Review Type |
Outcome |
Est. Completion Date |
Completed |
Building Plan Review
|
Approved
|
03/02/2011
|
03/02/2011
|
|
Tracy Deister
|
|
Misc
Corrective Action Required
Comments provide on this document are in addition to the comments provided at the time of permit issuance.
Action required - This comment is for information purposes.
|
|
Screening - Rooftop equipment
Corrective Action Required
Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped.
Action required - This will be verified on inspection.
|
|
Misc
Corrective Action Required
Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits.
Action required - This comment is for information purposes.
|
|
Misc
Corrective Action Required
The possible tenant address for this structure are 691, 695 and 699 NW Blue Pkwy going from south to north. The house panel can be addressed 691H NW Blue Pkwy.
Action required - This comment is for information purposes.
|
|
PLANS WERE REVEIWED AND APPROVED BY TRACY. I CALLED JERAMY W/ BLOCK AND TOLD HIM THE DRAWING WERE APPORVED AND THAT I GAVE THEM TO JOHN TO TAKE TO THE JOBSITE. RTD
|
Sprinkler Plan Review
|
Released for Construction
|
|
02/28/2011
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Comment: Plans received for the shell building system only.
|
|
Alarms connected to automatic sprinkler system
Corrective Action Required
2006 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
Comment: The alarm system shall be connected to the system at time of acceptance testing.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: Call (816) 969-1300 to schedule hydrostatic and flow testing.
|
|
Misc
Corrective Action Required
The FDC shall be provided with the appropriate drain piped to the exterior of the building.
Comment: Verified at inspection.
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
02/17/2011
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Information received 2/16/2011.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: Call (816) 969-1300 to schedule a test.
|
|
Misc
Corrective Action Required
A horn/strobe shall be located over the fire department connection and activate for water flow only.
Action required: Coordinate with the sprinkler contarctor to provide the appliance. Verified at inspection.
|
|
Misc
Corrective Action Required
2006 IFC 907.4.1 Location.
Manual fire alarm boxes shall be located not more than 5 feet (1524 mm) from the entrance to each exit. Additional manual fire alarm boxes shall be located so that travel distance to the nearest box does not exceed 200 feet (60 960 mm).
Action required: Place in accordance with above. Per 907.2.7 manual pull stations are not required in fully sprinklered building with alarm activation. Verified at inspection.
|
|
|
Internal Plan Review (Res)
|
Rejected
|
02/04/2011
|
02/10/2011
|
|
Mike Weisenborn
|
|
Corrective Action Required
|
|
|
Fire Plan Review
|
Approved
|
02/04/2011
|
02/10/2011
|
|
Jim Eden
|
|
Misc
Corrective Action Required
No change from original comments.
|
|
|
|
Misc
Corrective Action Required
Submit tenant finish plans for review.
|
|
|
Building Plan Review
|
Rejected
|
02/04/2011
|
02/04/2011
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
Comments provide on this document are in addition to the comments provided at the time of permit issuance.
Action required - This comment is for information purposes.
|
|
Misc
I am unable to locate a revised door schedule.
Action required - Provide a revised door and hardware schedule.
|
|
Misc
I am unable to locate a revised finish schedule.
Action required - Provide a revised finish schedule.
|
|
Mech - Outdoor air required
2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Action required - Show how the outside air was calculated for the units.
|
|
Screening - Rooftop equipment
Corrective Action Required
Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped.
Action required - This will be verified on inspection.
|
|
Misc
Corrective Action Required
Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits.
Action required - This comment is for information purposes.
|
|
Screening - Ground mounted equipment
Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened.
Action required - Obtain approval from Planning and Development for new ground mounted equipement. (816) 969-1600.
Transformer is located inside a screened area.
|
|
Misc
Corrective Action Required
The possible tenant address for this structure are 691, 695 and 699 NW Blue Pkwy going from south to north. The house panel can be addressed 691H NW Blue Pkwy.
Action required - This comment is for information purposes.
|
|
|
Building Plan Review
|
Rejected
|
02/04/2011
|
02/04/2011
|
|
Mike Weisenborn
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
Corrective Action Required
Comments provided on this document are in addition to the comments provided at the time of permit issuance
|
|
|
Internal Plan Review (Res)
|
Approved
|
06/17/2009
|
11/04/2010
|
|
Mike Weisenborn
|
|
Correction
Fire Department- 2006 IFC 505.1- Address numbers.
