pedicure stations do not meet this requirement.
Correction

Codes Administration - The plumbing specifications mentions cross connection protection but I am unable to locate information on which items are required to be protected.
Correction

Codes Administration - Note 4 on Sheet A01 indicates that the demising walls are existing. These walls are not shown on the shell building plans and to my knowledge have not been constructed.
Correction

Codes Administration - Details for the attachment of the awings have not been provided.
Correction

Codes Administration - The calculated occupant load is not provided in the Code Review Data.
Correction

Codes Administration - The Code Review Section indicates that the project is designed to the 2004 Plumbing Code. The 2006 International Plumbing Code is currently adopted by the City of Lee's Summit.
Correction

Codes Administration - The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff.
Correction

Codes Administration - The structual plans for the shell building indicates that the area in which the rooftop units are located is designed for a maximum weight of 2,000 lbs per unit and curb.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,538.60 $1,538.60 Paid 11/25/2009
89 Sewer Tap Fees $510.00 $510.00 Paid 11/25/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/04/2009
Correction
Resolved
12/04/2009
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Underslab Electrical Inspection - Commercial Not Ready 12/04/2009
Correction
Corrective Action Required
12/04/2009
READINESS FOR INSPECTION ELECTRICAL CONTRACTOR NOT LISTED ON PERMIT
Underslab Electrical Inspection - Commercial Passed 12/07/2009
Correction
Resolved
12/07/2009
READINESS FOR INSPECTION
Correction
Resolved
12/07/2009
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
All Rough Inspection - Commercial Partial 12/16/2009
Correction
Partial Correction
12/16/2009
WALL FRAMING + IN-WALL SYSTEMS 09; 11; 12; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Not Ready 12/17/2009
Correction
Partial Correction
12/17/2009
WALL FRAMING + IN-WALL SYSTEMS 09; 11; 12; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 12/18/2009
Correction
Partial Correction
12/18/2009
WALL FRAMING + IN-WALL SYSTEMS 05; 06; 07; 08; 09; 11; 12; HALLWAY 014 N END; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 12/21/2009
Correction
Partial Correction
12/21/2009
WALL FRAMING + IN-WALL SYSTEMS ALL WALLS & SOFFITS EXCEPT SOFFIT AT STUDIO 013 & RADIUS COLUMN N01 A10 OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Passed 12/23/2009
Correction
Resolved
12/23/2009
WALL FRAMING + IN-WALL SYSTEMS ALL WALLS & SOFFITS INCLUDING SOFFIT AT STUDIO 013 & RADIUS COLUMN N01 A10 OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Gas Piping Inspection - Commercial Passed 12/30/2009
Gas Service Inspection - Commercial Passed 12/30/2009
Correction
Resolved
12/30/2009
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Miscellaneous Inspection Passed 01/21/2010
Above Ceiling Inspection Partial 01/22/2010
Correction
Partial Correction
01/22/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 001 DL TO DJ.3; 05; 06; 07; 010; SUBJECT TO RE-INSPECTION AFTER RTU's ARE SET AND ALL WORK IS COMPLETED. OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 01/26/2010
Correction
Partial Correction
01/26/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 001 COMPLETE; 003; 005; 006; 007; 009; 010; SUBJECT TO RE-INSPECTION AFTER RTU's ARE SET AND ALL WORK IS COMPLETED. OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 01/28/2010
Correction
Partial Correction
01/28/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 001 COMPLETE; 003; 005; 006; 007; 009; 010; 002, 013, 011, 012; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Electrical Service Inspection Passed 01/29/2010
Correction
Resolved
01/29/2010
ELECTRICAL SERVICE INSTALLATION 400 AMPS RELEASE SERVICE
Above Ceiling Inspection Partial 02/09/2010
Correction
Partial Correction
02/09/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 001 COMPLETE; 003; 005; 006; 007; 009; 010; 002, 013, 011, 012, 008; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Occupancy Inspection - Codes Commercial Failed 02/17/2010
Correction
Corrective Action Required
02/17/2010
None 1. Water heater- temperature relief valve piping shall piped to the floor individually (used pvc as main drain for all units).
Correction
Corrective Action Required
02/17/2010
None INSTALL MIRROR TO APPROVED HEIGHT( MAX 40" ABOVE FLOOR) bathrooms
Correction
Corrective Action Required
02/17/2010
BACKFLOW INSTALL BACKFLOW PREVENTER AT ALL PEDICURE CHAIRS.
Correction
Corrective Action Required
02/17/2010
Receive Fire Department approval FIRE DEPARTMENT APPROVED TO STOCK ONLY DO NOT TRAIN OR OCCUPY
Correction
Corrective Action Required
02/17/2010
None APPROVED TO STOCK BUILDING ITEMS ONLY NOT APPROVED TO TRAIN OR OCCUPY
Occupancy Inspection - Codes Commercial Failed 02/19/2010
Correction
Resolved
02/19/2010
None
Correction
Resolved
02/19/2010
None
Correction
Resolved
02/19/2010
BACKFLOW
Correction
Resolved
02/19/2010
Receive Fire Department approval PER CPT JOE DIR 2/19/2010
Correction
Resolved
02/19/2010
None
Correction
Corrective Action Required
02/19/2010
INSTALLATION OF LIGHTED SIGN PER NEC 600-3: SUBJECT TO NATIONAL 2005 ELECTRICAL CODE. IF INTERNALLY LIGHTED > 12V MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN. SUBJECT TO APPROVAL. PER NEC 600-3
Correction
Corrective Action Required
02/19/2010
NUMBERING OF ROOFTOP HVAC UNITS APPLY PERMANENT LABELS PER #'s ON DRAWINGS
Correction
Corrective Action Required
02/19/2010
MISSING/UNTIGHTENED FASTENERS IN SHELL PANELS INSTALL / TIGHTEN SCREWS
Correction
Corrective Action Required
02/19/2010
NORTHEAST RTU 1) FILTER DISPLACED & DAMAGED -- REPLACE 2) UNUSED OPENING ABOVE ELECT RECEPT -- CLOSE OPENING SEE ISSUES BELOW
Correction
Corrective Action Required
02/19/2010
DEBRIS LEFT ON ROOF SURFACE REMOVE ALL DEBRIS AND UNUSED MATERIALS SCREWS & OTHER MATERIALS MAY DAMAGE MEMBRANE
Correction
Corrective Action Required
02/19/2010
PROTECTION OF METALLIC PIPE (OR TUBING) AGAINST CORROSION IFGC 404.8 ROOFTOP GAS PIPING PAINT OR OTHER APPROVED
Occupancy Inspection - Codes Commercial Failed 03/08/2010
Correction
Resolved
03/08/2010
INSTALLATION OF LIGHTED SIGN
Occupancy Inspection - Codes Commercial Passed 03/09/2010
Correction
Resolved
03/09/2010
NUMBERING OF ROOFTOP HVAC UNITS
Correction
Resolved
03/09/2010
MISSING/UNTIGHTENED FASTENERS IN SHELL PANELS
Correction
Resolved
03/09/2010
NORTHEAST RTU
Correction
Resolved
03/09/2010
DEBRIS LEFT ON ROOF SURFACE
Correction
Resolved
03/09/2010
PROTECTION OF METALLIC PIPE (OR TUBING) AGAINST CORROSION
Above Ceiling Inspection Passed 03/10/2010
Correction
Resolved
03/10/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home