Permit Application Status

B0900694


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900694
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
SAKURA JAPANESE RESTAURANT TENANT FINISH
07/16/2009
08/17/2009
09/14/2010
03/19/2010
Locations
Contacts
GJ ELECTRIC, Address:408 SE TOPAZ DR  
HBT INDUSTRIES, Address:1830 JASPER  
NEEDHAM PLUMBING & MECHANICAL, Address:4425 MISSION RD  
SAKURA, Address:860 NW BLUE PKWY SUITE Y  
ATLAS MECHANICAL SERVICES INC, Address:26015 RA HWY  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/10/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - The plans indicate that the storefront is existing. It was not installed as part of the shell package.
Correction

Codes Administration - It has been our experience that Kansas City Power and light will not allow multiple services/meters for a single tenant space.
Correction

Codes Administration - I am unable to locate details for the construction of the vestibule.
Correction

Codes Administration - 2006 IMC 507.2.2 - Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines.
Correction

Codes Administration - Manufactors specs for the hoods has not been provided.
Correction

Codes Administration - The two roof top units appear to be within the structural zone provided for installation of mechanical equipment per the shell building structural plans. The new kitchen equipment is not.
Correction

Codes Administration - 2006 IPC 1003.3.4.1 - Grease interceptors capacity. Grease interceptors shall have the grease retention capacity indicated in Table 1003.3.4.1 for the flow-through rates indicated.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. The interface of fire safety control functions.
Correction

