Permit Application Status

B0800716


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0800716
Building Permit - Commercial
Certificate of Occupancy
ABUNDANT LIFE BAPTIST CHURCH OF LEES SUMMIT
NEW COMMERCIAL
NEW YOUTH MINISTRY FACILITY
05/27/2008
01/02/2009
11/08/2010
06/15/2010
Locations
Contacts
SHAW ELECTRIC COMPANY, Address:3600 FULLER AVE  
ALL-PRO SHEET METAL CO, Address:1216 SE BROADWAY STE A  
INTERNATIONAL ARCHITECTS ATELIER, Address:912 BROADWAY SUITE 300  
LYTLE CONSTRUCTION, Address:1100 SE HAMBLEN RD  
ABUNDANT LIFE BAPTIST CHURCH OF LEES SUMMIT, Address:414 SW PERSELS RD, Phone:(816) 554-8181  
ABUNDANT LIFE BAPTIST CHURCH OF LS MO, Address:414 SW PERSELS  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/28/2009 10/29/2010
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - 2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the evenet of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building requried to have two or more exits. 3. Exterior egress componenets at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2006 IBC 1007.1 - Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1015.1 or 1019.1 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2006 IBC 1008.1.9 - Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds. Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Gourp A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equiped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side.
Correction

Codes Administration - 2006 IBC 1009.10 - Handrails. Stairways shall have handrails on each side and shall comply with Section 1012. Where glass is used to provide the handrail, the handrail shall also comply with Section 2047.
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2006 IBC 1015.1 - Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exist: 1. The occupant load of the space exceeds the values in Table 1015.1. 2. The common path of egress travel exceeds the limitations of Section 1014.3. 3. Where required by Sections 1015.3, 1015.4 and 1015.5. Exception: Group I-2 occupancies shall comply with Section 1014.2.2.
Correction

Codes Administration - 2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Correction

Codes Administration - 2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.
Correction

Codes Administration - 2006 IBC 1110.2 - Directional signage. Directional signage indicating the route to the nearest like accessible element shall be provided a the following locations. These directional signs shall include the International Symbol of Accessibility: 1. Inaccessible building entrances. 2. Inaccessible public toilets and bathing facilities. 3. Elevators not serving an accessible route. 4. At each separate-sex toilet and bathing room indicating the location of the nearest unisex toilet or bathing room where provided in accordance with Section 1109.2.1. 5. At exits and elevators serving a required accessible space, but not providing an approved accessible means of egress, signage shall be provided in accordance with Section 1007.7.
Correction

Codes Administration - 2006 IBC 1704.1.1 - Statement of special inspections. The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with 106.1 as a condition for permit issuance. This statement shall be in accordance with Section 1705. Exceptions: 1. A statement of special inspections is not required for structures designed and constructed in accordance with the conventional construction provisions of Section 2308. 2. The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
Correction

Codes Administration - 2006 IBC 1704.1.2 - Report Requirement. Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon by the permit applicant and the building official prior to the start of work.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Correction

Codes Administration - 2006 IBC 3006.2 - Venting. Elevator machine rooms that contain solid-state equipment for elevator operation shall be provided with an independent ventilation or air-conditioning system to protect against the overheating of the electrical equipment. The system shall be capable of maintaining temperatures within the range established for the elevator equipment.
Correction

Codes Administration - 2006 IBC 508.2.2 - Separation. Incidential use areas shall be separated or protected, or both, in accordance with Table 508.2. 508.2.2.1 Constrction. Where Table 508.2 requires a fire-resistance-rated separation, the incidental use area shall be separated from the remainder of the building by a fire barrier constructed in accordance with Section 706 or a horizontal assembly constructed in accordance with Section 711, or both. Where Table 508.2 permits an automatic fire-extinguishing system without a fire barrier, the incidental use area shall be separated from the remainder of the building by construction capable of resisting the passage of smoke. The partitions shall extend from the floor to the underside of the fir-resistance-rated floor/ceiling assembly of fire-resistance-rated roof/ceiling assembly above or the underside of the roof sheathing, or sub deck above. Doors shall be self- or automatic closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permited in accordance with NFPA 80.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - 2006 IPC 310.5 - Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The construction of such walls or partitions shall incorporate waterproof, smooth, readily cleanable and nonabsorbent finish surfaces. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal a minimum of 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measured from the finished back wall surface, whichever is greater.
Correction

Codes Administration - 2006IPC 708.3.2 - Building sewers. Building sewers shall be provided with cleanouts located not more than 100 feet apart measured from the upstream entrance of the cleanout. For building sewers 8 inches and larger, manholes shall be provided and located not more than 200 from the junction of the building drain and building sewer, at each change in direction and at intervals of not more than 400 feet apart. Manholes and manhole covers shall be of an approved type.
Correction

Codes Administration - The Code Review provided on Sheet G001 does not provide the breakdown of the building area.
Correction

Codes Administration - The Code Review on Sheet G001 indicates the allowable number of stories and height but does not indicate the actual.
Correction

