Summary
B0900201
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
JAKES SUMMIT TENANT FINISH IN NEW SHELL - RETAIL CLOTHES AND ACCESSORIES
03/24/2009
04/14/2009
06/15/2010
12/29/2009
Locations
Contacts
TEMP CON INC, Address:15670 S. KEELER  
MARTIN ELECTRIC LLC, Address:1542 E SPRUCE  
ACCURATE MECHANICAL LLC, Address:1237 ATLANTIC  
NOLTE & ASSOCIATES, Address:9400 REEDS ROAD SUITE 200  
PHOENIX BUILDING GROUP, Address:7387 W 162ND ST, STE 200  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/11/2009 10/29/2010
Correction

Fire Department- 2006 IFC 408.11.2 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Fire Department- 2006 IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
Correction

Fire Department- 2006 IFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Codes Administration - It appears from the wall sections on Sheet A1.1 that wall type A is to be constructed per UL U419. This should be indicated on the wall type information on Sheet A1.
Correction

Codes Administration - The electrical plans provided have not been signed and sealed by an engineer.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $456.61 $456.61 Paid 04/14/2009
89 Sewer Tap Fees $90.00 $90.00 Paid 04/14/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 05/14/2009
Correction
Resolved
05/14/2009
READINESS FOR INSPECTION
Correction
Resolved
05/14/2009
UNDER-SLAB WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY 5# PRESSURE TEST NOTED
All Rough Inspection - Commercial Failed 06/03/2009
Correction
Corrective Action Required
06/03/2009
WALL FRAMING + IN-WALL SYSTEMS NOT APPROVED TO COVER
Correction
Corrective Action Required
06/03/2009
PROTECTION OF PVC PIPING FROM PENETRATION IPC 305.8: INSTALL SHIELD PLATES AT STUDS & TRACKS. SHIELD PLATES SHALL COVER THE AREA OF THE PIPE WHERE THE MEMBER IS NOTCHED OR BORED AND SHALL EXTEND A MINIMUM OF 2" ABOVE SOLE PLATES & BELOW TOP PLATES. CHECK ALL. WHERE < 1-1/2" FROM FACE OF FRAMING TO RECEIVE GWB
Correction
Corrective Action Required
06/03/2009
MOUNTING OF IN-WALL ELECTRICAL BOXES AT 6" DEMISING WALL 4" STAND-OFFS INEFFECTIVE
Correction
Corrective Action Required
06/03/2009
GROUNDING OF METAL ELECTRICAL BOXES SOME NOT TERMINATED
Gas Service Inspection - Commercial Failed 06/04/2009
Correction
Resolved
06/04/2009
GAS PIPING PRESSURE TEST PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Correction
Corrective Action Required
06/04/2009
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY (NOT ON METER) APPLY PERMANENT TAG TO LOAD SIDE ENTRY PIPE
All Rough Inspection - Commercial Partial 06/04/2009
Correction
Resolved
06/04/2009
WALL FRAMING + IN-WALL SYSTEMS ELECT BOX GROUNDS SUBJECT TO APPROVAL WHEN TERMINATED OK TO COVER WHEN READY
Correction
Resolved
06/04/2009
PROTECTION OF PVC PIPING FROM PENETRATION
Correction
Resolved
06/04/2009
MOUNTING OF IN-WALL ELECTRICAL BOXES
Above Ceiling Inspection Partial 08/14/2009
Correction
Partial Correction
08/14/2009
SEE COMMENT APPROVAL TO COVER GRANTED CONTINGENT UPON MAINTAINING ACCESS FOR INSPECTION OF MOUNTING/CONNECTION OF PERIMETER TRACK LIGHTING. (NON-LANDED WHIPS)
All Rough Inspection - Commercial Passed 08/14/2009
Correction
Resolved
08/14/2009
GROUNDING OF METAL ELECTRICAL BOXES
Above Ceiling Inspection Failed 08/21/2009
Correction
Resolved
08/21/2009
SEE COMMENT
Correction
Corrective Action Required
08/21/2009
CEILING SUPPORT WIRES ROUTE DIRECT FROM ABOVE TO T-BAR POINT OF ATTACH
Electrical Service Inspection Partial 08/21/2009
Correction