Fire Department- 2006 IFC 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Codes Administration - 2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm). Exception: Clearance shall not be required from gypsum wallboard attaced to noncombustible structures provided that a smooth, cleanable, nonabsorbant and noncumbustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inces (457 mm) in all directions from the hood.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $879.20 $879.20 Paid 08/17/2009
89 Sewer Tap Fees $510.00 $510.00 Paid 08/17/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Hood/Duct Inspection Not Ready 09/16/2009
Correction
Corrective Action Required
09/16/2009
DESIGNATION OF LICENSED MECHANICAL CONTRACTOR NOT DESIGNATED ON PERMIT PRIOR TO COMMENCEMENT
Underslab Plumbing Inspection - Commercial Partial 09/25/2009
Correction
Partial Correction
09/25/2009
INSTALLATION PER DESIGN PROVIDE DRAIN FOR DISHWASHER TO APPROVED LOCATION. APPROVED TO COVER ALL PLUMBING EXCEPT IN NORTH HALF OF KITCHEN.
All Rough Inspection - Commercial Partial 10/01/2009
Correction
Partial Correction
10/01/2009
WALL FRAMING + IN-WALL SYSTEMS TRANSOM AREA ABOVE EAST ENTRANCE; EAST 35' OF NORTH WALL; EAST 45' OF SOUTH WALL ABOVE 10' ELEVATION; **NO CONCEALED M/E/P WORK TO BE INSTALLED IN THESE AREAS AFTER PLACEMENT OF DRYWALL** OK TO COVER WHEN READY FOLLOWING WALL SEGMENTS:
Electrical Service Inspection Not Ready 10/02/2009
Correction
Corrective Action Required
10/02/2009
CONFIGURATION OF SERVICE AS DESIGNED MEETING ON-SITE 10/2/09 NOT CORRECT FOR SITUATION PER ELECT CONTRACTOR
Underslab Plumbing Inspection - Commercial Passed 10/02/2009
Correction
Resolved
10/02/2009
INSTALLATION PER DESIGN
Correction
Resolved
10/02/2009
UNDER-SLAB WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Rough Plumbing Inspection - Commercial Passed 10/07/2009
Correction
Resolved
10/07/2009
PRESSURE TEST OF TOP ROUGH PLUMBING PIPING
Hood/Duct Inspection Failed 10/08/2009
Correction
Corrective Action Required
10/08/2009
LIGHT TEST OF GREASE DUCT WELDS PINHOLES IN SHOP WELDS
Correction
Resolved
10/08/2009
DESIGNATION OF LICENSED MECHANICAL CONTRACTOR
All Rough Inspection - Commercial Not Ready 10/15/2009
Correction
Corrective Action Required
10/15/2009
READINESS FOR INSPECTION IBC 109.1 WORK REQUESTED FOR INSP ALREADY COVERED
All Rough Inspection - Commercial Not Ready 10/16/2009
Correction
Resolved
10/16/2009
READINESS FOR INSPECTION
Correction
Corrective Action Required
10/16/2009
PROTECTION OF COPPER PIPING INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL AT PENETRATION OF STEEL FRAMING MEMBERS
Rated Assembly Inspection Not Ready 10/16/2009
Correction
Corrective Action Required
10/16/2009
FIRE-SEALING OF RATED WALL MEMBRANE PENETRATIONS ENTIRE ANNULAR CUT-OUT AREA MUST BE FILLED WITH APPROVED FIRE CAULK OR OTHER APPROVED MATERIAL. ALL PENETRATIONS BY STRUCTURAL ELEMENTS OR M/E/P SYSTEM COMPONENTS. TAPE/MUD SEALING NOT APPROVED @ WEST WALL
Correction
Corrective Action Required
10/16/2009
PVC PIPE PENETRATION OF RATED WALL MEMBRANE WEST WALL @ EGRESS CORRIDOR NOT APPROVED UNLESS PROTECTED BY FIRE COLLAR
Correction
Corrective Action Required
10/16/2009
FASTENING OF GWB TO FRAMING ALL REQUIRED SCREWS MUST BE VISIBLE. 1HR RATED WEST WALL TAPED/MUDDED W/O APPROVAL
All Rough Inspection - Commercial Passed 10/20/2009
Correction
Resolved
10/20/2009
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY ALL WALL SEGMENTS
