Permit Application Status

B0900782


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900782
Building Permit - Commercial
Certificate of Occupancy
LBP III LLC
NEW TENANT FINISH
FULL BUILD-OUT PERMIT
08/10/2009
08/20/2009
03/22/2010
09/25/2009
Locations
Contacts
CLEARLINE PLUMBING, Address:14922 KNORPP RD  
DAVIDSON BROWN, Address:11301 STRANG LINE ROAD  
UNITED HEATING & COOLING, Address:301 DUCK RD  
BLUE SPRINGS ELECTRICAL, Address:3402 LAKESHORE DR  
CAPITAL CONSTRUCTION SERVICES, Address:2642 NE HAGAN RD  
LBP III LLC, Address:3215 NE CARNEGIE DR STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/15/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the evenet of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building requried to have two or more exits. 3. Exterior egress componenets at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2005 NEC 210.63 - Heating, air-conditioning, and refrigeration equipement outlet. A 125-volt, single-phase, 12- or20-ampere-rated receptacle outlet shall be installed at an accessible loction for the servicing of heating, air conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 7.5 m (25 ft) of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2006 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire department- 2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Correction

Fire Department- Information not provided on duct detection.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Codes Administration - 2006 IBC 1008.1.9 - Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds. Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Gourp A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equiped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side.
Correction

Codes Administration - 2006 IBC 1008.1.2 - Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2. Group I-3 occupancies used as a place of detention. 3. Critical or intensive care patient rooms within suites of health care facilities. 4. Doors within or serving a single dwelling unit in Groups R-2 and R-3. 5. In other than Group H occupancies, revolving doors complying with Section 1008.1.3.1. 6. In other than Group H occupancies, horizontal sliding doors complying with Section 1008.1.3.3 are permitted in a means of egress. 7. Power-operated doors in accordance with Section 1008.1.3.2. 8. Doors serving a bathroom within an individual sleeping unit in Group R-1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force of interior side-swinging doors without closers shall not exceed a 5-pound force. For other side-swinging, sliding and folding doors, the door latch shall relase when subjected to a 15-pound force. The door shall be set in motion when subjected to a 30-pound force. The door shall swing to a full-open position when subjected to a 15-pound force. Forces shall be applied to the latch side.
Correction

Codes Administration - I am unable to locate structural information relating to the additional RTU's being installed.
Correction

Codes Administration - Specifications for the plumbing and mechanical installations have not been provided.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $2,180.42 $2,180.42 Paid 08/20/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 08/21/2009
Correction
Partial Correction
08/21/2009
None -102-110/120-121/132-135/DEMISE WALL IN-WALL
All Rough Inspection - Commercial Passed 08/28/2009
Correction
Resolved
08/28/2009
None OK TO ROCK FEW EMERGENCY LIGHTS NOT IN PLACE AT EAST ROOM. IN-WALL
Electrical Service Inspection Failed 09/08/2009
Correction
Corrective Action Required
09/08/2009
STRIP PAINT OFF AT CONNECTION (200 AMP DISCONNECT)
Correction
Corrective Action Required
09/08/2009
GROUNDING JUMPER TO 400 AMP DISCONNECT -EQUIPMENT GROUNDING CONDUCTOR SHALL BE #3 CU OR 1 AL. 250.122
Correction
Corrective Action Required
09/08/2009
EQUIPMENT GROUNDING CONDUCTORS FROM 400 AMP DISCONNECT EACH PARALLEL EGC SHALL BE SIZED PER 250.122 BASED ON 400 AMP BREAKER. #3 CU OR #1 AL. NEC 250.122 (F)
Electrical Service Inspection Passed 09/09/2009
Correction
Resolved
09/09/2009
STRIP PAINT OFF AT CONNECTION (200 AMP DISCONNECT)
Correction
Resolved
09/09/2009
GROUNDING JUMPER TO 400 AMP DISCONNECT
Correction
Resolved
09/09/2009
EQUIPMENT GROUNDING CONDUCTORS FROM 400 AMP DISCONNECT 600 AMP METER-SERVICE APPROVED FOR RELEASE.
Above Ceiling Inspection Failed 09/11/2009
Correction
Corrective Action Required
09/11/2009
None -EAST THIRD INSPECTED. SECURE FLEXIBLE CONDUITS TO RTU AND CIRCUITS TO CUBICLES. OK TO DROP TILES
Gas Service Inspection - Commercial Failed 09/11/2009
Correction
Corrective Action Required
09/11/2009
Gas Test Pressure (IRC)
Above Ceiling Inspection Failed 09/15/2009
Correction
Corrective Action Required
09/15/2009
None -EAST THIRD INSPECTED. SECURE FLEXIBLE CONDUITS TO RTU AND CIRCUITS TO CUBICLES. OK TO DROP TILES -REMAINING-SECURE WIRES TO FIXTURE SUPPORT WIRE; SUPPORT FLEXIBLE DUCT <= 5 FT
Above Ceiling Inspection Passed 09/16/2009
Correction
Resolved
09/16/2009
None OK TO DROP TILES
Gas Service Inspection - Commercial Passed 09/18/2009
Correction
Resolved
09/18/2009
Gas Test Pressure (IRC) GAS SERVICE APPROVED FOR RELEASE
Occupancy Inspection - Codes Commercial Failed 09/23/2009
Correction
Corrective Action Required
09/23/2009
REPLACE ALL RTU BREAKERS WITH SIZES PER LABELS
Correction
Corrective Action Required
09/23/2009
PROTECT ELECTRICAL SERVICE EQUIPMENTS FROM POTENTIAL DAMAGE
Correction
Corrective Action Required
09/23/2009
PAINT GAS LINES
Correction
Corrective Action Required
09/23/2009
FLOOR CLEANOUT SHALL BE ACCESSIBLE
Underslab Electrical Inspection - Commercial Passed 09/23/2009
Occupancy Inspection - Codes Commercial Passed 09/24/2009
Correction
Resolved
09/24/2009
REPLACE ALL RTU BREAKERS WITH SIZES PER LABELS
Correction
Resolved
09/24/2009
PROTECT ELECTRICAL SERVICE EQUIPMENTS FROM POTENTIAL DAMAGE
Correction
Resolved
09/24/2009
PAINT GAS LINES
Correction
Resolved
09/24/2009
FLOOR CLEANOUT SHALL BE ACCESSIBLE
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home