Permit Application Status

B0801656


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0801656
Building Permit - Commercial
Final Completion
SUMMIT NORTHRIDGE LLC
NEW SHELL BUILDING
SHELL BUILDING FOR RETAIL USE
11/26/2008
12/08/2010
08/09/2011
06/07/2011
Locations
Contacts
HOEFER WYSOCKI ARCHITECTS, Address:612 W 47TH ST SUITE 300  
ARC GENERAL CONTRACTING, Address:7833 BARTON ST, Phone:(913) 492-8008  
ACCURATE MECHANICAL LLC, Address:205 E 13TH AVE, Phone:(816) 471-2272  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
WESTERN LAFOLLETTE MECHANICAL, Address:956 OSAGE, Phone:(913) 342-0505  
SUMMIT NORTHRIDGE LLC, Address:605 W 47TH ST STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 03/02/2011 03/02/2011
Tracy Deister
Misc
Corrective Action Required
03/02/2011

Comments provide on this document are in addition to the comments provided at the time of permit issuance. Action required - This comment is for information purposes.
Screening - Rooftop equipment
Corrective Action Required
03/02/2011

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - This will be verified on inspection.
Misc
Corrective Action Required
03/02/2011

Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits. Action required - This comment is for information purposes.
Misc
Corrective Action Required
03/02/2011

The possible tenant address for this structure are 691, 695 and 699 NW Blue Pkwy going from south to north. The house panel can be addressed 691H NW Blue Pkwy. Action required - This comment is for information purposes.
PLANS WERE REVEIWED AND APPROVED BY TRACY. I CALLED JERAMY W/ BLOCK AND TOLD HIM THE DRAWING WERE APPORVED AND THAT I GAVE THEM TO JOHN TO TAKE TO THE JOBSITE. RTD
Sprinkler Plan Review Released for Construction 02/28/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
02/28/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Comment: Plans received for the shell building system only.
Alarms connected to automatic sprinkler system
Corrective Action Required
02/28/2011

2006 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Comment: The alarm system shall be connected to the system at time of acceptance testing.
Installation acceptance testing
Corrective Action Required
02/28/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule hydrostatic and flow testing.
Misc
Corrective Action Required
02/28/2011

The FDC shall be provided with the appropriate drain piped to the exterior of the building. Comment: Verified at inspection.
Alarm Plan Review Released for Construction 02/17/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
02/17/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Information received 2/16/2011.
Installation acceptance testing
Corrective Action Required
02/17/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test.
Misc
Corrective Action Required
02/17/2011

A horn/strobe shall be located over the fire department connection and activate for water flow only. Action required: Coordinate with the sprinkler contarctor to provide the appliance. Verified at inspection.
Misc
Corrective Action Required
02/17/2011

2006 IFC 907.4.1 Location. Manual fire alarm boxes shall be located not more than 5 feet (1524 mm) from the entrance to each exit. Additional manual fire alarm boxes shall be located so that travel distance to the nearest box does not exceed 200 feet (60 960 mm). Action required: Place in accordance with above. Per 907.2.7 manual pull stations are not required in fully sprinklered building with alarm activation. Verified at inspection.
Internal Plan Review (Res) Rejected 02/04/2011 02/10/2011
Mike Weisenborn
Corrective Action Required
02/10/2011

Fire Plan Review Approved 02/04/2011 02/10/2011
Jim Eden
Misc
Corrective Action Required
02/10/2011

No change from original comments.
Resolved
02/10/2011

Misc
Corrective Action Required
02/10/2011

Submit tenant finish plans for review.
Building Plan Review Rejected 02/04/2011 02/04/2011
Mike Weisenborn
Misc
Corrective Action Required
02/04/2011

Comments provide on this document are in addition to the comments provided at the time of permit issuance. Action required - This comment is for information purposes.
Misc
Resolved
03/02/2011

I am unable to locate a revised door schedule. Action required - Provide a revised door and hardware schedule.
Misc
Resolved
03/02/2011

I am unable to locate a revised finish schedule. Action required - Provide a revised finish schedule.
Mech - Outdoor air required
Resolved
03/02/2011

