Permit Application Status

B0900878


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900878
Building Permit - Commercial
Final Completion
ALTERATION COMMERCIAL
INTERIOR AND EXTERIOR RENOVATIONS
09/02/2009
01/27/2010
09/21/2010
03/30/2010
Locations
Contacts
CASCO CORP, Address:10877 WATSON RD  
ENGINEERED STRUCTURES INC, Address:12400 W OVERLAND RD  
LIN R ROGERS ELECTRICAL CONTRACTORS INC, Address:2050 MARCONI DR SUITE # 200  
OVERLAND PARK HEATING & COOLING INC, Address:16088 FOSTER  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/11/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Fire Department- 2006 IFC 1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building. Exception: Approved temporary means of egress systems and facilities.
Correction

Fire Department- Existing exit lights are not shown. Exit lighting is to remain, or be provided over the front doors.
Correction

Codes Administration - A phasing plan for the project has not been provided.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $3,134.05 $3,134.05 Paid 01/27/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Partial 01/29/2010
Correction
Corrective Action Required
01/29/2010
COURTESY VISIT TO JOBSITE PRE-CONSTR DISCUSSION JB W/ SUPT JAMES
Underslab Electrical Inspection - Commercial Partial 02/01/2010
Correction
Partial Correction
02/01/2010
UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES CASHWRAP RIGHT PER 5/E5; OK TO COVER WHEN READY WORK @FOLLOWING LOCATIONS
All Rough Inspection - Commercial Partial 02/03/2010
Correction
Partial Correction
02/03/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFFICE; MISSES UPDATED + MISSES UPDATED FITTING ROOM; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Above Ceiling Inspection Partial 02/03/2010
Correction
Partial Correction
02/03/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS CASH OFFICE; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Rough Framing Inspection - Commercial Request Complete 2/2/2010 2/3/2010 02/03/2010
Above Ceiling Inspection Partial 02/04/2010
Correction
Partial Correction
02/04/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS CASH OFFICE; MISSES-GIRLS LOUNGE; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
All Rough Inspection - Commercial Partial 02/05/2010
Correction
Partial Correction
02/05/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFFICE; MISSES UPDATED + MISSES UPDATED FITTING ROOM; SEASONAL W WALL; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Partial 02/08/2010
Correction
Partial Correction
02/08/2010
REVISED LIGHT GUAGE STEEL SOFFIT FRAMING EACH SIDE MISSES ENTRANCE OK TO COVER WHEN READY
Underslab Electrical Inspection - Commercial Partial 02/08/2010
Correction
Partial Correction
02/08/2010
UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES CASHWRAP RIGHT PER 5/E5; SEASONAL (LAYOUT REVISED FROM APPROVED PLAN); OK TO COVER WHEN READY WORK @FOLLOWING LOCATIONS
Underground Electrical Inspection - Commercial Request Complete 2/8/2010 2/8/2010 02/08/2010
All Rough Inspection - Commercial Partial 02/11/2010
Correction
Partial Correction
02/11/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFFICE; MISSES UPDATED + MISSES UPDATED FITTING ROOM; SEASONAL W WALL; MEN'S CASUAL; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Request Complete 2/11/2010 2/11/2010 02/11/2010
Underslab Electrical Inspection - Commercial Partial 02/17/2010
Correction
Partial Correction
02/17/2010
UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES CASHWRAP RIGHT PER 5/E5; SEASONAL (LAYOUT REVISED FROM APPROVED PLAN); *17FEB- UNDERSLAB ELECTRICAL IN JEWELRY DEPARTMENT OK TO COVER WHEN READY WORK @FOLLOWING LOCATIONS