Codes Administration - An egress plan has not been provided.
Correction

Codes Administration - The wall type information provided on Sheet A001 does not include the termination height.
Correction

Codes Administration - The lower level foundation plan on Sheet S101 does not match the basement plan on Sheet A100 for the stair area of the mechanical room.
Correction

Codes Administration - Access is not being provided to open space 007.
Correction

Codes Administration - The structural plans indicate that the building is to be supported by soil capable of supporting 3000 psf. The assumed soil bearing capacity for the soil in Lee's Summit is 2,000 psf.
Correction

Codes Administration - The stair, handrail and guard details need additional information.
Correction

Codes Administration - Stair and handrail details are not provided for the stairs in the mechanical room.
Correction

Codes Administration - I am unable to locate details for the construction of the platform in the worship center.
Correction

Codes Administration - I am unable to locate information on the construction of the mixin booth.
Correction

Codes Administration - I am unable to locate details for the construction of the stairs to the platform in the worship center and the mixing booth.
Correction

Codes Administration - The elevator equipement room is required to have the same level of protection as the elevator hoistway which is to be protected as a shaft. Table 715.4 requires that a door in a one-hour rated shaft is required to be listed for one-hour. The door schedule on Sheet A700 indicates that the door is listed for 45 minutes.
Correction

Codes Administration - The required clear space at plumbing fixtures is not indicated on the plans.
Correction

Fire Department- 2006 IFC 503.3 Marking. Where required by the fire code official, approved signs or other approved notices shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs or notices shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Correction

Codes Administration - The cost of the basement finish area has not been provided.
Correction

Fire Department- 2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Correction

Fire Department- 2006 IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Fire Department- 2006 IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet (1829 mm) wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equipped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more then one-half the width of the door measured from the latch side.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative.
Correction

CA - Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration Department prior to the state insection so that a member of the staff can witness the inspection.
Correction

