Permit Application Status

B0900775


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900775
Building Permit - Commercial
Final Completion
MJB OF MISSOURI LLC
ALTERATION COMMERCIAL
WHITE BOX TENANT FINISHED FOR SUITES 102 & 107
08/07/2009
09/02/2009
04/27/2010
11/04/2009
Locations
Contacts
DAVIDSON BROWN, Address:11301 STRANG LINE ROAD  
ACCURATE MECHANICAL LLC, Address:1237 ATLANTIC  
F & G MECHANICAL SERVICES INC., Address:17219 BEL-RAY PL  
KBS, Address:1701 SW 41ST ST  
D ELECTRIC LLC, Address:6416 W 194TH ST  
MJB OF MISSOURI LLC, Address:640 NE SHORELINE DR  
INDEPENDENCE SAFTEY STORAGE NORTH LLC, Address:1101 NW PAMELA BLVD UNIT C  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/14/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Fire Department- Alarm appliaces shall be compatible with existing equipment.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Fire Department- 2006 IFC 008.1.3.4 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
Correction

Codes Administration - I have discussed the possible address for these tenant spaces. We feel that the spaces should be addressed 3340 NE Ralph Powell Rd, Suites A and B with the south suite being A. This is consistant with our numbering scheme and allows for the MJB to remain 3350 NE Ralph Powell Rd.
Correction

Codes Administration - 2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation.
Correction

Fire Department- 2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $393.78 $393.78 Paid 09/02/2009
89 Sewer Tap Fees $540.00 $540.00 Paid 09/02/2009
91 EFHB Maybrook Water Shed $766.98 $766.98 Paid 09/02/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 09/11/2009
Correction
Resolved
09/11/2009
None UNDERSLAB CONDUITS TO DISTRIBUTION PANELS-APPROVED
Underslab Plumbing Inspection - Commercial Passed 09/11/2009
Correction
Resolved
09/11/2009
None UNDERSLAB PLUMBING-APPROVED
Electrical Service Inspection Passed 09/15/2009
Correction
Resolved
09/15/2009
None 400 AMP SERVICE METER-APPROVED FOR RELEASE *EXISTING BUILDING ELECTRODE GROUNDING CONDUCTOR INSTALLED BUT CONNECTION TO WATER SERVICE LINE CANNOT BE CONFIRMED.
All Rough Inspection - Commercial Partial 09/21/2009
Correction
Partial Correction
09/21/2009
None -EXTERIOR WALL AND EXISTING MISER WALL OK TO ROCK BELOW
Rough Plumbing Inspection - Commercial Passed 09/24/2009
Correction
Resolved
09/24/2009
None PRESSURE TEST OK
All Rough Inspection - Commercial Partial 09/25/2009
Correction
Partial Correction
09/25/2009
None -EXTERIOR WALL AND EXISTING MISER WALL -INTERIOR WALLS *HORNS & STROBES NOT INSTALLED. OK TO ROCK BELOW
Above Ceiling Inspection Passed 10/02/2009
Correction
Resolved
10/02/2009
None HARD LID CEILINGS ABOVE RESTROOMS AND ENTRY
Gas Piping Inspection - Commercial Passed 10/23/2009
Correction
Resolved
10/23/2009
None GAS PIPING AND PRESSURE TEST OK. GAS SERVICE IS ALREADY RELEASED
All Rough Inspection - Commercial Passed 10/30/2009
Correction
Resolved
10/30/2009
None -EXTERIOR WALL AND EXISTING MISER WALL -INTERIOR WALLS *HORNS & STROBES NOT INSTALLED. OK TO ROCK BELOW
Above Ceiling Inspection Passed 10/30/2009
Correction
Resolved
10/30/2009
None HARD LID CEILINGS ABOVE RESTROOMS AND ENTRY; THE REMAINDER-OK TO DROP
Final Inspection - Commercial Failed 10/30/2009
Correction
Corrective Action Required
10/30/2009
OBTAIN FIRE DEPARTMENT APPROVAL -ALARM SYSTEM NOT INSTALLED PER PLAN.
Final Inspection - Commercial Passed 11/03/2009
Correction
Resolved
11/03/2009
OBTAIN FIRE DEPARTMENT APPROVAL -ALARM SYSTEM NOT INSTALLED PER PLAN. *RECEIVE LETTER AGREEING THAT THE WHITE BOX CANNOT BE OCCUPIED. THE TENANTS WILL BE RESPONSIBLE FOR THE ALARM SYSTEM THEMSELVES WHEN OBTAINING TENANT FINISH PERMITS. FIRE OK
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home