Permit Application Status

B0900193


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0900193
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
ALTER EXISTING WOMEN'S CARE FACILITY TO ACCOMMODATE INSTALLATION OF NEW BREAST MRI
03/18/2009
04/15/2009
03/13/2010
09/16/2009
Locations
Contacts
P1 GROUP INC, Address:16210 WEST 108TH ST  
SHAW ELECTRIC COMPANY, Address:3600 FULLER AVE  
P1 GROUP INC, Address:16210 WEST 108TH ST  
J E DUNN CONSTRUCTION, Address:929 HOLMES  
P1 GROUP INC, Address:16210 WEST 108TH ST  
ACI BOLAND, Address:11229 NALL SUITE 140  
P1 GROUP INC, Address:16210 WEST 108TH ST  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/04/2009 10/29/2010
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Fire Department- Provide appropriate warning signage for the cryogenic liquid.
Correction

Codes Administration - 2006 IBC 1109.12.1 - Dressing, fitting and locker rooms. Where dressing rooms, fitting rooms or locker rooms are provided, at least 5 percent, but not less than one, of each type of use in each cluster provided shall be accessible.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Fire Department- 2006 IFC 1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building. Exception: Approved temporary means of egress systems and facilities.
Correction

Fire Department- 2006 IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
Correction

Planning and Development - Commercial buisnesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $2,754.73 $2,754.73 Paid 04/15/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 04/28/2009
Correction
Resolved
04/28/2009
UNDER-SLAB WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Underslab Plumbing Inspection - Commercial Passed 04/29/2009
Underslab Electrical Inspection - Commercial Passed 04/29/2009
Correction
Resolved
04/29/2009
FLOOR BOXES @ ROOM 216A NO ISSUES ON BOXES CONDUIT ALREADY COVERED
All Rough Inspection - Commercial Partial 05/20/2009
Correction
Partial Correction
05/20/2009
WALL FRAMING + IN-WALL SYSTEMS 215A&B STEEL STUD WALL; 221; 213B; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 05/20/2009
Rough Framing Inspection - Commercial Request Complete 5/19/2009 5/20/2009 05/20/2009
All Rough Inspection - Commercial Partial 05/26/2009
Correction
Partial Correction
05/26/2009
WALL FRAMING + IN-WALL SYSTEMS 215A&B STEEL STUD WALL; 221 INCLUDING WEST WALL; 213B; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Failed 06/04/2009
Correction
Corrective Action Required
06/04/2009
PROTECTION OF COPPER PIPING FROM PENETRATION IPC 305.8: INSTALL SHIELD PLATES AT STUDS @ 213A SOUTH WALL WHERE < 1-1/2" FROM FACE OF FRAMING TO RECEIVE GWB
Correction
Corrective Action Required
06/04/2009
CONNECTIONS OF LIGHT GUAGE FRAMING WITHIN WIDTH OF WALL OPENINGS EXCEPT @ TOP SLIP TRACKS SCREW ALL CONNECTIONS INCLUDING CRIPPLE STUDS
All Rough Inspection - Commercial Partial 06/05/2009
Correction
Partial Correction
06/05/2009
WALL FRAMING + IN-WALL SYSTEMS 200; 200A; 213; 213A; 214B; 215; 215A&B STEEL STUD WALL; 216; 216B; 217; 218; 221; 213B; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Resolved
06/05/2009
PROTECTION OF COPPER PIPING FROM PENETRATION
Correction
Resolved
06/05/2009
CONNECTIONS OF LIGHT GUAGE FRAMING WITHIN WIDTH OF WALL OPENINGS