Correction
Resolved
10/20/2009
PROTECTION OF COPPER PIPING
All Rough Inspection - Commercial Passed 10/30/2009
Correction
Resolved
10/30/2009
READINESS FOR INSPECTION
Rated Assembly Inspection Partial 10/30/2009
Correction
Partial Correction
10/30/2009
PVC PIPE PENETRATION OF RATED WALL MEMBRANE TWO PVC PENETRATIONS LOW ON WALL. FIRE COLLARS INSTALLED EXCEPT @ NW CORNER
Hood/Duct Inspection Partial 10/30/2009
Correction
Partial Correction
10/30/2009
LIGHT TEST OF GREASE DUCT WELDS FIELD WELDS SUBJECT TO APPROVAL SHOP WELDS OK ON THREE DUCT SECTIONS
All Rough Inspection - Commercial Passed 11/02/2009
Hood/Duct Inspection Partial 11/02/2009
Rated Assembly Inspection Partial 11/03/2009
Correction
Partial Correction
11/03/2009
FIRE-SEALING OF RATED WALL MEMBRANE PENETRATIONS OK TO TAPE/MUD/FIRE-SEAL WEST WALL @ EGRESS CORR
Correction
Partial Correction
11/03/2009
PVC PIPE PENETRATION OF RATED WALL MEMBRANE FIRE COLLARS INSTALLED EXCEPT ONE @ KITCHEN
Correction
Resolved
11/03/2009
FASTENING OF GWB TO FRAMING
Rated Assembly Inspection Partial 11/05/2009
Correction
Resolved
11/05/2009
FIRE-SEALING OF RATED WALL MEMBRANE PENETRATIONS WEST WALL @ EGRESS CORR
Correction
Partial Correction
11/05/2009
PVC PIPE PENETRATION OF RATED WALL MEMBRANE FIRE COLLARS INSTALLED EXCEPT ONE @ KITCHEN
Gas Piping Inspection - Commercial Not Ready 11/17/2009
Correction
Corrective Action Required
11/17/2009
SUPPORT OF RIGID STEEL PIPING @ ROOFTOP IFGC 415; IRC G2423: 3/4" OR 1" PIPE -- 8" MAX SPACING; 1-1/4" OR LARGER PIPE -- 10" MAX SPACING; ALSO, SUPPORT NEAR ALL JOINTS. INCOMPLETE HORIZONTAL RUNS
Correction
Corrective Action Required
11/17/2009
READINESS FOR INSPECTION COMPLETE ALL PIPING BEFORE REQUESTING INSPECTION. PIPING TO APPLIANCES NOT COMPLETED
Gas Service Inspection - Commercial Not Ready 11/17/2009
Correction
Corrective Action Required
11/17/2009
READINESS FOR INSPECTION REQUESTING PRESSURE TEST VISUAL INSPECTION OF PIPE MUST BE APPROVED BEFORE
Electrical Service Inspection Passed 11/19/2009
Correction
Resolved
11/19/2009
CONFIGURATION OF SERVICE AS DESIGNED MEETING ON-SITE 10/2/09 NOT CORRECT FOR SITUATION PER ELECT CONTRACTOR
Correction
Resolved
11/19/2009
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE 480V 3P; XFRMR TWO 200A PANELS
Gas Service Inspection - Commercial Not Ready 12/02/2009
Correction
Corrective Action Required
12/02/2009
READINESS FOR INSPECTION REQUESTING PRESSURE TEST VISUAL INSPECTION OF PIPE MUST BE APPROVED BEFORE
Gas Piping Inspection - Commercial Failed 12/03/2009
Correction
Corrective Action Required
12/03/2009
PROTECTION OF EXPOSED STEEL PIPING WHEN OUTDOOR TEMPERATURE IS ABOVE 40 DEGREES ROOFTOP PAINT ALL PIPE
Correction
Corrective Action Required
12/03/2009
PIPING TO WATER HEATER NOT SECURED TO WALL + DIRT LEG CAP CONSTRAINED
Correction
Corrective Action Required
12/03/2009
SUPPORT OF RIGID STEEL PIPING @ ROOFTOP RE-POSITION ONE SUPPORT TO NEAR TEE AS POINTED-OUT; SECURE COMPONENTS OF "STACKED" SUPPORTS; PROPERLY ATTACH SLIP SHEETS TO ANY WOOD SUPPORTS IN CONTACT WITH ROOF INCOMPLETE HORIZONTAL RUNS
Correction
Resolved
12/03/2009
READINESS FOR INSPECTION
Gas Service Inspection - Commercial Failed 12/03/2009
Correction
Corrective Action Required
12/03/2009
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY TO LOAD SIDE ENTRY PIPE (NOT ON METER). WHERE 2 OR MORE SERVICES APPLY PERMANENT TAG
Correction
Corrective Action Required
