Permit Application Status

B0801305


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0801305
Building Permit - Commercial
Certificate of Occupancy
LBP III LLC
NEW TENANT FINISH
ORIGINAL TENANT SPACE FOR OFFICE AND WAREHOUSE USE
09/08/2008
10/28/2008
11/25/2009
06/02/2009
Locations
Contacts
BLUE SPRINGS ELECTRICAL, Address:3402 LAKESHORE DR  
CAPITAL CONSTRUCTION SERVICES, Address:2642 NE HAGAN RD  
CLEARLINE PLUMBING, Address:14922 KNORPP RD  
DAVIDSON BROWN, Address:11301 STRANG LINE ROAD  
UNITED HEATING & COOLING, Address:301 DUCK RD  
LBP III LLC, Address:3215 NE CARNEGIE DR STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/13/2009 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Fire Department- 2006 IFC 011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Fire Department- Provide a storage plan for the warehouse.
Correction

Fire Department- The occupant load of the Training Room may exceed 49 depending on the use and type of furniture to be installed. Exit and emergency lighting shall be provided if the calculated occupant load exceeds 49.
Correction

Codes Administration - I am unable to find information regarding required safety glass in the doors or adjacent to doors on either the door schedule or the frame type details found on Sheet A1.4.
Correction

Codes Administration - Information on the ice maker to be installed has not been provided.
Correction

Codes Administration - The plumbing plans do not include information for the dishwasher and ice maker.
Correction

Codes Administration - The required clearances for the water closets and urinal are not indicated on the plans. The Codes Administration Department feels that this information is important to as it can be difficult and costly to move the fixtures and stalls if installed incorrectly.
Correction

Codes Administration - I am unable to locate any structural information pertaining to the installation of RTU's 16 and 17.
Correction

Codes Administration - The wall finishes are not included on the finish schedule.
Correction

Codes Administration - Details 11 and 12 on Sheet A1.3 are incorrectly labeled restroom elevations.
Correction

Codes Administration - The furniture layout of the training room has not been provided. This information is required to determine requirements such as exit signage, door hardware and door swing.
Correction

Planning and Development - Commercial buisnesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,618.61 $1,618.61 Paid 10/28/2008
89 Sewer Tap Fees $480.00 $480.00 Paid 10/28/2008
91 EFHB Maybrook Water Shed $681.76 $681.76 Paid 10/28/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 10/29/2008
Correction
Partial Correction
10/29/2008
None -BATHROOMS AND SINKS APPROVED BELOW
Underslab Electrical Inspection - Commercial Partial 10/29/2008
Correction
Partial Correction
10/29/2008
None -TRAINING RM AND CONFERENCE RM APPROVED BELOW
Electrical Service Inspection Passed 11/21/2008
Correction
Resolved
11/21/2008
None ELECTRICAL SERVICE METER (600 AMP) APPROVED FOR TOSHIBA TENANT
All Rough Inspection - Commercial Partial 11/26/2008
Correction
Partial Correction
11/26/2008
None OK TO ROCK RM 141,142,143 NOT READY APPROVED BELOW
All Rough Inspection - Commercial Partial 12/01/2008
Correction
Partial Correction
12/01/2008
None OK TO ROCK RM 141,142,143 NOT READY APPROVED BELOW
Gas Service Inspection - Commercial Passed 12/02/2008
Correction
Resolved
12/02/2008
None GAS SERVICE APPROVED FOR RELEASE-2 METERS
All Rough Inspection - Commercial Passed 12/03/2008
Correction
Resolved
12/03/2008
None IN-WALL ALLROUGH APPROVED
Above Ceiling Inspection Passed 12/16/2008
Correction
Resolved
12/16/2008
None ABOVE-CEILING APPROVED
Occupancy Inspection - Codes Commercial Failed 12/29/2008
Correction
Corrective Action Required
12/29/2008
Receive Fire Department approval
Correction
Corrective Action Required
12/29/2008
Receive Planning & Development Approval
Correction
Corrective Action Required
12/29/2008
Receive Public Works Approval
Correction
Corrective Action Required
12/29/2008
LICENSE TAX PAYMENT NO TYPE OF OCCUPANCY SHALL BE ISSUED UNTIL LICENSE TAX IS PAID
Correction
Corrective Action Required
12/29/2008
Handrails (IRC) HANDRAILS AT STAIRS& RAMPS ON EAST AND NORTH SIDES
Correction
Corrective Action Required
12/29/2008
LANDINGS & STAIRS AT EXTERIOR DOORS
Correction
Corrective Action Required
12/29/2008
PAINT WEATHER-EXPOSED GAS LINE
Correction
Corrective Action Required
12/29/2008
MISC ROOF FLASHING AND SEAL WALL PENETRATIONS
Correction
Corrective Action Required
12/29/2008
PROVIDE ACCESS TO RTUs PER IMC306.5
Correction
Corrective Action Required
12/29/2008
INSTALL WEATHER PROOF COVERS FOR ALL RTU GFCI RECEPTACLES ALSO LABEL RTUs
Underslab Plumbing Inspection - Commercial Passed 12/29/2008
Correction
Resolved
12/29/2008
None
Underslab Electrical Inspection - Commercial Passed 12/29/2008
Correction
Resolved
12/29/2008
None
Gas Piping Inspection - Commercial Passed 12/29/2008
Occupancy Inspection - Codes Commercial Failed 01/07/2009
Correction
Resolved
01/07/2009
Receive Fire Department approval
Correction
Resolved
01/07/2009
Receive Public Works Approval
Correction
Resolved
01/07/2009
LICENSE TAX PAYMENT TCO APPROVED FOR TENANT
Correction
Resolved
01/07/2009
Handrails (IRC)
Correction
Resolved
01/07/2009
LANDINGS & STAIRS AT EXTERIOR DOORS
Correction
Corrective Action Required
01/07/2009
PAINT WEATHER-EXPOSED GAS LINE
Correction
Corrective Action Required
01/07/2009
PROVIDE ACCESS TO RTUs PER IMC306.5
Correction
Corrective Action Required
01/07/2009
INSTALL WEATHER PROOF COVERS FOR ALL RTU GFCI RECEPTACLES ALSO LABEL RTUs
Occupancy Inspection - Codes Commercial Failed 03/09/2009
Correction
Resolved
03/09/2009
Receive Planning & Development Approval
Correction
Resolved
03/09/2009
PAINT WEATHER-EXPOSED GAS LINE
Correction
Resolved
03/09/2009
MISC
Correction
Resolved
03/09/2009
PROVIDE ACCESS TO RTUs PER IMC306.5
Correction
Corrective Action Required
03/09/2009
INSTALL WEATHER PROOF COVERS FOR ALL RTU GFCI RECEPTACLES
Occupancy Inspection - Codes Commercial Failed 05/14/2009
Occupancy Inspection - Codes Commercial Passed 06/01/2009
Correction
Resolved
06/01/2009
INSTALL WEATHER PROOF COVERS FOR ALL RTU GFCI RECEPTACLES
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home