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - Show how the outside air was calculated for the units.
Screening - Rooftop equipment
Corrective Action Required
02/04/2011

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - This will be verified on inspection.
Misc
Corrective Action Required
02/04/2011

Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits. Action required - This comment is for information purposes.
Screening - Ground mounted equipment
Resolved
02/04/2011

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required - Obtain approval from Planning and Development for new ground mounted equipement. (816) 969-1600. Transformer is located inside a screened area.
Misc
Corrective Action Required
02/04/2011

The possible tenant address for this structure are 691, 695 and 699 NW Blue Pkwy going from south to north. The house panel can be addressed 691H NW Blue Pkwy. Action required - This comment is for information purposes.
Building Plan Review Rejected 02/04/2011 02/04/2011
Mike Weisenborn
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Corrective Action Required
02/04/2011

Comments provided on this document are in addition to the comments provided at the time of permit issuance
Internal Plan Review (Res) Approved 06/17/2009 11/04/2010
Mike Weisenborn
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start wth a number representing the floor on which the unit is located.
Correction

Codes Administration - 2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances' level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minumum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks instlled to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Correction

Fire Department- The location of the FDC is shown in several locations on the drawings. The approved location is on the southwest corner of the building.
Correction

Fire Department- Interior alarm notification appliances are required, and with monitoring of fire suppression systems as part of the shell building and systems installed as part of the tenant finish.
Correction

Fire Department- Restaurants are classified as an A2 occupancy.
Correction

Codes Administration - The site lighting plans were not included in the building permit package.
Correction

Codes Administration - I am unable to determine if the architectural element over the north restaurant space is inclosed. If it is inclosed it will need to meet the requirements in Chapter 12 of the 2006 IBC for access and ventilation for attic spaces.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Fire Plan Review Approved 12/10/2008 11/04/2010
Mike Weisenborn
Portable fire extinguishers - general
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Construction documents for fire alarm systems
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required - Provide alarm plans for review and approval.
Construction documents - Fire protection systems
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required - Provide sprinkler plans for review and approval.
Fire protection equipment identification
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Action required - The Sprinkler Room shall be marked. Verified at inspection.
Misc
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required - Duct detectors shall be connected to the building alarm system as supervisory only.
Building Plan Review Approved 12/10/2008 11/04/2010
Mike Weisenborn
Misc
Corrective Action Required
11/04/2010

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits. Action required - This comment is for information purposes.
Suite address
Corrective Action Required
11/04/2010

Codes Administration - This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required - This comment is for information purposes.
Mech - Access to elevated appliances
Corrective Action Required
11/04/2010

Codes Administration - 2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minimum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms. Action required - To be verified on inspection.
WU - Backflow testing
Corrective Action Required
11/04/2010