All Rough Inspection - Commercial Partial 06/10/2009
Correction
Partial Correction
06/10/2009
WALL FRAMING + IN-WALL SYSTEMS 200; 200A; 213; 213A; 213B; 214B; 215; 215A&B STEEL STUD WALL; 216; 216A; 216B; 217; 218; 219; 221; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 06/15/2009
Correction
Partial Correction
06/15/2009
WALL FRAMING + IN-WALL SYSTEMS 200; 200A; 213; 213A; 213B; 214B; 215; 215A&B STEEL STUD WALL; 215B WOOD FRAME WALL; 216; 216A; 216B; 217; 218; 219; 221; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 06/16/2009
Correction
Partial Correction
06/16/2009
WALL FRAMING + IN-WALL SYSTEMS 200; 200A; 213; 213A; 213B; 214B; 215; 215A&B STEEL STUD WALL; 215B WOOD FRAME WALLS; 215A WOOD FRAME E, N, W WALLS; 216; 216A; 216B; 217; 218; 219; 221 OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Electrical Inspection - Commercial Partial 06/26/2009
Correction
Partial Correction
06/26/2009
SEPARATELY-DERIVED SYSTEM GROUNDING ELECTRODE CONDUCTOR CONNECTION TO WATER ENTRY NOT YET COMPLETED.
All Rough Inspection - Commercial Passed 06/26/2009
Correction
Resolved
06/26/2009
WALL FRAMING + IN-WALL SYSTEMS 200; 200A; 213; 213A; 213B; 214B; 215; 215A&B STEEL STUD WALL; 215B WOOD FRAME WALLS; 215A WOOD FRAME E, N, W WALLS; 216; 216A; 216B; 217; 218; 219; 221 OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Electrical Inspection - Commercial Passed 06/29/2009
Correction
Resolved
06/29/2009
SEPARATELY-DERIVED SYSTEM 45KVA TRANSFORMER OK FOR ACTIVATION
Above Ceiling Inspection Partial 07/06/2009
Correction
Resolved
07/06/2009
None Aurora Scan Room
Correction
Partial Correction
07/06/2009
None SOFFIT AT ENTRY TO ROOM 1C213 ONLY Rm 1C213
Above Ceiling Inspection Partial 07/10/2009
Correction
Partial Correction
07/10/2009
None SOFFIT AT ENTRY TO ROOM 1C213, IC213, IC213A
Above Ceiling Inspection Passed 07/20/2009
Correction
Resolved
07/20/2009
None Aurora Scan Room
Correction
Resolved
07/20/2009
None ALL REMAINING ACT TILE AREAS, AFTER FIRE SEALING IS COMPLETED AT RATED WALL AT CORRIDOR EAST END SOFFIT AT ENTRY TO RMS 213, 213, 213A +
Occupancy Inspection - Codes Commercial Failed 07/31/2009
Correction
Partial Correction
07/31/2009
USE / OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FOR BUSINESS NO PUBLIC ENTRY
Correction
Partial Correction
07/31/2009
Receive Fire Department approval PER CPT DIR 7/31/09 OK FOR EQUIPMENT INSTALL
All Rough Inspection - Commercial Passed 08/19/2009
Correction
Resolved
08/19/2009
RE-CONSTRUCTION OF WALL AFTER INSTALLATION OF MAGNET IN-PROGRESS PHOTOS VIEWED @ JED FIELD OFFICE
Occupancy Inspection - Codes Commercial Partial 08/27/2009
Correction
Partial Correction
08/27/2009
USE / OCCUPANCY APPROVAL STATUS CONTROL, MAGNET, & SCAN ROOMS NOT TO BE USED UNTIL APPROVED BY LSFD. OK FOR USE & OCCUPANCY EXCEPT FOR SPACES BELOW:
Correction
Partial Correction
08/27/2009
Receive Fire Department approval OK EXCEPT CONTROL, MAGNET, & SCAN ROOMS PER CPT DIR 7/31/09
Occupancy Inspection - Codes Commercial Passed 09/15/2009
Correction
Resolved
09/15/2009
USE / OCCUPANCY APPROVAL STATUS BREAST MRI DEPARTMENT
Correction
Resolved
09/15/2009
Receive Fire Department approval PER CPT DIR 9/15/09
Documents & Images
Date Uploaded File Type Document Name
09/19/2017 Letter B0900193breastmricomments1
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home