Permit Application Status

B0900900


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900900
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
IO METRO TENANT FINISH
09/09/2009
11/03/2009
05/02/2010
01/27/2010
Locations
Contacts
TEMP CON INC, Address:15670 S. KEELER  
TEMP CON INC, Address:15670 S. KEELER  
BCC CONSTRUCTION, Address:12410 CANTRELL RD SUITE 200  
TEMP CON INC, Address:15670 S KEELER ST  
TEMP CON INC, Address:15670 S KEELER ST  
MIKE HAGEN ELECTRIC CO, Address:8820 NE 108TH ST  
RPPY ARCHITECTS, Address:713 W 2ND ST  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/04/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Codes Administration - 2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Codes Administration - ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.)
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

Codes Administration - 2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the evenet of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building requried to have two or more exits. 3. Exterior egress componenets at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Correction

Codes Administration - The Code Search indicates a construction type of V-B but shell building was actually constructed as type II-B.
Correction

Codes Administration - The Codes Search provides an allowable area based on type V-B construction with a 200 percent increase for the sprinkler system. The construction type is actually type II-B which has a base area of 12,500 square feet and the sprinkler increase would be 300 percent as it is a single story building. The sprinkler increase is in addition to the base area so the total allowable area is actually 50,000 square feet.
Correction

Codes Administration - The occupant load is calculated using one person for every 60 square feet. Per Table 1004.1.1, this is the multiplier used for areas on floors other than the basement or grade level. The occupant load needs to be calculated at one person for every 30 square feet of sales area and one person for every 300 square feet of storage area.
Correction

Codes Administration - I am unable to locate the listing for the 1-hour rated partition.
Correction

Codes Administration - I am unable to locate details for the construction and attachment of the awnings.
Correction

Codes Administration - I am unable to locate any information on the lock fast fabric wall materials.
Correction

Codes Administration - The structual plans for the shell building indicates that the area in which the rooftop units are located is designed for a maximum weight of 2,000 lbs per unit and curb. Unit HP-1 is shown to weight 2,399 lbs.
Correction

Codes Administration - The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $2,307.90 $2,307.90 Paid 11/03/2009
89 Sewer Tap Fees $240.00 $240.00 Paid 11/03/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 11/09/2009
Correction
Partial Correction
11/09/2009
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY WALLS HIGHLIGHTED ON A1.1
Underslab Plumbing Inspection - Commercial Passed 11/09/2009
Correction
Resolved
11/09/2009
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 11/13/2009
Correction
Partial Correction
11/13/2009
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY WALLS HIGHLIGHTED ON A1.1
All Rough Inspection - Commercial Partial 11/19/2009
Correction
Partial Correction
11/19/2009
WALL FRAMING + IN-WALL SYSTEMS WALL SECTIONS ADDED 11/19/09 PRESENTLY EXCLUDED ARE RATED WALL, EAST EXTERIOR WALL, INTERIOR PARTIAL WALLS NOT YET FRAMED. OK TO COVER WHEN READY WALLS HIGHLIGHTED ON A1.1
Rated Assembly Inspection Not Ready 11/23/2009
Correction
Corrective Action Required
11/23/2009
READINESS FOR INSPECTION CALL FOR INSPECTION AFTER PREPARATION IS COMPLETE WORK REQUESTED FOR INSP NOT COMPLETED
Rated Assembly Inspection Partial 11/25/2009
Correction
Partial Correction
11/25/2009
GWB AT UL-RATED WALLS -- INSIDE FACE ALL EXCEPT S.E. CORNER OK TO COVER WHEN READY WALL SECTIONS BELOW:
Correction
Resolved
11/25/2009
READINESS FOR INSPECTION
All Rough Inspection - Commercial Partial 11/25/2009
Correction
Partial Correction
11/25/2009
WALL FRAMING + IN-WALL SYSTEMS WALL SECTIONS ADDED 11/19/09; STUBS @ DISPLAY WALLS PER (8/A6.1); 103 EAST WALL; FALSE WEST WALL @ RESTROOMS; OK TO COVER WHEN READY WALLS HIGHLIGHTED ON A1.1
Rated Assembly Inspection Passed 12/02/2009
Correction
Resolved
12/02/2009
GWB AT UL-RATED WALLS -- INSIDE FACE INSIDE FACE OF RATED WALL COMPLETE INCLUDING S.E. CORNER -- OK TO TAPE, MUD & FIRE-SEAL OK TO COVER WHEN READY WALL SECTIONS BELOW:
Above Ceiling Inspection Passed 12/04/2009
Correction
Resolved
12/04/2009
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS SUBJECT TO RE-INSPECTION WHEN MISSING CAN LIGHTS ARE INSTALLED. CANOPY ABOVE CHECK/WRAP OK TO COVER WHEN READY
Rated Assembly Inspection Partial 12/04/2009
Correction
Partial Correction
12/04/2009
GWB AT UL-RATED WALLS -- INSIDE FACE INSIDE FACE OF RATED WALL COMPLETE INCLUDING S.E. CORNER -- OK TO TAPE, MUD & FIRE-SEAL OK TO COVER WHEN READY WALL SECTIONS BELOW:
Electrical Service Inspection Passed 12/09/2009
Correction
Resolved
12/09/2009
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE. ENSURE LIVE PARTS ARE PROTECTED PRIOR TO SERVICE ACTIVATION. 600A 277/480V 3P 225 KVA 480V 3P XFRMR
Occupancy Inspection - Codes Commercial Not Ready 12/10/2009
Correction
Corrective Action Required
12/10/2009
ROOFTOP FINAL INSPECTION
Correction
Resolved
12/10/2009
ADDRESS LABELING OF ELECTRICAL SERVICE
Correction
Resolved
12/10/2009
CONNECTION OF TRUSS JOIST BOTTOM CHORD BRACES WELDED @ BAR JOISTS AFTER ROOF DEAD LOAD IN PLACE
Correction
Corrective Action Required
12/10/2009
Receive Water Utilities Approval
Correction
Corrective Action Required
12/10/2009
Receive Fire Department approval
Above Ceiling Inspection Passed 12/28/2009
Correction
Resolved
12/28/2009
ACT GRID AND ABOVE-CEILING SYSTEMS 104; 105; 106; 107; 108 OK TO COVER WHEN READY CEILINGS @ AREAS BELOW:
Correction
Resolved
12/28/2009
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS CANOPY ABOVE CHECK/WRAP OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 01/15/2010
Correction
Corrective Action Required
01/15/2010
SURFACE OF RESTROOM WALLS IBC 1210.1 NOT NON-ABSORBENT TO HEIGHT OF 4' @ FIXTURE
Correction
Resolved
01/15/2010
ROOFTOP FINAL INSPECTION
Correction
Resolved
01/15/2010
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Partial Correction
01/15/2010
Receive Fire Department approval OK FOR TEMP OCCUPANCY SEE ISSUES ON REPORT
Occupancy Inspection - Codes Commercial Failed 01/22/2010
Correction
Resolved
01/22/2010
EGRESS LIGHT @ EAST EXTERIOR DOOR MUST ILLUMINATE EXIT AREA
Correction
Resolved
01/22/2010
SURFACE OF RESTROOM WALLS
Rated Assembly Inspection Passed 01/26/2010
Correction
Resolved
01/26/2010
GWB AT UL-RATED WALLS -- INSIDE FACE
Correction
Resolved
01/26/2010
GWB AT UL RATED WALLS -- BACK FACE TEMPORARY CONCESSION TO ACCOMODATE FUTURE WORK AT ADJACENT SUITE. 5/8" TYPE X GWB SCREWED NOT TAPED/MUDDED/SEALED
All Rough Inspection - Commercial Passed 01/26/2010
Correction
Resolved
01/26/2010
WALL FRAMING + IN-WALL SYSTEMS
Occupancy Inspection - Codes Commercial Passed 01/26/2010
Correction
Resolved
01/26/2010
Receive Fire Department approval PER CPT JOE DIR 1/26/2010
Documents & Images
Date Uploaded File Type Document Name
01/28/2014 Letter DOC012814-001.pdf
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home