Permit Application Status

B0900964


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900964
Building Permit - Commercial
Certificate of Occupancy
JHE FOSTER LLC
NEW COMMERCIAL
MEDICAL OFFICE BUILDING - FULL PERMIT
09/22/2009
11/19/2009
12/15/2010
06/22/2010
Locations
Contacts
J & N UTILITIES, Address:PO BOX 1284  
A & A ELECTRICAL, INC, Address:PO BOX 576  
NORTON & SCHMIDT, Address:311 E 11TH AVENUE  
SHUKLA AND ASSOCIATES, Address:3693 W 129TH PLACE  
JAKES REFRIGERATION HTG/COOLING, Address:1101 SW 1ST ST  
SHUKLA AND ASSOCIATES, Address:3693 W 129TH PLACE  
JHE FOSTER LLC, Address:4411 NE GEORGIAN DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/17/2010 10/29/2010
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - The structural plans indicate that they are designed to the requirements of the 2003 IBC. The 2006 IBC is currently adopted by the City of Lee's Summit.
Correction

Codes Administration - The plans do not indicate how the suites will be identified.
Correction

Codes Administration - The plans do not provide any information on the x-ray equipment or requirements for special construction.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - ICC/ANSI A117.1 2003 602.4 - Spout outlet height. Spout outlets of wheelchair accessible drinking fountains shall be 36 inches maximum above the floor. Spout outlets of drinking fountains for standing persons shall be 38 inches minimum and 43 inches maximum above the floor.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.3.2 - Overlap. The required clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, paper dispensers, sanitary napkin receptacles, coat hooks, shelves, accessible routes, clear floor space at other fixtures and the turning space. No other fixtures or obstructions shall be within the required water closet clearance.
Correction

Codes Administration - ICC/ANSI A117.1-2003 604.5.2 - Rear wall grab bars. The rear wall grab bar shall be 36 inches minimum in length, and extend from the centerline of the water closet 12 inches minimum on the side closest to the wall, and 24 inches minimum on the transfer side.
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

Codes Administration - 2005 NEC 210.63 - Heating, air-conditioning, and refrigeration equipement outlet. A 125-volt, single-phase, 12- or20-ampere-rated receptacle outlet shall be installed at an accessible loction for the servicing of heating, air conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 7.5 m (25 ft) of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Correction

Codes Administration - 2006 IBC 1008.1.5 - Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches.
Correction

Codes Administration - 2006 IBC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Correction

Fire Department- 2006 IFC 508.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
Correction