12/03/2009
PRESSURE GUAGE REPLACE GUAGE AND PRESSURIZE TO >= 10 PSI; REQUEST RE-INSPECTION DOES NOT "ZERO" WHEN PRESSURE IS LET OFF
Correction
Corrective Action Required
12/03/2009
READINESS FOR INSPECTION REQUESTING PRESSURE TEST VISUAL INSPECTION OF PIPE MUST BE APPROVED BEFORE
Gas Service Inspection - Commercial Not Ready 12/04/2009
Correction
Corrective Action Required
12/04/2009
READINESS FOR INSPECTION PIPING NOT PRESSURED-UP FOR PRESSURE TEST. REQUEST RE-INSPECTION WHEN ALL ISSUES ARE RESOLVED AND PIPE IS UNDER TEST PRESSURE. WORK REQUESTED FOR INSP NOT COMPLETED
Gas Piping Inspection - Commercial Not Ready 12/04/2009
Above Ceiling Inspection Failed 12/08/2009
Correction
Corrective Action Required
12/08/2009
ATTACHMENTS TO CEILING SUPPORT WIRES ONLY TO SUPPORT GRID ATTACH NOTHING ELSE
Correction
Corrective Action Required
12/08/2009
WELDING OF BOTTOM CHORD BRACES ENSURE ENDS WELDED TO BAR JOISTS
Correction
Corrective Action Required
12/08/2009
WET PIPING ABOVE ELECTRICAL EQUIPMENT NEC 110.26(F)(1)(b) WITHOUT PROTECTION FOR EQUIPMENT BELOW
Correction
Corrective Action Required
12/08/2009
ELECTRICAL JUNCTION BOXES ONE FOUND OPEN CHECK / CLOSE ALL
Correction
Corrective Action Required
12/08/2009
DUCTING OF RESTROOM EXHAUST FANS NOT FOUND DUCTED TO ABOVE ROOF
Correction
Corrective Action Required
12/08/2009
GREASE DUCTS FROM HOOD NOTICE: LIGHT TEST MUST BE PERFORMED AND APPROVED BY INSPECTOR BEFORE WRAP IS APPLIED. NOT FIRE-WRAPPED PER DRAWING NOTES
Gas Piping Inspection - Commercial Failed 12/08/2009
Correction
Resolved
12/08/2009
PIPING TO WATER HEATER
Correction
Resolved
12/08/2009
SUPPORT OF RIGID STEEL PIPING @ ROOFTOP
Gas Service Inspection - Commercial Passed 12/08/2009
Correction
Resolved
12/08/2009
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY
Correction
Resolved
12/08/2009
PRESSURE GUAGE
Correction
Resolved
12/08/2009
READINESS FOR INSPECTION
Above Ceiling Inspection Partial 12/11/2009
Correction
Resolved
12/11/2009
ATTACHMENTS TO CEILING SUPPORT WIRES
Correction
Resolved
12/11/2009
WELDING OF BOTTOM CHORD BRACES
Correction
Partial Correction
12/11/2009
WET PIPING ABOVE ELECTRICAL EQUIPMENT NEC 110.26(F)(1)(b): WATER PIPING ABOVE EQUIPMENT AREA WITHOUT PROTECTION FOR EQUIPMENT BELOW
Correction
Resolved
12/11/2009
ELECTRICAL JUNCTION BOXES
Correction
Resolved
12/11/2009
DUCTING OF RESTROOM EXHAUST FANS
Correction
Resolved
12/11/2009
GREASE DUCTS FROM HOOD
Correction
Corrective Action Required
12/11/2009
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS DO NOT PLACE TILE ADJACENT TO ELECTRICAL EQUIPMENT AREA ALSO, SPRINKLER HEAD YET TO BE LOWERED TO CEILING AT SOUTH ENTRANCE TO KITCHEN. OK TO COVER WHEN READY ALL AREAS EXCEPT BELOW
Above Ceiling Inspection Passed 12/23/2009
Correction
Resolved
12/23/2009
WET PIPING ABOVE ELECTRICAL EQUIPMENT
Correction
Resolved
12/23/2009
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY ALL ACT & GWB AREAS
Miscellaneous Inspection Failed 01/22/2010
Correction
Corrective Action Required
01/22/2010
LIGHTED SIGN INSPECTION
Miscellaneous Inspection Passed 01/25/2010
Correction
Resolved
01/25/2010
LIGHTED SIGN INSPECTION THEREFORE UL LISTING NOT REQUIRED E.C. CONTRACTOR STATES LIGHTED SIGNS ARE 12V
Occupancy Inspection - Codes Commercial Failed 01/29/2010
Correction
Resolved
01/29/2010
Receive Fire Department approval PER CPT JOE DIR
Correction
Corrective Action Required
01/29/2010
SIDEWALL GRAB BARS AT RESTROOMS PER ANSI NOT INSTALLED
