Permit Application Status

B0801045


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0801045
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
REMODEL OF EXISTING TENANT SPACE.
07/15/2008
09/15/2008
03/14/2009
03/17/2009
Locations
Contacts
ACI BOLAND, Address:11229 NALL SUITE 140  
P1 GROUP INC, Address:16210 WEST 108TH ST  
SHAW ELECTRIC COMPANY, Address:3600 FULLER AVE  
P1 GROUP INC, Address:16210 WEST 108TH ST  
P1 GROUP INC, Address:16210 WEST 108TH ST  
P1 GROUP INC, Address:16210 WEST 108TH ST  
SAINT LUKES HEALTH SYSTEM, Address:4401 WORNALL RD  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/07/2009 10/29/2010
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Fire Department- 2006 IFC 3006.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter.
Correction

Codes Administration - The suite number for this space has not been provided.
Correction

Fire Department- 2006 IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
Correction

Fire Department- 2006 IFC 1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building. Exception: Approved temporary means of egress systems and facilities.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $494.85 $494.85 Paid 09/15/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 09/16/2008
Correction
Partial Correction
09/16/2008
None -ECHO ROOMS: 1D07 (MINUS W. WALL ), 1D21 (MINUS S. WALL) APPROVED TO COVER BELOW IN-WALL
Rated Assembly Inspection Partial 09/18/2008
Correction
Partial Correction
09/18/2008
None -ECHO RM 1D21 WEST 2HR SMOKE BARRIER WALL-1ST LAYER OK
Rated Assembly Inspection Partial 09/19/2008
Correction
Partial Correction
09/19/2008
None -ECHO RM 1D21 WEST 2HR SMOKE BARRIER WALL-2ND LAYER BOTH SIDES OK
Above Ceiling Inspection Partial 10/08/2008
Correction
Partial Correction
10/08/2008
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 07; 21; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
All Rough Inspection - Commercial Passed 10/08/2008
Correction
Resolved
10/08/2008
None
Rated Assembly Inspection Passed 10/08/2008
Correction
Resolved
10/08/2008
None
Occupancy Inspection - Codes Commercial Partial 10/15/2008
Correction
Partial Correction
10/15/2008
USE / OCCUPANCY APPROVAL STATUS 07; 21; OK FOR USE/OCCUPANCY FOLLOWING SPACES ONLY:
Correction
Partial Correction
10/15/2008
Receive Fire Department approval PER CPT JOE DIR SPACES 07; 21
All Rough Inspection - Commercial Partial 10/27/2008
Correction
Partial Correction
10/27/2008
WALL FRAMING + IN-WALL SYSTEMS 01; 01A; 04; 05; 06; 07; 10; 11; 21; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Above Ceiling Inspection Partial 11/12/2008
Correction
Partial Correction
11/12/2008
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS ALL EXCEPT 08 & 09 OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 11/17/2008
Correction
Partial Correction
11/17/2008
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS ALL EXCEPT 08 OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Occupancy Inspection - Codes Commercial Failed 11/26/2008
Correction
Partial Correction
11/26/2008
USE / OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Partial Correction
11/26/2008
Receive Fire Department approval PER CPT JOE DIR SPACES DOCUMENTED
All Rough Inspection - Commercial Partial 01/23/2009
Correction
Partial Correction
01/23/2009
WALL FRAMING + IN-WALL SYSTEMS 01; 01A; 04; 05; 06; 07; 10; 11; 21; NORTH-SOUTH LEG OF CORR 08 EAST WALL & SOUTH END WALL; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rated Assembly Inspection Partial 01/28/2009
Correction
Partial Correction
01/28/2009
CONSTRUCTION OF FIRE-RATED WALL NORTH-SOUTH LEG OF CORR 08 EAST WALL EXCEPT FOR 8'-9" ACCESS OPENING & SOUTH END WALL: 1ST LAYER OF 5/8" TYPE X GWB; OK TO COVER WHEN READY FOLLOWING COMPONENTS:
Rated Assembly Inspection Partial 01/30/2009
Correction
Partial Correction
01/30/2009
CONSTRUCTION OF FIRE-RATED WALL NORTH-SOUTH LEG OF CORR 08 EAST WALL EXCEPT FOR 8'-9" ACCESS OPENING & SOUTH END WALL: 1ST LAYER OF 5/8" TYPE X GWB; 1-30-09-2ND LAYER INSPECTED -APPROVED TO MUD TAPE/FIRE SEALANT. OK TO COVER WHEN READY FOLLOWING COMPONENTS:
Above Ceiling Inspection Passed 02/19/2009
Correction
Resolved
02/19/2009
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS ALL INCLUDING CORR 08 E-W & N-S LEGS + CORR 00 NORTH TO INTERFACE W/ EXISTING OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Rated Assembly Inspection Passed 02/19/2009
Correction
Resolved
02/19/2009
CONSTRUCTION OF FIRE-RATED WALL
All Rough Inspection - Commercial Passed 02/19/2009
Correction
Resolved
02/19/2009
WALL FRAMING + IN-WALL SYSTEMS
Occupancy Inspection - Codes Commercial Failed 03/04/2009
Correction
Partial Correction
03/04/2009
USE / OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Rated Assembly Inspection Passed 03/09/2009
Correction
Resolved
03/09/2009
CONSTRUCTION OF FIRE-RATED WALL INCLUDING TAPE/MUD/SEAL OF WALL @W END OF CORR 08
Occupancy Inspection - Codes Commercial Passed 03/16/2009
Correction
Resolved
03/16/2009
USE / OCCUPANCY APPROVAL STATUS
Correction
Resolved
03/16/2009
Receive Fire Department approval PER CPT JOE DIR
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home