Water Utilities - All backflow prevention assemblies must be tested and reports filed with the Lees Summit Water Utilities Backflow Division (816-969-1900) within 30 days from the date installed. Action required - This comment is for information purposes.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Shell Building $3,334.92 $3,334.92 Paid 12/08/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 12/14/2010 at 12:00 AM 12/14/2010
Misc
Partial Correction
12/14/2010
OK TO POUR WHEN READY EXTERIOR GRADE BEAM AND INTEGRAL COLUMN FOOTINGS AT FOLLOWING SEGMENTS: A/4.8 TO A/1 TO 1/B.3;
Electrical Service Inspection Partial 12/15/2010 at 12:00 AM 12/15/2010
Misc
Partial Correction
12/15/2010
FOOTING GROUND G.E.C. CLAMPED TO RE-BAR IN PLACE FOR GRADE BEAM POUR AT SOUTH WALL LINE
Footing Inspection - Commercial Partial 12/15/2010 at 12:00 AM 12/15/2010
Misc
Partial Correction
12/15/2010
OK TO POUR WHEN READY EXTERIOR GRADE BEAM AND INTEGRAL COLUMN FOOTINGS AT FOLLOWING SEGMENTS: A/4.8 TO A/1 TO 1/B.3; A/4.8 TO A/5 TO C/5 TO C/1.2;
Misc
Partial Correction
12/15/2010
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/4;
Footing Inspection - Commercial Partial 12/16/2010 at 12:00 AM 12/16/2010
Misc
Partial Correction
12/15/2010
OK TO POUR WHEN READY EXTERIOR GRADE BEAM AND INTEGRAL COLUMN FOOTINGS AT FOLLOWING SEGMENTS: A/4.8 TO A/1 TO 1/B.3; A/4.8 TO A/5 TO C/5 TO C/1.2; C/1.3 TO AROUND PERIMETER OF NW ENTRANCE TO 1/B.2; TRANSFORMER ENCLOSURE
Misc
Partial Correction
12/15/2010
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/4
Underslab Plumbing Inspection - Commercial Partial 12/17/2010 at 12:00 AM 12/17/2010
Misc
Partial Correction
12/17/2010
UNDER-SLAB SANITARY PIPING FROM NORTH BUILDING LINE SOUTH TO (4) APPROVED EXCEPT NO BEDDING ROCK IN PLACE -- DO NOT COVER
Underslab Plumbing Inspection - Commercial Passed 12/17/2010 at 12:00 AM 12/17/2010
Misc
Resolved
12/17/2010
UNDER-SLAB SANITARY PIPING FROM NORTH BUILDING LINE SOUTH TO (4) APPROVED EXCEPT NO BEDDING ROCK IN PLACE -- DO NOT COVER
Underslab Electrical Inspection - Commercial Passed 12/21/2010 at 12:00 AM 12/21/2010
Water Service Inspection Passed 12/29/2010 at 12:00 AM 12/29/2010
Sewer Service Inspection Passed 12/30/2010 at 12:00 AM 12/30/2010
Rough Framing Inspection - Commercial Partial 1/27/2011 at 12:00 AM 01/27/2011
Misc
Partial Correction
01/27/2011
LIGHT-GUAGE STEEL FRAMING OK TO COVER WITH SHEATHING WHEN READY AT EXTERIOR WALLS: SOUTH;
Rough Framing Inspection - Commercial Partial 1/28/2011 at 12:00 AM 01/28/2011
Misc
Partial Correction
01/27/2011
LIGHT-GUAGE STEEL FRAMING OK TO COVER WITH SHEATHING WHEN READY AT EXTERIOR WALLS EXCEPT AT NW CORNER WHERE SCREWS ARE MISSING AT BOTTOM TRACK
Rough Electrical Inspection - Commercial Partial 2/8/2011 at 12:00 AM 02/08/2011
Misc
Partial Correction
02/08/2011
OK TO COVER WHEN READY: MC CABLE AND BOXES AT ROOFTOP;
Rough Electrical Inspection - Commercial Failed 02/14/2011
Misc
Partial Correction
02/08/2011
OK TO COVER WHEN READY: MC CABLE AND BOXES AT ROOFTOP;
Misc