Codes Administration - The minor plat must be recorded with the County and returned to the City prior to permit issuance.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - 2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,283.36 $1,283.36 Paid 11/19/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 11/20/2009
Correction
Partial Correction
11/20/2009
UNDER-SLAB STORM DRAIN PIPING UPPER LIFT PIPING SUBJECT TO APPROVAL WHEN INSPECTION IS REQUESTED. OK TO COVER WHEN READY LOWER LEVEL PIPING
Correction
Partial Correction
11/20/2009
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING UPPER LIFT PIPING SUBJECT TO APPROVAL WHEN INSPECTION IS REQUESTED. OK TO COVER WHEN READY LOWER LIFT PIPING
Underslab Electrical Inspection - Commercial Passed 11/23/2009
Correction
Resolved
11/23/2009
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
Water Service Inspection - Commercial Request Complete 11/23/2009 11/23/2009 11/23/2009
Sewer Service Inspection - Commercial Request Complete 11/24/2009 11/24/2009 11/24/2009
Rough Framing Inspection - Commercial Partial 12/21/2009
Correction
Partial Correction
12/21/2009
LIGHT-GUAGE STEEL FRAMING OF EXTERIOR WALLS OK TO COVER WHEN READY EXTERIOR FACE ONLY
Rough Framing Inspection - Commercial Request Complete 12/18/2009 12/21/2009 12/21/2009
All Rough Inspection - Commercial Failed 02/26/2010
Correction
Corrective Action Required
02/26/2010
STUDS AT DOOR OPENING # NOT SECURED AT BOTTOM
Correction
Corrective Action Required
02/26/2010
SECURING OF ELECTRICAL BOXES IN WALLS TO CONTACT OPPOSITE WALL FACE SOME BOX STAND-OFFS NOT LONG ENOUGH
Correction
Corrective Action Required
02/26/2010
PROTECTION OF COPPER PIPING INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL AT PENETRATION OF STEEL FRAMING MEMBERS
Correction
Corrective Action Required
02/26/2010
PROTECTION OF PVC PIPING FROM PENETRATION IPC 305.8: INSTALL SHIELD PLATES AT STUDS & PLATES/TRACKS. CHECK ALL. WHERE < 1-1/2" FROM FACE OF FRAMING TO RECEIVE GWB
Above Ceiling Inspection Not Ready 02/26/2010
Correction
Partial Correction
02/26/2010
SHEET METAL HVAC DUCT OK TO COVER WHEN READY
Gas Service Inspection - Commercial Passed 02/26/2010
Correction
Resolved
02/26/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE PRESSURE HELD STEADY FOR >=10 MIN
Gas Piping Inspection - Commercial Failed 02/26/2010
Correction
Corrective Action Required
02/26/2010
SUPPORT OF ROOFTOP GAS PIPING 1) BLOCK MATERIAL NOT PER DRAWING P3 2) CHECK SPACING: IFGC 407.2 & 415: 3/4" OR 1" PIPE -- 8" MAX SPACING; 1-1/4" OR LARGER PIPE -- 10" MAX SPACING 3) SUPPORT PIPE NEAR FITTINGS & CHANGES OF DIRECTION 4) PIPING MUST BE PAINTED AT FINAL INSPECTION SEE ISSUES BELOW:
All Rough Inspection - Commercial Passed 03/02/2010
Correction
Resolved
03/02/2010
STUDS AT DOOR OPENING #
Correction
Resolved
03/02/2010
SECURING OF ELECTRICAL BOXES IN WALLS
Correction
Resolved
03/02/2010
PROTECTION OF COPPER PIPING
Correction
Resolved
03/02/2010
PROTECTION OF PVC PIPING FROM PENETRATION
Electrical Service Inspection Failed 03/26/2010
Correction
Corrective Action Required
03/26/2010
PLANS PROVED APPROVED PLANS FOR INSPECTION. PLEASE RECALL FOR ELECTRICAL SERVICE WHEN PLANS ARE ON SITE.
Electrical Service Inspection Passed 03/30/2010
Correction
Resolved
03/30/2010
PLANS
Above Ceiling Inspection Failed 04/14/2010
Correction
Resolved
04/14/2010
SHEET METAL HVAC DUCT
Correction
Corrective Action Required
04/14/2010
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES CHECK ALL. EXAMPLES: 101; 106; 107;.. OPPOSITE DIAGONAL CORNERS SOME NOT COMPLETED
Correction
Corrective Action Required
04/14/2010
WIRING OF HVAC EQUIPMENT @ 105 NOT TERMINATED
Correction
Corrective Action Required
04/14/2010
WIRING OF LIGHT FIXTURE @ 101 NOT TERMINATED
Correction
Corrective Action Required
04/14/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ SUITE "A" ONLY SEE ISSUE ITEMS BELOW DO NOT COVER
Above Ceiling Inspection Passed 04/15/2010
Correction
Resolved
04/15/2010
SHEET METAL HVAC DUCT
Correction
Resolved
04/15/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ SUITE "A" ONLY
Correction
Resolved
04/15/2010
WIRING OF LIGHT FIXTURE @ 101
Correction
Resolved
04/15/2010
WIRING OF HVAC EQUIPMENT @ 105
Correction
Resolved
04/15/2010
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES
Underground Electrical Inspection - Commercial Request Complete 4/21/2010 4/22/2010 04/22/2010
Underground Electrical Inspection - Commercial Failed 04/26/2010
Correction
Corrective Action Required
