Permit Application Status

B0800971


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0800971
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
NEW TENANT FINISH
LONGS SAWMILL RESTAURANT TENANT FINISH
07/02/2008
07/25/2008
01/21/2009
11/03/2008
Locations
Contacts
INTEGRITY PLUMBING SERVICES, LLC, Address:3801 SE VALLEY FORGE DR  
ROZIER ELECTRIC, INC., Address:1608 SW JEFFERSON  
DIMAGGIO MECHANICAL INC., Address:1 SE 4TH ST  
SULLIVAN PALMER, Address:8849 LONG  
ALLIED RETAIL CONCEPTS, Address:6200 MASTON  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 210, Phone:(816) 645-2336  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/21/2009 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2006 IBC 1012.5 - Handrail Extensions. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight or ramp run. At stairways where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser. At ramps where handrails are not continuous between runs, the handrail shall extend horizontally above the landing 12 inches minimum beyond the top and bottom ramps.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - I am unable to locate details of the construction of the column pads.
Correction

Codes Adminstration - I am unable to locate details on the construction of the stairs.
Correction

Codes Administration - The structural plans indicate that the freezer footings are to contain 3 #4's but it doese not indicate how they are to be installed.
Correction

Codes Administrtion - The plans do not provide for egress from the patio area.
Correction

Codes Administration - 2006 IBC 1009.5.3 - Enclosures under stairways. The walls and soffits within enclosed usable spaces under enclosed and unenclosed stairways shall be protected by 1-hour fire-resistance-rated construction or the fire-resistance rating of the stairway enclosure, whichever is greater. Access to the enclosed space shall not be directly from within the stair enclosure.
Correction

Codes Administration - 2006 IBC 1208.2 - Minimum ceiling heights. Occupiable spaces, habitable spaces and corridors shall have a ceiling height of not less than 7 feet 6 inches. Bathrooms, toilet rooms, kitchens, storage rooms and laundry rooms shall be permitted to have a ceiling height of not less than 7 feet. (See code for possible exceptions.)
Correction

Codes Administration - The required clear space for the water closets is not indicated on the plans.
Correction

Codes Administration - 2006 IMC 507.2.2 - Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines. (See code for possible exceptions.)
Correction

Fire Department- 2006 IFC 1004.8 Outdoor areas. Yards, patios, courts and similar outdoor areas accessible to and usable by the building occupants shall be provided with means of egress as required by this chapter. The occupant load of such outdoor areas shall be assigned by the fire code official in accordance with the anticipated use. Where outdoor areas are to be used by persons in addition to the occupants of the building, and the path of egress travel from the outdoor areas passes through the building, means of egress requirements for the building shall be based on the sum of the occupant loads of the building plus the outdoor areas.
Correction

Fire Department- 2006 IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - I am unable to locate calculations for air balancing.
Correction

Fire Department- 2006 IFC the storefront door that will be locked shall be marked "NOT AN EXIT"
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- What type of door hardware is on the east exit door?
Correction

Codes Administration - This permit does not include the construction of the cooler structure at this time as the Final Development Plan for this portion of the project has not been approved. Once the FDP has been approved this portion of work will be released.
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

Codes Adminstration - I am unable to locate details on the construction of the guards.
Correction

Codes Administration - I am unable to locate the loads used in the design of the structural systems.
Correction

Codes Administration - 2006 IBC 1015.1 - Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exist: 1. The occupant load of the space exceeds the values in Table 1015.1. 2. The common path of egress travel exceeds the limitations of Section 1014.3. 3. Where required by Sections 1015.3, 1015.4 and 1015.5. Exception: Group I-2 occupancies shall comply with Section 1014.2.2.
Correction