Corrective Action Required
02/14/2011
- IN WALL ELECTRICAL - PLANS DO NOT SHOW ANY OUTLETS - OUTLETS HAVE BEEN INSTALLED - SUBMIT PLANS SHOWING OUTLETS INSTALLED FOR REVIEW
Rough Framing Inspection - Commercial Passed 2/18/2011 at 12:00 AM 02/18/2011
Misc
Resolved
02/18/2011
LIGHT-GUAGE STEEL FRAMING OK TO COVER WITH SHEATHING WHEN READY AT EXTERIOR WALLS EXCEPT AT NW CORNER WHERE SCREWS ARE MISSING AT BOTTOM TRACK
In-wall Inspection Not Ready 3/4/2011 at 12:00 AM 03/04/2011
Misc
Partial Correction
03/04/2011
ELECTRICAL WIRING AND BOXES AT EXTERIOR WALLS APPROVED -- WALLS NOT APPROVED TO COVER; CALL FOR INSPECTION WHEN REVISED DRAWINGS ARE FULLY SUBMITTED AND APPROVED FOR CONSTRUCTION
In-wall Inspection Partial 03/07/2011
Misc
Resolved
04/11/2011
In-wall Inspection Partial 3/7/2011 at 12:00 AM 03/07/2011
Misc
Partial Correction
03/04/2011
EXTERIOR WALLS INTERIOR FACE OK TO COVER WHEN READY
Rough Plumbing Inspection - Commercial Partial 3/9/2011 3/9/2011 at 12:00 AM 03/09/2011
Misc
Partial Correction
03/09/2011
- ROOF DRAINS - APPROVED. - SANITARY WATER DISTRUBTION LINES INSTALLED BELOW ROOF - PLANS CALL FOR 3" COPPER LINE - 2" COPPER LINE INSTALLED. - PROVIDE ENGINEER'S APPROVAL FOR CHANGE
Rough Framing Inspection - Commercial Failed 3/9/2011 at 12:00 AM 03/09/2011
Misc
Corrective Action Required
03/09/2011
- UNABLE TO PERFORM UNTIL 10 MAR 11
Rough Framing Inspection - Commercial Passed 3/10/2011 3/10/2011 at 12:00 AM 03/10/2011
Misc
Resolved
03/10/2011
- UNABLE TO PERFORM UNTIL 10 MAR 11
Underslab Plumbing Inspection - Commercial Passed 3/24/2011 3/24/2011 at 12:00 AM 03/24/2011
Rough Framing Inspection - Commercial Passed 3/24/2011 at 12:00 AM 03/24/2011
Gas Piping Inspection - Commercial Partial 4/1/2011 at 12:00 AM 04/01/2011
Misc
Partial Correction
04/01/2011
ROOFTOP GAS PIPING SUPPORT IN PROGRESS; SUBJECT TO APPROVAL WHEN COMPLETED. PIPE TO BE PAINTED BEFORE FINAL INSPECTION.
Gas Service Inspection - Commercial Passed 4/1/2011 at 12:00 AM 04/01/2011
Rough Framing Inspection - Commercial Partial 4/7/2011 4/7/2011 at 12:00 AM 04/07/2011
Misc
Partial Correction
04/07/2011
- DEMISING WALLS - OKAY TO SHEETROCK ONE (1) OF INTERIOR WALLS
Sprinkler - Hydrostatic Test Passed 4/7/2011 at 10:00 AM 04/07/2011
Rough Electrical Inspection - Commercial Not Ready 4/8/2011 4/8/2011 at 12:00 AM 04/08/2011
In-wall Inspection Passed 04/11/2011
Misc
Partial Correction
03/07/2011
Underslab Electrical Inspection - Commercial Passed 4/14/2011 4/14/2011 at 12:00 AM 04/14/2011
Electrical Service Inspection Failed 4/19/2011 4/19/2011 at 12:00 AM 04/19/2011
Misc
Partial Correction
12/15/2010
FOOTING GROUND G.E.C. CLAMPED TO RE-BAR IN PLACE FOR GRADE BEAM POUR AT SOUTH WALL LINE
Misc
Corrective Action Required
04/19/2011
REIVSE PLANS TO SHOW CHANGES MADE ON SERVICE-500 CHANGED TO 250, ALUMINUM USED NOT COPPER NOTE-IN METER CANS- SOLID #4 GROUND UNDER SAME LUG AS STRANDED COPPER GROUND.
Above Ceiling Inspection Partial 4/25/2011 12/16/2010 at 12:00 AM 04/25/2011
Misc
Partial Correction
04/25/2011
