Permit Application Status

B0900827


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900827
Building Permit - Commercial
Certificate of Occupancy
I-470 FRONTAGE INVESTORS LLC
CHANGE OF TENANT
ROLOX WINDOWS TENANT FINISH
08/25/2009
10/06/2009
04/04/2010
01/19/2010
Locations
Contacts
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
KESSINGER HUNTER AND COMPANY LC, Address:2600 GRAND #700  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
GARWIN ELECTRIC LLC, Address:27065 W 102ND  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
I-470 FRONTAGE INVESTORS LLC, Address:% KESSINGER/HUNTER & CO INC  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/03/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Codes Administration - 2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employess shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
Correction

Codes Administration - The suite identifier for this space was not included. The space is Suite A.
Correction

Codes Administration - Plans and specifications for the mechanical, electrical and plumbing work have not been provided.
Correction

Fire Department- 2006 IFC 1008.1.1 Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches (813 mm). Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees (1.57 rad). Where this section requires a minimum clear width of 32 inches (813 mm) and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches (813 mm). The maximum width of a swinging door leaf shall be 48 inches (1219 mm) nominal. Means of egress doors in a Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches (1054 mm). The height of doors shall not be less than 80 inches (2032 mm).
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $510.63 $510.63 Paid 10/06/2009
89 Sewer Tap Fees $30.00 $30.00 Paid 10/06/2009
91 EFHB Maybrook Water Shed $42.61 $42.61 Paid 10/06/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 10/07/2009
Correction
Corrective Action Required
10/07/2009
IN-WALL ALL ROUGH -ALL EMERGENCY LIGHTS SHALL BE INSTALLED PER PLAN -MISSING ONE WALL RECEPTACLE AT RM 105 -BLOCKING REQUIRED FOR RESTROOM 18" VERTICAL GRAB BARS DO NOT ROCK
Rough Framing Inspection - Commercial Request Complete 10/6/2009 10/7/2009 10/07/2009
Rough Framing Inspection - Commercial Request Complete 10/6/2009 10/7/2009 10/07/2009
All Rough Inspection - Commercial Passed 10/09/2009
Correction
Resolved
10/09/2009
IN-WALL ALL ROUGH MERGENCY LIGHTING FOR SHOWROOM 113 AND HALLWAY 108 SHALL BE INSTALLED AND CHECKED LATER. OK TO ROCK WALLS
Above Ceiling Inspection Failed 11/05/2009
Correction
Corrective Action Required
11/05/2009
STRUCTURAL HAVE ENGINEER ADDRESS DISCONNECTED BRACING CABLE BETWEEN RM 105/126.
Correction
Corrective Action Required
11/05/2009
PLENUM RATED MATERIAL ALL LOW VOLTAGE WIRING SHALL BE PLENUM RATED; NO PVC IN PLENUM
Correction
Corrective Action Required
11/05/2009
MECHANICAL CAP OFF ALL UNUSED SUPPLY DUCT OPENINGS
Correction
Corrective Action Required
11/05/2009
ELECTRICAL -ALL BOX AND MC SUPPORT WIRINGS SHALL BE SECURED TO UPPER STRUCTURE AND TO CEILING GRID AS WELL -GENERAL WIRING SUPPORT: 1) MAX. SPACING IS 4.5 FT BETWEEN SECURE POINTS 2) SECURE WITHIN 6 FT OF LIGHTS AND WITHIN 12" OF BOXES
Above Ceiling Inspection Failed 11/19/2009
Correction
Corrective Action Required
11/19/2009
STRUCTURAL HAVE ENGINEER ADDRESS DISCONNECTED BRACING CABLE BETWEEN RM 105/126. FAX. LETTER TO 969-1201
Correction
Resolved
11/19/2009
PLENUM RATED MATERIAL
Correction
Corrective Action Required
11/19/2009
MECHANICAL CAP OFF ALL UNUSED SUPPLY DUCT OPENINGS
Correction
Corrective Action Required
11/19/2009
ELECTRICAL -ALL BOX AND MC SUPPORT WIRINGS SHALL BE SECURED TO UPPER STRUCTURE AND TO CEILING GRID AS WELL -GENERAL WIRING SUPPORT: 1) MAX. SPACING IS 4.5 FT BETWEEN SECURE POINTS 2) SECURE WITHIN 6 FT OF LIGHTS AND WITHIN 12" OF BOXES
Above Ceiling Inspection Failed 11/23/2009
Correction
Corrective Action Required
11/23/2009
STRUCTURAL *HAVE ENGINEER INSPECT KINKED NORTH BRACING CABLE FAX. LETTER TO 969-1201 *OK TO DROP CEILING TILES
Correction
Resolved
11/23/2009
MECHANICAL
Correction
Resolved
11/23/2009
ELECTRICAL
Occupancy Inspection - Codes Commercial Failed 12/01/2009
Correction
Corrective Action Required
12/01/2009
SECURE EMT WITHIN 3 FT OF PANEL
Correction
Corrective Action Required
12/01/2009
Appliance Disconnecting Means (IRC) INSTALL LOCK DEVICE AT BREAKER OR INSTALL SWITCH BY WATER HEATER WATER HEATER IN MECH RM
Correction
Corrective Action Required
12/01/2009
BATHROOMS -GFCI NOT WORKING -BATHFANS NOT WORKING
Correction
Corrective Action Required
12/01/2009
SIGN PERMIT REQUIRED PER TRACY DEISTER
Correction
Corrective Action Required
12/01/2009
ENGINEER LETTER FAX ENGINEER LETTER TO CODE REGARDING WIND BRACING AT SOUTH END OF BUILDING
Correction
Corrective Action Required
12/01/2009
Receive Fire Department approval -SPRINKLER SYSTEM RECERTIFICATION REQUIRED
Occupancy Inspection - Codes Commercial Failed 12/03/2009
Correction
Resolved
12/03/2009
SECURE EMT WITHIN 3 FT OF PANEL
Correction
Resolved
12/03/2009
Appliance Disconnecting Means (IRC)
Correction
Resolved
12/03/2009
BATHROOMS
Correction
Corrective Action Required
12/03/2009
SIGN PERMIT REQUIRED PER TRACY DEISTER/TED STROBACH
Correction
Corrective Action Required
12/03/2009
ENGINEER LETTER FAX REVISED ENGINEER LETTER TO CODE REGARDING WIND BRACING AT SOUTH END OF BUILDING
Correction
Resolved
12/03/2009
Receive Fire Department approval
Above Ceiling Inspection Passed 12/03/2009
Correction
Resolved
12/03/2009
STRUCTURAL
Occupancy Inspection - Codes Commercial Failed 12/08/2009
Correction
Resolved
12/08/2009
ENGINEER LETTER LETTER RECEIVED
Occupancy Inspection - Codes Commercial Passed 01/15/2010
Correction
Resolved
01/15/2010
SIGN PERMIT REQUIRED
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home