Fire Department- 2006 IFC 904.5 Wet-chemical systems. Wet-chemical extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 17A and their listing.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $571.48 $571.48 Paid 07/25/2008
89 Sewer Tap Fees $480.00 $480.00 Paid 07/25/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 07/28/2008
Piers/Caissons Inspection - Commercial Passed 07/29/2008
Correction
Resolved
07/29/2008
None PIERS APPROVED PER PLANS INTERIOR
All Rough Inspection - Commercial Partial 08/14/2008
Correction
Partial Correction
08/14/2008
None WALLS ONLY APPROVED. FIRE PLACE FRAMING APPROVED.
Correction
Resolved
08/14/2008
None RAISED FLOOR AREA APPROVED. NOTE - STAIRS NOT BUILT AT TIME OF INSPECTION
Correction
Partial Correction
08/14/2008
None PLUMBING - WALLS ONLY APPROVED
Correction
Partial Correction
08/14/2008
Smoke Alarms (IRC) ELECT. - WALLS ONLY APPROVED.
Above Ceiling Inspection Partial 08/14/2008
Correction
Partial Correction
08/14/2008
None HARD CEILING AREAS APPROVED.
Rough Framing Inspection - Commercial Request Complete 8/14/2008 8/14/2008 08/14/2008
Gas Piping Inspection - Commercial Failed 08/29/2008
Correction
Corrective Action Required
08/29/2008
Gas Piping Support (IRC) STRAP GAS PIPE TO SUPPORT BLOCKS. ROOF
Gas Service Inspection - Commercial Passed 08/29/2008
Correction
Resolved
08/29/2008
None GAS SERVICE APPROVED TEST PRESSURE 21 PSI. RELEASE GAS
All Rough Inspection - Commercial Partial 08/29/2008
Correction
Partial Correction
08/29/2008
None STAIR STRINGERS / RISE AND RUN ONLY APPROVED STAIRS ONLY
Above Ceiling Inspection Partial 08/29/2008
Correction
Partial Correction
08/29/2008
None HARD CEILING AREAS APPROVED.
Rough Framing Inspection - Commercial Request Complete 8/28/2008 8/29/2008 08/29/2008
Footing Inspection - Commercial Failed 09/09/2008
Correction
Partial Correction
09/09/2008
None PENDING PSI REPORT PENDING PSI
Electrical Service Inspection Failed 09/10/2008
Correction
Corrective Action Required
09/10/2008
System Service Ground (IRC) BUILDING STEEL GROUND REQUIRED
Electrical Service Inspection Passed 09/11/2008
Correction
Resolved
09/11/2008
None 400 AMP SERVICE APPROVED. RELEASE ELECTRIC SERVICE.
Correction
Resolved
09/11/2008
System Service Ground (IRC)
Above Ceiling Inspection Passed 09/19/2008
Correction
Resolved
09/19/2008
None
All Rough Inspection - Commercial Partial 09/23/2008
Correction
Partial Correction
09/23/2008
None
Correction
Partial Correction
09/23/2008
None
Correction
Resolved
09/23/2008
None
Correction
Partial Correction
09/23/2008
Smoke Alarms (IRC)
Correction
Partial Correction
09/23/2008
None STAIRS ONLY
Correction
Corrective Action Required
09/23/2008
None FRAMING APPROVED ON STRUCTURE ENCLOSING THE FREEZER AND COOLER.
Rough Mechanical Inspection - Commercial Partial 09/23/2008
Correction
Partial Correction
09/23/2008
None EXHAUST DUCT WELD LIGHT TEST APPROVED.
Rough Framing Inspection - Commercial Request Complete 9/23/2008 9/23/2008 09/23/2008
All Rough Inspection - Commercial Passed 10/01/2008
Correction
Resolved
10/01/2008
None
Correction
Resolved
10/01/2008
None
Correction
Resolved
10/01/2008
None
Correction
Resolved
10/01/2008
Smoke Alarms (IRC)
Correction
Resolved
10/01/2008
None STAIRS ONLY
Correction
Resolved
10/01/2008
None
Electrical Service Inspection Passed 10/01/2008
Correction
Resolved
10/01/2008
None 100 AMP SUB PANEL APPROVED. UTILITY ROOM SOUTH WALL
Rough Mechanical Inspection - Commercial Passed 10/01/2008
Correction
Resolved
10/01/2008
None
Footing Inspection - Commercial Passed 10/01/2008
Correction
Resolved
10/01/2008
None PENDING PSI
Gas Piping Inspection - Commercial Passed 10/01/2008
Correction
Resolved
10/01/2008
Gas Piping Support (IRC) ROOF
Occupancy Inspection - Codes Commercial Failed 10/02/2008
Correction
Corrective Action Required
10/02/2008
COOLER ENCLOSURER COMPLETE COOLER EXTERIOR COOLER
Correction
Corrective Action Required
10/02/2008
EGRESS WEST FRONT DOOR IS REQUIRED TO BE REMOVED AND REPLACED WITH GLASS. THE DOOR DOSE'T MEET THE REQUIREMENTS FOR EGRESS. WEST FRONT DOOR
Correction
Resolved
10/02/2008
UTILITY ROOM NOTE: UTILITY ROOM SHALL NOT BE USED AS AN OFFICE AS THIS AREA DOSEN'T MEET THE REQUIREMENTS FOR HABITABLE SPACE.
Hood/Duct Inspection Passed 10/02/2008
Correction
Resolved
10/02/2008
None APPROVED BY FIREDEPT. 10 - 1 - 08
Occupancy Inspection - Codes Commercial Failed 10/30/2008
Correction
Resolved
10/30/2008
EGRESS WEST FRONT DOOR
Correction
Corrective Action Required
10/30/2008
COOLER ENCLOSURER COMPLETE COOLER EXTERIOR COOLER
Correction
Corrective Action Required
10/30/2008
WEST FRONT DOOR WEST FRONT DOOR REQUIRED TO MEET THE REQUIREMENTS OF CODE MODIFICATION.
Occupancy Inspection - Codes Commercial Passed 10/31/2008
Correction
Resolved
10/31/2008
COOLER ENCLOSURER COOLER
Correction
Resolved
10/31/2008
None OCCUPANCY APPROVED CLOSE PERMIT C. O.
Correction
Resolved
10/31/2008
ACCESS
Correction
Resolved
10/31/2008
WEST FRONT DOOR APPROVED PER CODE MODIFICATION
Documents & Images
Date Uploaded File Type Document Name
07/31/2017 Long Sawmill Re-Inspection
07/31/2017 Long Sawmill Inspection
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home