OK TO COVER WHEN READY ACT CEILING SYSTEM AND ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 101 ONLY;
Electrical Service Inspection Passed 4/28/2011 (8:00 to 5:00) 4/28/2011 at 12:00 AM 04/28/2011
Misc
Resolved
04/28/2011
FOOTING GROUND G.E.C. CLAMPED TO RE-BAR IN PLACE FOR GRADE BEAM POUR AT SOUTH WALL LINE
Misc
Resolved
04/28/2011
REIVSE PLANS TO SHOW CHANGES MADE ON SERVICE-500 CHANGED TO 250, ALUMINUM USED NOT COPPER NOTE-IN METER CANS- SOLID #4 GROUND UNDER SAME LUG AS STRANDED COPPER GROUND.
Above Ceiling Inspection Partial 4/29/2011 at 12:00 AM 04/29/2011
Misc
Partial Correction
04/25/2011
OK TO COVER WHEN READY ACT CEILING SYSTEM AND ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 101; 101C; 101D; 101E
Alarm Test Passed 5/5/2011 at 12:00 AM 05/05/2011
Sprinkler - Flow Test Passed 5/5/2011 at 12:00 AM 05/05/2011
Occupancy Inspection - Fire Passed 05/06/2011
Final Inspection - Commercial Failed 5/6/2011 at 12:00 AM 05/06/2011
Misc
Corrective Action Required
05/06/2011
ROOFTOP INSPECTION: 1) GAS PIPING TO BE PAINTED; 2) RTU'S TO BE DESIGNATED BY ADDRESS #; 3) ROOFTOP TO BE LEFT CLEAR/CLEAN OF ALL DEBRIS AND UNSUSED MATERIALS
Misc
Corrective Action Required
05/06/2011
SEALING OF PENETRATIONS OF EIFS WALL SURFACE: CHECK TO ENSURE PROPERLY SEALED -- EXAMPLE: GAS PIPE ENTRY AT SOUTH WALL
Misc
Corrective Action Required
05/06/2011
FLOOR DRAIN BELOW WATER SERVICE BACKFLOW PREVENTION DEVICE: STRAINER INCOMPLETE
Misc
Corrective Action Required
05/06/2011
ADDRESS LABELING OF GAS SERVICE ENTRIES: HANG ADDRESS-STAMPED MEDALLIONS ON LOAD SIDE PIPES
Misc
Corrective Action Required
05/06/2011
EGRESS LIGHT @ 691 NOT INSTALLED
Misc
Corrective Action Required
05/06/2011
REQUIRED 18" VERTICAL GRAB BAR AT 699 RESTROOMS NOT INSTALLED.
Occupancy Inspection - Planning Temporary C of O 05/06/2011
Corrective Action Required
05/06/2011
LANDSCAPING. Complete landscaping around building per the approved plan. Also, replace the damaged tree planted in the parking lot landscape island north of the building.
Corrective Action Required
05/06/2011
ACCESSIBLE PARKING SPACE SIGN. Replace the signs at the head of the accessible parking spaces with sign R7-8 as identified in the MUTCD. The correct sign has a white background, green text, green border and blue wheelchair symbol.
Above Ceiling Inspection Passed 05/06/2011
Misc
Resolved
05/06/2011
OK TO COVER WHEN READY ACT CEILING SYSTEM AND ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 101; 101C; 101D; 101E
Footing Inspection - Commercial Passed 05/06/2011
Misc
Resolved
05/06/2011
OK TO POUR WHEN READY EXTERIOR GRADE BEAM AND INTEGRAL COLUMN FOOTINGS AT FOLLOWING SEGMENTS: A/4.8 TO A/1 TO 1/B.3; A/4.8 TO A/5 TO C/5 TO C/1.2; C/1.3 TO AROUND PERIMETER OF NW ENTRANCE TO 1/B.2; TRANSFORMER ENCLOSURE
Misc
Resolved
05/06/2011
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT FOLLOWING LOCATIONS: B/2; B/3; B/4
Gas Piping Inspection - Commercial Passed 05/06/2011
Misc
Resolved
05/06/2011
ROOFTOP GAS PIPING SUPPORT IN PROGRESS; SUBJECT TO APPROVAL WHEN COMPLETED. PIPE TO BE PAINTED BEFORE FINAL INSPECTION.