All Rough Inspection - Commercial Partial 02/18/2010
Correction
Partial Correction
02/18/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFFICE; MISSES UPDATED + MISSES UPDATED FITTING ROOM; SEASONAL W WALL; MEN'S CASUAL; MISSES CLASSICS; JEWELRY (INCL SOFFIT @ W); OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Request Complete 2/18/2010 2/18/2010 02/18/2010
Underslab Electrical Inspection - Commercial Partial 02/22/2010
Correction
Partial Correction
02/22/2010
UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES CASHWRAP RIGHT PER 5/E5; SEASONAL (LAYOUT REVISED FROM APPROVED PLAN); JEWELRY; CASHWRAP LEFT (MEN'S) PER 5/E5; OK TO COVER WHEN READY WORK @FOLLOWING LOCATIONS
Rough Framing Inspection - Commercial Partial 02/22/2010
Correction
Partial Correction
02/22/2010
REVISED LIGHT GUAGE STEEL SOFFIT FRAMING EACH SIDE MISSES ENTRANCE; MEN'S ENTRANCE COVERED FOR SECURITY -- INSPECTION WAIVED; OK TO COVER WHEN READY FOLLOWING ELEMENTS:
Rough Framing Inspection - Commercial Not Ready 02/24/2010
Correction
Corrective Action Required
02/24/2010
READINESS FOR INSPECTION SUBJECT OF INSPECTION REQUEST UNKNOWN. SUPT NOT AVAILABLE ON JOBSITE
Rough Framing Inspection - Commercial Request Complete 2/24/2010 2/24/2010 02/24/2010
All Rough Inspection - Commercial Partial 02/25/2010
Correction
Partial Correction
02/25/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFFICE; MISSES UPDATED + MISSES UPDATED FITTING ROOM; SEASONAL W WALL; MEN'S CASUAL; MISSES CLASSICS; JEWELRY (INCL SOFFIT @ W); YOUNG MEN'S/STOCKROOM; MISSES UPDATED/ WOMENS/ BOYS/ GIRLS; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Request Complete 2/25/2010 2/25/2010 02/25/2010
All Rough Inspection - Commercial Partial 02/26/2010
Correction
Partial Correction
02/26/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFFICE; MISSES UPDATED + MISSES UPDATED FITTING ROOM; SEASONAL W WALL; MEN'S CASUAL; MISSES CLASSICS; JEWELRY (INCL SOFFIT @ W); YOUNG MEN'S/STOCKROOM; MISSES UPDATED/ WOMENS/ BOYS/ GIRLS; YOUNG MEN'S EAST WALL; T WALL @ LUGGAGE; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Partial 02/26/2010
Correction
Resolved
02/26/2010
READINESS FOR INSPECTION
Rough Framing Inspection - Commercial Request Complete 2/26/2010 2/26/2010 02/26/2010
All Rough Inspection - Commercial Partial 03/01/2010
Correction
Partial Correction
03/01/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFC; MISSES UPDATED INCL FITTING RM; SEASONAL W WALL; MENS CASUAL; MISSES CLASSICS; JEWELRY (INCL SOFFIT @ W); YOUNG MEN'S/STOCKROOM; MISSES UPDATED/ WOMENS/ BOYS/ GIRLS; YOUNG MENS EAST WALL; T WALL @ LUGGAGE; MENS ACTIVE WALLS + SOFFIT; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Above Ceiling Inspection Partial 03/01/2010
Correction
Partial Correction
03/01/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS CASH OFFICE; MISSES-GIRLS LOUNGE; JEWELRY; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Rough Framing Inspection - Commercial Request Complete 3/1/2010 3/1/2010 03/01/2010
All Rough Inspection - Commercial Partial 03/02/2010
Correction
Partial Correction
03/02/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFC; MISSES UPDATED INCL FITTING RM; SEASONAL W WALL; MENS CASUAL; MISSES CLASSICS; JEWELRY (INCL SOFFIT @ W); YOUNG MEN'S/STOCKROOM; MISSES UPDATED/ WOMENS/ BOYS/ GIRLS; YOUNG MENS EAST WALL; T WALL @ LUGGAGE; C.S. RETURNS/WALLS + SOFFIT; CONT'D. OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Partial Correction
03/02/2010
WALL FRAMING + IN-WALL SYSTEMS, CONT'D. JUNIORS FITTING; S.E. ELECTRICAL RM; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Request Complete 3/2/2010 3/2/2010 03/02/2010
All Rough Inspection - Commercial Partial 03/04/2010
Correction