Correction
Corrective Action Required
01/29/2010
PADDING OF PIPING UNDER H.C. RESTROOM LAVS/SINKS NOT INSTALLED ADA/ANSI
Correction
Corrective Action Required
01/29/2010
APPROVAL OF GREASE HOODS SEE DETAIL ELSEWHERE
Hood/Duct Inspection Failed 01/29/2010
Correction
Corrective Action Required
01/29/2010
SMOKE CAPTURE TEST NOT CLOSE TO FULL CAPTURE NOT APPROVED
Correction
Corrective Action Required
01/29/2010
MODIFICATIONS TO MANUFACTURED HOOD LOUVERS AT FRONT VERIFY WITH MANUFACTURER
Hood/Duct Inspection Failed 02/01/2010
Correction
Corrective Action Required
02/01/2010
SMOKE CAPTURE TEST FULL CAPTURE NOT DEMONSTATED
Correction
Corrective Action Required
02/01/2010
COMMERCIAL KITCHEN HOOD PERFORMANCE TESTS IMC 507.16: SEE PRO BALANCE REPORT DTD JANUARY 15, 2010 ACTUAL PERFORMANCE BELOW REQUIRED MINIMUMS
Occupancy Inspection - Codes Commercial Failed 02/01/2010
Correction
Resolved
02/01/2010
PADDING OF PIPING UNDER H.C. RESTROOM LAVS/SINKS
Correction
Corrective Action Required
02/01/2010
ROOFTOP GREASE EXHAUST FAN MOUNTING IMC 506.5.3: ELECTRICAL WHIP MUST ACCOMDATE HINGE OPERATION MUST BE HINGED FOR INSPECTION / CLEANING
Correction
Corrective Action Required
02/01/2010
PAINTING OF ROOFTOP GAS PIPING NOT COMPLETED
Correction
Corrective Action Required
02/01/2010
REMOVAL OF DEBRIS @ ROOFTOP
Correction
Corrective Action Required
02/01/2010
DIRT LEGS AT ROOFTOP GAS PIPING TO RTU'S INSTALLED UPSTREAM OF SHUT-OFF VALVES
Rated Assembly Inspection Passed 02/04/2010
Correction
Resolved
02/04/2010
PVC PIPE PENETRATION OF RATED WALL MEMBRANE
Hood/Duct Inspection Failed 02/04/2010
Correction
Resolved
02/04/2010
LIGHT TEST OF GREASE DUCT WELDS
Occupancy Inspection - Codes Commercial Failed 02/05/2010
Correction
Resolved
02/05/2010
APPROVAL OF GREASE HOODS
Correction
Corrective Action Required
02/05/2010
PAINTING OF ROOFTOP GAS PIPING WHEN OUTDOOR TEMPERATURE IS ABOVE 40 DEGREES TO BE COMPLETED PER IFGC 404.8
Correction
Resolved
02/05/2010
REMOVAL OF DEBRIS @ ROOFTOP ENSURE ROOF IS CLEAR OF ALL METAL DEBRIS
Correction
Resolved
02/05/2010
DIRT LEGS AT ROOFTOP GAS PIPING TO RTU'S
Hood/Duct Inspection Passed 02/05/2010
Correction
Resolved
02/05/2010
SMOKE CAPTURE TEST WAIVED BASED ON PRO BALANCE RPT
Correction
Resolved
02/05/2010
MODIFICATIONS TO MANUFACTURED HOOD PER PERMIT HOLDER (PETER) GRILLES AT FRONT VERIFIED W/ MANUFACTURER
Correction
Resolved
02/05/2010
COMMERCIAL KITCHEN HOOD PERFORMANCE TESTS IMC 507.16 PRO BALANCE REPORT DTD FEBRUARY 3, 2010
Gas Piping Inspection - Commercial Passed 02/05/2010
Correction
Resolved
02/05/2010
PROTECTION OF EXPOSED STEEL PIPING SEE OCCUPANCY INSPECTION
Occupancy Inspection - Codes Commercial Failed 02/08/2010
Correction
Resolved
02/08/2010
SIDEWALL GRAB BARS AT RESTROOMS
Occupancy Inspection - Codes Commercial Failed 02/11/2010
Correction
Resolved
02/11/2010
ROOFTOP GREASE EXHAUST FAN MOUNTING
Occupancy Inspection - Codes Commercial Failed 02/26/2010
Correction
Corrective Action Required
02/26/2010
REAR DOOR TO RATED CORRIDOR OPENING NOT APPROVED FRAME NOT WELDED UL LABLE IN QUESTION
Occupancy Inspection - Codes Commercial Passed 03/18/2010
Correction
Resolved
03/18/2010
REAR DOOR TO RATED CORRIDOR
Correction
Resolved
03/18/2010
PAINTING OF ROOFTOP GAS PIPING
Correction
Resolved
03/18/2010
REMOVAL OF DEBRIS @ ROOFTOP
Occupancy Inspection - Codes Commercial Passed 03/19/2010
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home