Rough Electrical Inspection - Commercial Passed 05/06/2011
Rough Framing Inspection - Commercial Passed 05/06/2011
Misc
Resolved
05/06/2011
- DEMISING WALLS - OKAY TO SHEETROCK ONE (1) OF INTERIOR WALLS
Rough Plumbing Inspection - Commercial Passed 05/06/2011
Misc
Resolved
05/06/2011
- ROOF DRAINS - APPROVED. - SANITARY WATER DISTRUBTION LINES INSTALLED BELOW ROOF - PLANS CALL FOR 3" COPPER LINE - 2" COPPER LINE INSTALLED. - PROVIDE ENGINEER'S APPROVAL FOR CHANGE
Final Inspection - Commercial Failed 5/17/2011 at 12:00 AM 05/17/2011
Misc
Corrective Action Required
05/06/2011
ROOFTOP INSPECTION: 1) GAS PIPING TO BE PAINTED; 2) RTU'S TO BE DESIGNATED BY ADDRESS #; 3) ROOFTOP TO BE LEFT CLEAR/CLEAN OF ALL DEBRIS AND UNSUSED MATERIALS
Misc
Corrective Action Required
05/06/2011
SEALING OF PENETRATIONS OF EIFS WALL SURFACE: CHECK TO ENSURE PROPERLY SEALED -- EXAMPLE: GAS PIPE ENTRY AT SOUTH WALL
Misc
Corrective Action Required
05/06/2011
FLOOR DRAIN BELOW WATER SERVICE BACKFLOW PREVENTION DEVICE: STRAINER INCOMPLETE
Misc
Corrective Action Required
05/06/2011
ADDRESS LABELING OF GAS SERVICE ENTRIES: HANG ADDRESS-STAMPED MEDALLIONS ON LOAD SIDE PIPES
Misc
Corrective Action Required
05/06/2011
EGRESS LIGHT @ 691 NOT INSTALLED
Misc
Corrective Action Required
05/06/2011
REQUIRED 18" VERTICAL GRAB BAR AT 699 RESTROOMS NOT INSTALLED.
Misc
Corrective Action Required
05/17/2011
MONUMENT SIGN NOT UL-LABELED
Final Inspection - Commercial Failed 5/17/2011 at 12:00 AM 05/17/2011
Misc
Corrective Action Required
05/17/2011
ROOFTOP INSPECTION: 1) GAS PIPING TO BE PAINTED; 2) RTU'S TO BE DESIGNATED BY ADDRESS #; 3) ROOFTOP TO BE LEFT CLEAR/CLEAN OF ALL DEBRIS AND UNSUSED MATERIALS
Misc
Corrective Action Required
05/17/2011
SEALING OF PENETRATIONS OF EIFS WALL SURFACE: CHECK TO ENSURE PROPERLY SEALED -- EXAMPLE: GAS PIPE ENTRY AT SOUTH WALL
Misc
Corrective Action Required
05/17/2011
FLOOR DRAIN BELOW WATER SERVICE BACKFLOW PREVENTION DEVICE: STRAINER INCOMPLETE
Misc
Corrective Action Required
05/17/2011
ADDRESS LABELING OF GAS SERVICE ENTRIES: HANG ADDRESS-STAMPED MEDALLIONS ON LOAD SIDE PIPES
Misc
Corrective Action Required
05/17/2011
EGRESS LIGHT @ 691 NOT INSTALLED
Misc
Corrective Action Required
05/17/2011
REQUIRED 18" VERTICAL GRAB BAR AT 699 RESTROOMS NOT INSTALLED.
Misc
Corrective Action Required
05/17/2011
NEC 600.3: LIGHTED MONUMENT SIGN NOT UL-LABELED
Occupancy Inspection - Planning Temporary C of O 5/20/2011 at 12:00 AM 05/20/2011
Corrective Action Required
05/20/2011
LANDSCAPING. Replace the damaged tree in the parking lot landscape island north of the building.
Corrective Action Required
05/20/2011
ACCESSIBLE PARKING SIGN. The sign posted at the head of the handicap accessible parking spaces shall be replaced with the R7-8 signs (white background, blue wheelchair symbol and green text and border) as identified in the Manual on Uniform Traffic Control Devices (MUTCD).
Final Inspection - Commercial Failed 5/20/2011 at 12:00 AM 05/20/2011
Misc
Resolved
05/20/2011