Partial Correction
03/04/2010
WALL FRAMING + IN-WALL SYSTEMS, CONT'D. JUNIORS FITTING; S.E. ELECTRICAL RM; INTIMATES; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 03/09/2010
Correction
Partial Correction
03/09/2010
WALL FRAMING + IN-WALL SYSTEMS, CONT'D. JUNIORS FITTING; S.E. ELECTRICAL RM; INTIMATES; INTIMATES FITTING; INFANTS & TODDLERS; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Request Complete 3/9/2010 3/9/2010 03/09/2010
All Rough Inspection - Commercial Passed 03/11/2010
Correction
Resolved
03/11/2010
WALL FRAMING + IN-WALL SYSTEMS CASH OFC; MISSES UPDATED INCL FITTING RM; SEASONAL W WALL; MENS CASUAL; MISSES CLASSICS; JEWELRY (INCL SOFFIT @ W); YOUNG MEN'S/STOCKROOM; MISSES UPDATED/ WOMENS/ BOYS/ GIRLS; YOUNG MENS EAST WALL; T WALL @ LUGGAGE; C.S. RETURNS/WALLS + SOFFIT; CONT'D. OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Resolved
03/11/2010
WALL FRAMING + IN-WALL SYSTEMS, CONT'D. JUNIORS FITTING; S.E. ELECTRICAL RM; INTIMATES; INTIMATES FITTING; INFANTS & TODDLERS; TOYS OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Framing Inspection - Commercial Request Complete 3/11/2010 3/11/2010 03/11/2010
Above Ceiling Inspection Partial 03/16/2010
Correction
Partial Correction
03/16/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS TOYS; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Occupancy Inspection - Codes Commercial Failed 03/23/2010
Correction
Resolved
03/23/2010
Receive Fire Department approval PER CPT JOE DIR 3/23/2010
Correction
Resolved
03/23/2010
Receive Water Utilities Approval PER BEN HASKAMP 3/23/2010
Correction
Corrective Action Required
03/23/2010
UPDATING OF ELECTRICAL PANEL SCHEDULES TO BE COMPLETED
Correction
Resolved
03/23/2010
FINAL ABOVE CEILING INSPECTION 1) REMOVE/ENCLOSE ANY UNTERMINATED CONDUCTORS 2) SECURE ANY LOOSE BOXES 3) ENSURE ALL BOXES ARE CLOSED CONTINGENT ON CORRECTIONS DESCRIBED BELOW:
Miscellaneous Inspection Passed 03/23/2010
Correction
Resolved
03/23/2010
COURTESY VISIT TO JOBSITE
Above Ceiling Inspection Passed 03/23/2010
Correction
Resolved
03/23/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS CASH OFFICE; MISSES-GIRLS LOUNGE; JEWELRY; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Correction
Resolved
03/23/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS TOYS; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Correction
Resolved
03/23/2010
FINAL ABOVE-CEILING INSPECTION SEE OCCUPANCY INSPECTION
Underslab Electrical Inspection - Commercial Passed 03/23/2010
Correction
Resolved
03/23/2010
UNDER-SLAB ELECTRICAL CONDUIT & FLOOR BOXES CASHWRAP RIGHT PER 5/E5; SEASONAL (LAYOUT REVISED FROM APPROVED PLAN); JEWELRY; CASHWRAP LEFT (MEN'S) PER 5/E5; OK TO COVER WHEN READY WORK @FOLLOWING LOCATIONS
Rough Framing Inspection - Commercial Passed 03/23/2010
Correction
Resolved
03/23/2010
REVISED LIGHT GUAGE STEEL SOFFIT FRAMING EACH SIDE MISSES ENTRANCE; MEN'S ENTRANCE COVERED FOR SECURITY -- INSPECTION WAIVED; OK TO COVER WHEN READY FOLLOWING ELEMENTS:
Occupancy Inspection - Codes Commercial Failed 03/24/2010
Correction
Resolved
03/24/2010
Receive Planning & Development Approval PER CHRISTINA ALEXANDER 3/23/2010
Occupancy Inspection - Codes Commercial Passed 03/25/2010
Correction
Resolved
03/25/2010
UPDATING OF ELECTRICAL PANEL SCHEDULES
Correction
Resolved
03/25/2010
FINAL ABOVE CEILING INSPECTION 1) REMOVE/ENCLOSE ANY UNTERMINATED CONDUCTORS 2) SECURE ANY LOOSE BOXES 3) ENSURE ALL BOXES ARE CLOSED GENERAL CONTRACTOR RESPONSIBLE TO ENSURE COMPLETION CONTINGENT ON CORRECTIONS DESCRIBED BELOW:
Documents & Images
Date Uploaded File Type Document Name
07/31/2017 Kohl's Facade - 1820 NW Chipman Rd
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home