Corrective Action Required
08/21/2009
SUPPORT OF TRANSFORMER FROM BOTTOM CHORD TO BE APPROVED BY ARCHITECT/ENGINEER OF BAR JOIST AND TRUSS JOIST
Correction
Resolved
08/21/2009
ELECTRICAL SERVICE INSTALLATION 277/480V 4W 3P 150A
Electrical Service Inspection Failed 08/24/2009
Correction
Corrective Action Required
08/24/2009
PERMANENT LABELING OF ELECTRICAL SERVICE METER/DISCONNECT NOT FOUND AT METER BANK LABEL SUITE-SPECIFIC
Occupancy Inspection - Codes Commercial Failed 08/24/2009
Correction
Corrective Action Required
08/24/2009
ELECTRICAL RECEPTACLE AT RTU NEC 406.8 WEATHERPROOF COVER REQ'D
Correction
Corrective Action Required
08/24/2009
PAINTING OF ROOFTOP GAS PIPING NOT COMPLETED COVER ENTIRE SURFACE
Correction
Corrective Action Required
08/24/2009
ELECTRICAL PANEL SCHEDULES NEC 110-22; 384-13: EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. LABEL UNUSED BREAKERS "SPARE" TO BE IN PLACE
Correction
Corrective Action Required
08/24/2009
GAS SERVICE INSPECTION NOT REQUESTED TO DATE SERVICE NOT RELEASED
Correction
Corrective Action Required
08/24/2009
ELECTRICAL RECEPTACLE AT RESTROOM APPARENT GROUND FAULT
Correction
Corrective Action Required
08/24/2009
APPROVAL OF SHELL PERMIT FINAL INSPECTION PENDING VCC RESPONSIBILITY
Correction
Corrective Action Required
08/24/2009
Receive Fire Department approval
Above Ceiling Inspection Passed 08/25/2009
Correction
Resolved
08/25/2009
CEILING SUPPORT WIRES
Electrical Service Inspection Passed 08/25/2009
Correction
Resolved
08/25/2009
PERMANENT LABELING OF ELECTRICAL SERVICE METER/DISCONNECT SEE FINAL INSPECTION
Correction
Resolved
08/25/2009
SUPPORT OF TRANSFORMER FROM BOTTOM CHORD SEE FINAL INSPECTION
Occupancy Inspection - Codes Commercial Failed 08/25/2009
Correction
Corrective Action Required
08/25/2009
PERMANENT LABELING OF ELECTRICAL SERVICE DISCONNECT NOT FOUND AT METER BANK LABEL SUITE-SPECIFIC
Correction
Corrective Action Required
08/25/2009
SUPPORT OF ELECT TRANSFORMER TO BE APPROVED BY ARCHITECT/ENGINEER FROM BOTTOM CHORD OF BAR/TRUSS JOISTS
Correction
Resolved
08/25/2009
GAS SERVICE INSPECTION
Correction
Resolved
08/25/2009
ELECTRICAL RECEPTACLE AT RESTROOM
Gas Service Inspection - Commercial Passed 08/25/2009
Correction
Resolved
08/25/2009
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY
Occupancy Inspection - Codes Commercial Failed 09/28/2009
Correction
Resolved
09/28/2009
SUPPORT OF ELECT TRANSFORMER ENGINEER LTR RECEIVED
Correction
Resolved
09/28/2009
APPROVAL OF SHELL PERMIT FINAL INSPECTION
Occupancy Inspection - Codes Commercial Failed 10/28/2009
Occupancy Inspection - Codes Commercial Failed 11/17/2009
Correction
Resolved
11/17/2009
ELECTRICAL RECEPTACLE AT RTU
Correction
Resolved
11/17/2009
PERMANENT LABELING OF ELECTRICAL SERVICE DISCONNECT
Correction
Resolved
11/17/2009
PAINTING OF ROOFTOP GAS PIPING
Correction
Resolved
11/17/2009
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Failed 12/15/2009
Correction
Resolved
12/15/2009
Receive Fire Department approval PER CPT JOE DIR 12/15/09
Occupancy Inspection - Codes Commercial Failed 12/18/2009
Correction
Corrective Action Required
12/18/2009
ELECTRICAL PANEL SCHEDULES ALSO, PANEL AT LEFT LABEL MISSING SCHEDULE @ PANEL A DOES NOT MATCH POSTION #s
Occupancy Inspection - Codes Commercial Passed 12/28/2009
Correction
Resolved
12/28/2009
ELECTRICAL PANEL SCHEDULES
Documents & Images
Date Uploaded File Type Document Name
09/19/2017 B0900201jakessummitcomments1
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home