ROOFTOP INSPECTION: 1) GAS PIPING TO BE PAINTED; 2) RTU'S TO BE DESIGNATED BY ADDRESS #; 3) ROOFTOP TO BE LEFT CLEAR/CLEAN OF ALL DEBRIS AND UNSUSED MATERIALS
Misc
Resolved
05/20/2011
SEALING OF PENETRATIONS OF EIFS WALL SURFACE: CHECK TO ENSURE PROPERLY SEALED -- EXAMPLE: GAS PIPE ENTRY AT SOUTH WALL
Misc
Resolved
05/20/2011
FLOOR DRAIN BELOW WATER SERVICE BACKFLOW PREVENTION DEVICE: STRAINER INCOMPLETE
Misc
Resolved
05/20/2011
ADDRESS LABELING OF GAS SERVICE ENTRIES: HANG ADDRESS-STAMPED MEDALLIONS ON LOAD SIDE PIPES
Misc
Resolved
05/20/2011
EGRESS LIGHT @ 691 NOT INSTALLED
Misc
Resolved
05/20/2011
REQUIRED 18" VERTICAL GRAB BAR AT 699 RESTROOMS NOT INSTALLED.
Misc
Resolved
05/20/2011
NEC 600.3: LIGHTED MONUMENT SIGN NOT UL-LABELED
Misc
Corrective Action Required
05/20/2011
RESOLVE PLANNING & DEVELOPMENT ISSUES. E.G., HANDICAPPED ACCESSIBLE SIGNS; DAMAGED TREE
Final Inspection - Commercial Partial 6/1/2011 at 12:00 AM 06/01/2011
Misc
Corrective Action Required
05/20/2011
RESOLVE PLANNING & DEVELOPMENT ISSUES. E.G., HANDICAPPED ACCESSIBLE SIGNS; DAMAGED TREE
Final Inspection - Commercial Passed 6/6/2011 at 12:00 AM 06/06/2011
Misc
Resolved
06/06/2011
RESOLVE PLANNING & DEVELOPMENT ISSUES. E.G., HANDICAPPED ACCESSIBLE SIGNS; DAMAGED TREE
Occupancy Inspection - Engineering Passed 04/12/2013
Documents & Images
Date Uploaded File Type Document Name
12/08/2010 Letter Building Permit
12/08/2010 Letter Plan Review Conditions
12/14/2010 Letter Inspection Summary
12/15/2010 Letter Inspection Summary
12/16/2010 Letter Inspection Summary
12/17/2010 Letter Inspection Summary
12/17/2010 Letter Inspection Summary
12/21/2010 Letter Inspection Summary
12/29/2010 Letter Inspection Summary
12/30/2010 Letter Inspection Summary
01/27/2011 Letter Inspection Summary
01/28/2011 Letter Inspection Summary
02/08/2011 Letter Inspection Summary
02/10/2011 Letter Plan Review Conditions
02/10/2011 Letter Plan Review Conditions
02/14/2011 Letter Inspection Summary
02/17/2011 Letter Fire (Alarm) Plan Review Notice
02/18/2011 Letter Inspection Summary
02/28/2011 Letter Fire (Sprinkler) Plan Review
03/04/2011 Letter Inspection Summary
03/07/2011 Letter Inspection Summary
03/09/2011 Letter Inspection Summary
03/10/2011 Letter Inspection Summary
03/24/2011 Letter Inspection Summary
03/24/2011 Letter Inspection Summary
04/01/2011 Letter Inspection Summary
04/07/2011 Letter Inspection Summary
04/11/2011 Letter Inspection Summary
04/14/2011 Letter Inspection Summary
04/19/2011 Letter Inspection Summary
04/25/2011 Letter Inspection Summary
04/28/2011 Letter Inspection Summary
04/29/2011 Letter Inspection Summary
05/06/2011 Letter Fire Loss Reduction Form
05/06/2011 Letter Inspection Summary
05/17/2011 Letter Inspection Summary
05/20/2011 Letter Inspection Summary
06/06/2011 Letter Inspection Summary
06/21/2013 Letter Fire (Sprinkler) Plan Review
06/21/2013 Letter Fire (Alarm) Plan Review Notice
09/19/2017 B0801656summitfairpad3comments1
09/19/2017 b0801656summitfairpad3invoice1
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home