Permit Application Status

B0900645


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900645
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
TENANT FINISH
07/09/2009
07/28/2009
04/25/2010
11/19/2009
Locations
Contacts
MEYER COMPLETE, Address:200 NE MISSOURI RD  
KLOVER ARCHITECTS, Address:10955 LOWELL AVE  
MIDWEST HEATING COOLING & PLUMBING, Address:13228 HOLMES RD  
MEYER BROTHERS BUILDING COMPANY, Address:200 NE MISSOURI RD  
MIDWEST HEATING COOLING & PLUMBING, Address:13228 HOLMES RD  
MIDWEST HEATING COOLING & PLUMBING, Address:13228 HOLMES RD  
MIDWEST HEATING COOLING & PLUMBING, Address:13228 HOLMES RD  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/20/2010 10/29/2010
Correction

Fire Department- 2006 IFC 408.11.2 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Codes Administration - ICC/ANSI A117 2003 803.4 - Benches. A bench complying with Section 903 shall be provided within the room.
Correction

Codes Administration - ICC/ANSI A117 2003 803.5 - Coat hooks and shelves. Accessible coat hooks provided within the room shall accommodate a forward reach or side reach complying with Section 308. Where provided, a shelf shall be 40 inches minimum and 48 inches maximum above the floor.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture.
Correction

Codes Administration - Per the approved shell plans, the rear wall of the tenant space is a UL U465 assembly.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances.
Correction

Codes Administration - The plans indicate that there is an existing store front. There is not.
Correction

Codes Administration - I don't believe the door from the space to the rear corridor has been installed.
Correction

Codes Administration - The rear wall of the space is a listed one-hour fire-resistant assembly. Note 6 needs to provide more detail for the infill at the door relocation.
Correction

Codes Administration - Framing details for the door relocation have not been provided.
Correction

Codes Administration - 2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $659.40 $659.40 Paid 07/28/2009
89 Sewer Tap Fees $90.00 $90.00 Paid 07/28/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Passed 08/06/2009
Correction
Resolved
08/06/2009
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY
Underslab Plumbing Inspection - Commercial Passed 08/06/2009
Correction
Resolved
08/06/2009
UNDER-SLAB WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Electrical Service Inspection Passed 08/25/2009
Correction
Resolved
08/25/2009
ELECTRICAL SERVICE INSTALLATION PERMANENT ADDRESS LABELING OF MAIN LOAD-SIDE DISCONNECT TO BE AFFIXED PRIOR TO FINAL INSPECTION. 277/480V, 3P, 100A RELEASE SERVICE
Above Ceiling Inspection Passed 09/01/2009
Correction
Resolved
09/01/2009
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY RESTROOM
Gas Piping Inspection - Commercial Failed 09/01/2009
Correction
Corrective Action Required
09/01/2009
ROOFTOP GAS PIPING 1) PIPE NOT PROTECTED FROM CORROSION -- ENTIRE SURFACE 2) NO CAREY TREAD OR APPROVED EQUAL UNDER BLOCKS 3) CLAMPS TIGHT TO PIPE -- CONTRARY TO DRAWING NOTE SEE ISSUES BELOW:
Gas Service Inspection - Commercial Passed 09/01/2009
Correction
Resolved
09/01/2009
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Occupancy Inspection - Codes Commercial Failed 09/03/2009
Correction
Partial Correction
09/03/2009
Receive Fire Department approval APPROVAL OF SHELL PERMIT REQUIRED FOR FULL COFO
Correction
Corrective Action Required
09/03/2009
IDENTIFICATION OF GAS SERVICE ENTRY TO LOAD SIDE ENTRY PIPE (NOT ON METER) WHERE 2 OR MORE SERVICES APPLY ADDRESS TAG
Correction
Resolved
09/03/2009
SUPPORT OF ELECTRICAL TRANSFORMER FROM ROOF JOISTS A/E LETTER DATED 8/27/09
Occupancy Inspection - Codes Commercial Failed 09/08/2009
Correction
Resolved
09/08/2009
Receive Fire Department approval PER CPT JOE DIR 9/4/09
Correction
Corrective Action Required
09/08/2009
APPROVAL OF SHELL PERMIT FINAL INSPECTION REQUIRED FOR FULL COFO
Occupancy Inspection - Codes Commercial Failed 09/28/2009
Correction
Resolved
09/28/2009
APPROVAL OF SHELL PERMIT FINAL INSPECTION
Correction
Resolved
09/28/2009
ENGINEER ASSESSMENT OF RTU SUPERIMPOSED LOAD APEX ENGRG LTR RECEIVED DATED 9/17/09
Occupancy Inspection - Codes Commercial Failed 10/28/2009
Occupancy Inspection - Codes Commercial Passed 11/17/2009
Correction
Resolved
11/17/2009
IDENTIFICATION OF GAS SERVICE ENTRY
Gas Piping Inspection - Commercial Passed 11/18/2009
Correction
Resolved
11/18/2009
ROOFTOP GAS PIPING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home