Summary
B0800998
Building Permit - Commercial
Certificate of Occupancy
DOUGLAS STATION SHOPPING CENTER LLC
CHANGE OF TENANT
TENANT FINISH FOR CHIROPRACTOR OFFICE
07/07/2008
08/06/2008
03/03/2009
09/08/2008
Locations
Contacts
ADVANCE ELECTRIC CO, INC, Address:7212 MARION AVE  
STRINGER CONSTRUCTION CO INC, Address:11125 W 61ST STREET  
VIELHAUER PLUMBING INC., Address:12107 JOHNSON DR  
E & Q HEATING AND COOLING, Address:5 SW 4TH ST  
GOLDBLATT ARCHITECTURE, Address:4200 MERCIER ST  
DOUGLAS STATION SHOPPING CENTER LLC, Address:1725 NE RICE RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/25/2009 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B).
Correction

Codes Administration - 2006 IBC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Fire Department- 2006 IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
Correction

Fire Department- Provide a detail for the curtains to be used. They shall meet meet the requirements of NFPA 13 Section 8.6.5.2.2.1.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances.
Correction

Codes Administration - Per our previous phone conversation the 2-hour fire-resistive walls are not required and will not be installed.
Correction

Codes Administration - The mechanical and electrical plans have not been provided.
Correction

Codes Administration - I am unable to locate the details for the construction of the partitions.
Correction

Codes Administration - Note X1 address possible protection of the walls in the x-ray room but does not mention possible protection of the door.
Correction

Fire Deaprtment- The existing remote reset for the duct detector shall be located at an accessible location within the space.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $183.83 $183.83 Paid 08/06/2008
89 Sewer Tap Fees $30.00 $30.00 Paid 08/06/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 08/07/2008
Correction
Corrective Action Required
08/07/2008
GROUNDING OF RECEPTACLES & FIXED ELECTRICAL EQUIPMENT NEC 517.13 PATIENT CARE AREAS REDUNDANT GROUND REQUIRED
All Rough Inspection - Commercial Passed 08/12/2008
Correction
Resolved
08/12/2008
GROUNDING OF RECEPTACLES & FIXED ELECTRICAL EQUIPMENT PATIENT CARE AREAS
Correction
Resolved
08/12/2008
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY
Above Ceiling Inspection Failed 08/26/2008
Correction
Corrective Action Required
08/26/2008
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS SEE BELOW
Correction
Corrective Action Required
08/26/2008
LIGHTING IN INTERSTITIAL SPACE INCLUDING AT SERVICE PANEL INTENDED FOR REMOVAL REMOVE ENTIRELY
Correction
Corrective Action Required
08/26/2008
SUPPORT OF HVAC DUCT TO STRUCTURE SUPPORT @ 5' INTERVALS NOT OVER LIGHT FIXTURES
Correction
Corrective Action Required
08/26/2008
SECURING/SUPPORT OF MC ELECTRICAL CABLE DO NOT SUPPORT FROM CEILING HANGER WIRES SUPPORT FROM OWN WIRES TO STRUCTURE ABOVE
Correction
Corrective Action Required
08/26/2008
ELECTRICAL JUNCTION BOXES CLOSE ALL
Correction
Corrective Action Required
08/26/2008
EXIT SIGN AT FRONT ENTRANCE CURRENTLY ABOVE CEILING RELOCATE TO GRID
Above Ceiling Inspection Partial 08/28/2008
Correction
Partial Correction
08/28/2008
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS TO BE RE-INSPECTED FROM LADDER OK TO COVER WHEN READY EXCEPT AT THREE LOCATIONS
Correction
Partial Correction
08/28/2008
SUPPORT OF HVAC DUCT TO STRUCTURE NOT TO BE SUPPORTED BY LIGHT FIXTURES
Correction
Resolved
08/28/2008
SECURING/SUPPORT OF MC ELECTRICAL CABLE
Correction
Partial Correction
08/28/2008
ELECTRICAL JUNCTION BOXES CLOSE ALL
Correction
Resolved
08/28/2008
EXIT SIGN AT FRONT ENTRANCE
Occupancy Inspection - Codes Commercial Passed 09/05/2008
Correction
Resolved
09/05/2008
Receive Fire Department approval THEREUPON, APPROVED FOR OCCUPANCY PER JOE DIR 9/5/08 ADDITIONAL EMERGENCY LITE INSTALLED IN CORRIDOR
Correction
Resolved
09/05/2008
WALL BASE TRIM AT WOMEN'S RESTROOM 4" EXISTING REPLACED WITH 6" VINYL BASE
Above Ceiling Inspection Passed 09/05/2008
Correction
Resolved
09/05/2008
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS
Correction
Resolved
09/05/2008
LIGHTING IN INTERSTITIAL SPACE
Correction
Resolved
09/05/2008
SUPPORT OF HVAC DUCT TO STRUCTURE
Correction
Resolved
09/05/2008
ELECTRICAL JUNCTION BOXES
Documents & Images
Date Uploaded File Type Document Name
10/12/2015 Activity Document DOC101215-002
10/30/2015 Activity Document DOC103015
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents