Permit Application Status

B0801612


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0801612
Building Permit - Commercial
Final Completion
CP DEER BROOK PLAZA LLC
ALTERATION COMMERCIAL
INTERIOR ALTERATION OF EXISTING OFFICE SPACE. ENCLOSE 3 OFFICE AREAS, MOVE A COUPLE OF WALLS AND CREATE NEW ENTRANCE
11/14/2008
11/17/2008
07/15/2009
01/22/2009
Locations
Contacts
GWC CONTRACTING INC, Address:13115 4TH ST  
AFC HEATING & COOLING INC, Address:824 NW MAIN ST  
AGMP ARCHITECTS, Address:226 SE DOUGLAS  
KIRCO DEVELOPMENT LLC, Address:304 NW VICTORIA DR  
R & R PLUMBING, INC., Address:1600 W. WALL  
CP DEER BROOK PLAZA LLC, Address:3400 COLLEGE BLVD STE 195  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/16/2009 10/29/2010
Correction

Fire Department- 2006 IFC 408.11.2 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2006 IBC 1008.1.4 - Floor elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal (2-percent slope).
Correction

Fire Department- 2006 IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
Correction

Fire Department- 2006 IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Fire Department- 2006 IFC 1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $98.97 $98.97 Paid 11/17/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Not Ready 11/19/2008
Correction
Corrective Action Required
11/19/2008
Approved Plans PROVIDE A COMPLETE SET OF PLANS FOR INSPECTION
All Rough Inspection - Commercial Failed 11/20/2008
Correction
Corrective Action Required
11/20/2008
Approved Plans PROVIDE A COMPLETE SET OF PLANS FOR INSPECTION
Correction
Corrective Action Required
11/20/2008
See Comment - THERE ARE 24 NEW OUTLETS INSTALLED - NONE SHOWN ON APPROVED PLANS. - THERE ARE 6 NEW SWITCHES INSTALLED - NONE SHOWN ON PLANS. Electrical
Correction
Corrective Action Required
11/20/2008
See Comment - AT WEST SIDE - SOUTH END OF AREA OF ALTERATION - PLANS SHOWN 3 NEW OFFICE SPACES - ONLY 2 INSTALLED. Walls
Correction
Corrective Action Required
11/20/2008
See Comment - NEW EXTERIOR WALL AND EXIT DOOR - NOT STARTED. - EXISTING DOOR IN NEW OFFICE SPACE - NOT SHOWN ON PLANS - IS THIS TO BE REPLACED WITH SOLID WALL OR LEFT AS IS? Doors
Rough Framing Inspection - Commercial Request Complete 11/20/2008 11/20/2008 11/20/2008
Above Ceiling Inspection Failed 12/12/2008
Correction
Corrective Action Required
12/12/2008
Electrical Conduit - CONDUIT LAYING ON TOP OF LIGHT FIXTURE & CEILING PANELS. - SWITCH & J-BOX LAYING ON CEILING TILE. Throughout
Occupancy Inspection - Codes Commercial Failed 12/12/2008
Correction
Corrective Action Required
12/12/2008
Receive Fire Department approval RECEIVE UNDER SEPARATE COVER.
Correction
Corrective Action Required
12/12/2008
Above Ceiling
All Rough Inspection - Commercial Passed 12/12/2008
Correction
Resolved
12/12/2008
Approved Plans PROVIDE A COMPLETE SET OF PLANS FOR INSPECTION
Correction
Resolved
12/12/2008
See Comment - THERE ARE 24 NEW OUTLETS INSTALLED - NONE SHOWN ON APPROVED PLANS. - THERE ARE 6 NEW SWITCHES INSTALLED - NONE SHOWN ON PLANS. Electrical
Correction
Resolved
12/12/2008
See Comment - AT WEST SIDE - SOUTH END OF AREA OF ALTERATION - PLANS SHOWN 3 NEW OFFICE SPACES - ONLY 2 INSTALLED. Walls
Correction
Resolved
12/12/2008
See Comment - NEW EXTERIOR WALL AND EXIT DOOR - NOT STARTED. - EXISTING DOOR IN NEW OFFICE SPACE - NOT SHOWN ON PLANS - IS THIS TO BE REPLACED WITH SOLID WALL OR LEFT AS IS? Doors
Occupancy Inspection - Codes Commercial Passed 01/20/2009
Correction
Resolved
01/20/2009
Receive Fire Department approval
Correction
Resolved
01/20/2009
Above Ceiling
Correction
Resolved
01/20/2009
Receive Water Utilities Approval
Above Ceiling Inspection Passed 01/21/2009
Correction
Resolved
01/21/2009
Electrical Conduit
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home