04/26/2010
PREPARATION TO POUR LIGHT POLE BASE 1) VERTICAL RE-BAR NOT #6 2) RE-BAR CAGE NOT SUSPENDED WITH 6" CLEARANCE 3) COPPER-CLAD GROUND ROD NOT INSTALLED 4) GROUNDING JUMPER NOT WELDED TO GROUND ROD 5) FEEDER CONDUIT NOT >=18" BELOW GRADE SEE VARIATIONS BELOW: FROM DRAWING & NEC
Underground Electrical Inspection - Commercial Passed 04/27/2010
Correction
Resolved
04/27/2010
PREPARATION TO POUR LIGHT POLE BASE OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 4/26/2010 4/27/2010 04/27/2010
Occupancy Inspection - Codes Commercial Not Ready 04/28/2010
Correction
Corrective Action Required
04/28/2010
Receive Public Works Approval
Correction
Corrective Action Required
04/28/2010
Receive Planning & Development Approval
Correction
Corrective Action Required
04/28/2010
DISPLAY OF "NO SMOKING" SIGN REQUIRED @PUBLIC ENTRANCE
Correction
Corrective Action Required
04/28/2010
ROOFTOP INSPECTION
Correction
Corrective Action Required
04/28/2010
ELEVATION OF WATER SERVICE WELL LID BELOW GRADE
Correction
Corrective Action Required
04/28/2010
TERMINATION OF SANITARY SEWER SERVICE CLEANOUT RISER NOT SET TO GRADE
Correction
Corrective Action Required
04/28/2010
Receive Water Utilities Approval
Correction
Corrective Action Required
04/28/2010
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Failed 04/29/2010
Correction
Partial Correction
04/29/2010
Receive Fire Department approval SEE INSPECTION REPORT PROVIDED COORDINATE W/ CPT JOE DIR PHONE 816-969-1317
Correction
Resolved
04/29/2010
Receive Water Utilities Approval PER BEN HASKAMP 4/29/2010
Correction
Corrective Action Required
04/29/2010
Receive Public Works Approval SUBJECT TO APPROVAL
Correction
Corrective Action Required
04/29/2010
Receive Planning & Development Approval ISSUES TO BE RECEIVED FROM P&D INSPECTOR
Correction
Corrective Action Required
04/29/2010
ROOFTOP INSPECTION 1) ROOFTOP GAS PIPING TO BE PAINTED 2) ATTACH ROOF PROTECTION SLIPSHEETS TO SUPPORT BLOCKS 3) RTU ELECTRICAL RECEPTACLES TO HAVE IN-USE COVERS 4) CLEAR/CLEAN ALL DEBRIS & UNSUSED MATERIAL FROM ROOF SEE ISSUES BELOW:
Correction
Corrective Action Required
04/29/2010
ELEVATION OF WATER SERVICE WELL LID BELOW GRADE
Correction
Corrective Action Required
04/29/2010
WALL PENETRATIONS AT GAS SERVICE ENTRIES ENSURE WATER/INSECT TIGHT
Correction
Resolved
04/29/2010
TESTING OF TWO EXTERIOR ELECT RECEPTS @ EAST END OF BLDG NOT HOT FOR TEST DEFERRED TO 6B T/F FINAL
Correction
Corrective Action Required
04/29/2010
WATER HEATER TEMPERATURE/PRESSURE RELIEF DISCHARGE PIPING IPC 504.6 TERMINATION > 6" ABOVE FLOOR OR WASTE RECEPTOR
Correction
Corrective Action Required
04/29/2010
ADDRESS LABELING OF GAS SERVICE ENTRIES TO BE CONFIRMED
Underslab Plumbing Inspection - Commercial Passed 05/04/2010
Correction
Resolved
05/04/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING
Correction
Resolved
05/04/2010
UNDER-SLAB STORM DRAIN PIPING
Rough Framing Inspection - Commercial Passed 05/04/2010
Correction
Resolved
05/04/2010
LIGHT-GUAGE STEEL FRAMING OF EXTERIOR WALLS
Gas Piping Inspection - Commercial Passed 05/04/2010
Correction
Resolved
05/04/2010
SUPPORT OF ROOFTOP GAS PIPING SEE FINAL INSPECTION
Occupancy Inspection - Codes Commercial Failed 05/26/2010
Correction
Resolved
05/26/2010
Receive Public Works Approval PER BILL LYON 5/25/2010
Occupancy Inspection - Codes Commercial Failed 05/27/2010
Correction
Resolved
05/27/2010
DISPLAY OF "NO SMOKING" SIGN
Correction
Resolved
05/27/2010
ELEVATION OF WATER SERVICE WELL
Correction
Resolved
05/27/2010
WALL PENETRATIONS AT GAS SERVICE ENTRIES
Occupancy Inspection - Codes Commercial Failed 06/07/2010
Correction
Resolved
06/07/2010
Receive Planning & Development Approval PER CHRIS HUGHEY 6/4/2010
Occupancy Inspection - Codes Commercial Failed 06/10/2010
Correction
Resolved
06/10/2010
Receive Fire Department approval PER CPT JOE DIR 6/10/2010
Correction
Corrective Action Required
06/10/2010
ROOFTOP INSPECTION CLEAR/CLEAN ALL DEBRIS & UNSUSED MATERIAL FROM ROOF SEE ISSUES BELOW:
Correction
Resolved
06/10/2010
WATER HEATER TEMPERATURE/PRESSURE RELIEF DISCHARGE PIPING
Occupancy Inspection - Codes Commercial Passed 06/21/2010
Correction
Resolved
06/21/2010
ROOFTOP INSPECTION MAY CAUSE DAMAGE TO ROOF MEMBRANE OR BLOCKAGE OF ROOF DRAINS. PROPERTY OWNER BE ADVISED DEBRIS REMAINS ON ROOFTOP
Correction
Resolved
06/21/2010
TERMINATION OF SANITARY SEWER SERVICE CLEANOUT RISER
Correction
Resolved
06/21/2010
ADDRESS LABELING OF GAS SERVICE ENTRIES
Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home