New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
|
|
Correction
Fire Department- 2006 IFC 506.1- Where required.
Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
|
|
Correction
Fire Department- 2006 IFC 510.1- Identification.
Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
|
|
Correction
Fire Department- 2006 IFC 901.2- Construction documents.
The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
|
|
Correction
Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
|
|
Correction
Fire Department- 2006 IFC 907.1.1- Construction documents.
Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following:
1. A floor plan which indicates the use of all rooms.
2. Locations of alarm-initiating and notification appliances.
3. Alarm control and trouble signaling equipment.
4. Annunciation.
5. Power connection.
6. Battery calculations.
7. Conductor type and sizes.
8. Voltage drop calculations.
9. Manufacturers, model numbers and listing information for equipment, devices and materials.
10. Details of ceiling height and construction.
11. The interface of fire safety control functions.
|
|
Correction
Codes Administration - This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start wth a number representing the floor on which the unit is located.
|
|
Correction
Codes Administration - 2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances' level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal.
Permanent ladders installed to provide the required access shall comply with the following minimum design criteria:
1. The side railing shall extend above the parapet or roof edge not less than 30 inches.
2. Ladders shall have rung spacing not to exceed 14 inches on center.
3. Ladders shall have a toe spacing not less than 6 inches deep.
4. There shall be a minimum of 18 inches between rails.
5. Rungs shall have a minumum 0.75-inch diameter and be capable of withstanding a 300-pound load.
6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot.
7. Ladders shall be protected against corrosion by approved means.
Catwalks instlled to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms.
|
|
Correction
Fire Department- 2006 IFC 907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
|
|
Correction
Fire Department- The location of the FDC is shown in several locations on the drawings. The approved location is on the southwest corner of the building.
|
|
Correction
Fire Department- Interior alarm notification appliances are required, and with monitoring of fire suppression systems as part of the shell building and systems installed as part of the tenant finish.
|
|
Correction
Fire Department- Restaurants are classified as an A2 occupancy.
|
|
Correction
Codes Administration - The site lighting plans were not included in the building permit package.
|
|
Correction
Codes Administration - I am unable to determine if the architectural element over the north restaurant space is inclosed. If it is inclosed it will need to meet the requirements in Chapter 12 of the 2006 IBC for access and ventilation for attic spaces.
|
|
Correction
CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
|
|
Correction
CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
|
|
Correction
CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
|
|
Correction
CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
|
|
Correction
CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
|
|
Correction
CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
|
|
Correction
CA - The Final Development Plan must be approved prior to issuing full building permits.
|
|
Correction
CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
|
|
Correction
CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
|
|
Correction
CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
|
|
Correction
CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
|
|
Correction
P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
|
|
Correction
Lee's Summit Code of Ordinance - Sec.17-309 - Smoking.
A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place.
B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
|
|
Correction
All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
|
|
|
Fire Plan Review
|
Approved
|
12/10/2008
|
11/04/2010
|
|
Mike Weisenborn
|
|
Portable fire extinguishers - general
Corrective Action Required
Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
|
|
Construction documents for fire alarm systems
Corrective Action Required
Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required - Provide alarm plans for review and approval.
|
|
Construction documents - Fire protection systems
Corrective Action Required
Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required - Provide sprinkler plans for review and approval.
|
|
Fire protection equipment identification
Corrective Action Required
Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Action required - The Sprinkler Room shall be marked. Verified at inspection.
|
|
Misc
Corrective Action Required
Fire Department- 2006 IFC 907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required - Duct detectors shall be connected to the building alarm system as supervisory only.
|
|
|
Building Plan Review
|
Approved
|
12/10/2008
|
11/04/2010
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits. Action required - This comment is for information purposes.
|
|
Suite address
Corrective Action Required
Codes Administration - This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required - This comment is for information purposes.
|
|
Mech - Access to elevated appliances
Corrective Action Required
Codes Administration - 2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minimum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms. Action required - To be verified on inspection.
|
|
WU - Backflow testing
Corrective Action Required
Water Utilities - All backflow prevention assemblies must be tested and reports filed with the Lees Summit Water Utilities Backflow Division (816-969-1900) within 30 days from the date installed. Action required - This comment is for information purposes.
|
|
|