NOTE: The contractor must contact the Missouri Department of Natural Resources at 1-800-361-4827 prior to starting the demolition.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $12,577.24 $12,577.24 Paid 01/02/2009
84 Water Meters $1,325.93 $1,325.93 Paid 01/02/2009
85 Water Taps $9,523.00 $9,523.00 Paid 01/02/2009
89 Sewer Tap Fees $930.00 $930.00 Paid 01/02/2009
Right of Way Permit $35.00 $35.00 Paid 01/02/2009
0120 Building Permit Fee $727.05 $727.05 Paid 10/15/2009
89 Sewer Tap Fees $30.00 $30.00 Paid 10/15/2009
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Failed 01/07/2009
Correction
Corrective Action Required
01/07/2009
None SEE FOOTING INSPECTIONS ON FOUNDATION ONLY PERMIT PENDING ENGINEERS REPORT. SEE BELOW
Miscellaneous Inspection Failed 01/07/2009
Correction
Corrective Action Required
01/07/2009
CONTRACTOR STEVE 816-835-2701
Foundation Inspection - Commercial Failed 01/07/2009
Correction
Partial Correction
01/07/2009
None WEST WALL 1-9 AND SOUTH WALL F TO M SEE FOOTING INSPECTIONS ON FOUNDATION PERMIT. A-LINE
Footing Inspection - Commercial Failed 01/09/2009
Correction
Partial Correction
01/09/2009
None SEE FOOTING INSPECTIONS ON FOUNDATION ONLY PERMIT PENDING ENGINEERS REPORT. SEE BELOW
Correction
Resolved
01/09/2009
None AIR INTAKE FOOTING AND RETAINING WALL FOOTINWEST SIDE OG BUILDING- APPROVED RETAINING WALL WEST SIDE
Foundation Inspection - Commercial Failed 01/09/2009
Correction
Partial Correction
01/09/2009
None WEST WALL 1-9 AND SOUTH WALL F TO M SEE FOOTING INSPECTIONS ON FOUNDATION PERMIT. A-LINE
Foundation Inspection - Commercial Failed 01/20/2009
Correction
Partial Correction
01/20/2009
None LINE A 10-11 ; LINE 11 A-M, 10 COLUMNS WEST SECTION LINE G 10-11 NORTH WALL SEC
Foundation Inspection - Commercial Failed 02/02/2009
Correction
Partial Correction
02/02/2009
None LINE A 10-11 ; LINE 11 A-M, 10 COLUMNS WEST SECTION LINE G 10-11 LINE G TO ELEVATOR SHAFT NORTH WALL SEC
Correction
Resolved
02/02/2009
COLUMNS 8 WEST SIDE INTERIOR COLUMNS-APPROVED 7 EAST SIDE INTERIOR COLUMNS - APPROVED
Footing Inspection - Commercial Failed 02/06/2009
Correction
Partial Correction
02/06/2009
None FOOTING ON LOWER LEVEL COMPLETE-PENDING APPROVAL FROM ENGINEER REPORT. LOWER SECTION COMPLETE 2-6-9
Foundation Inspection - Commercial Failed 02/12/2009
Correction
Partial Correction
02/12/2009
None LINE A 10-11 ; LINE 11 A-M, 10 COLUMNS WEST SECTION LINE G 10-11 LINE G TO ELEVATOR SHAFT LINE G TO M COLUMN 8(SOUTH EAST) LINE A- 8 TO 10( WEST WALL NORTH WALL SEC
Foundation Inspection - Commercial Partial 02/19/2009
Correction
Partial Correction
02/19/2009
None WEST SIDE RETAINING WALL APPROVED
Foundation Inspection - Commercial Passed 02/20/2009
Correction
Resolved
02/20/2009
None WEST WALL 1-9 AND SOUTH WALL F TO M EAST WALL APPROVED SEE FOOTING INSPECTIONS ON FOUNDATION PERMIT. A-LINE
Correction
Resolved
02/20/2009
None LINE A 10-11 ; LINE 11 A-M, 10 COLUMNS WEST SECTION LINE G 10-11 LINE G TO ELEVATOR SHAFT LINE G TO M COLUMN 8(SOUTH EAST) LINE A- 8 TO 10( WEST WALL NORTH WALL SEC
Correction
Resolved
02/20/2009
COLUMNS 8 WEST SIDE INTERIOR COLUMNS-APPROVED 7 EAST SIDE INTERIOR COLUMNS - APPROVED
Correction
Resolved
02/20/2009
None WEST SIDE RETAINING WALL APPROVED EAST WALL COMPLETE- BASEMENT WALLS AND FOOTINGS COMPLETE- APPROVED PENDING SPECIAL INSPECTIONS APPROVAL.
Underground Electrical Inspection - Commercial Request Complete 2/26/2009 2/27/2009 02/27/2009
Underslab Plumbing Inspection - Commercial Failed 03/02/2009
Correction
Partial Correction
03/02/2009
None WEST SIDE APPROVED TO BACKFILL TO EJECTOR PIT. EAST SIDE APPROVED TO CENTER WALL. NEED TO SEE FROM CENTER WALL TO PIT. LOWER LEVEL
Footing Inspection - Commercial Failed 03/03/2009
Correction
Corrective Action Required
03/03/2009
SOUTH-GRADE LEVEL ELEVATION 4 PIERS APPROVED
Underslab Plumbing Inspection - Commercial Failed 03/04/2009
Correction
Partial Correction
03/04/2009
None LOWER LEVEL APPROVED LOWER LEVEL
Underslab Electrical Inspection - Commercial Failed 03/05/2009
Correction
Partial Correction
03/05/2009
BASEMENT LEVEL LOWER SLAB; EAST SECTION;
Footing Inspection - Commercial Failed 03/09/2009
Correction
Corrective Action Required
03/09/2009
SOUTH-GRADE LEVEL ELEVATION 4 PIERS APPROVED; B3 TO H3, AND 1 PIER;
Underslab Plumbing Inspection - Commercial Failed 03/11/2009
Correction
Partial Correction
03/11/2009
None LOWER LEVEL APPROVED. 6" FIRELINE AND MAIN LINE IN BUILDING LOWER LEVEL
Underslab Electrical Inspection - Commercial Failed 03/17/2009
Correction
Partial Correction
03/17/2009
BASEMENT LEVEL LOWER SLAB; EAST SECTION;REAR SECTION
Underground Electrical Inspection - Commercial Request Complete 3/16/2009 3/17/2009 03/17/2009
Underslab Electrical Inspection - Commercial Failed 03/18/2009
Correction
Partial Correction
03/18/2009
BASEMENT LEVEL LOWER SLAB; EAST SECTION;REAR SECTION, GROUND TO FOOTING STEEL- APPROVED
Underground Electrical Inspection - Commercial Request Complete 3/17/2009 3/18/2009 03/18/2009
Underslab Electrical Inspection - Commercial Failed 04/09/2009
Correction
Partial Correction
04/09/2009
MAIN FLOOR WEST SLAB AND EAST SLAB- APPROVED
Footing Inspection - Commercial Failed 05/06/2009
Correction
Resolved
05/06/2009
None AIR INTAKE FOOTING AND RETAINING WALL FOOTINWEST SIDE OG BUILDING- APPROVED. NORTH RETAINING WALL FOOTING - COMPLETE RETAINING WALL WEST SIDE
Correction
Resolved
05/06/2009
SOUTH-GRADE LEVEL ELEVATION 4 PIERS APPROVED; B3 TO H3, AND 1 PIER;
Underground Electrical Inspection - Commercial Failed 05/07/2009
Correction
Partial Correction
05/07/2009
DATA-PHONE WEST SIDE OF BUILDING- STREET TO REAR LOT
Underground Electrical Inspection - Commercial Request Complete 5/6/2009 5/7/2009 05/07/2009
Underground Electrical Inspection - Commercial Failed 05/12/2009
Correction
Partial Correction
05/12/2009
None LIGHT POLE TRENCH- EAST SIDE PARKING LOT-APPROVED
Underground Electrical Inspection - Commercial Request Complete 5/11/2009 5/12/2009 05/12/2009
Underground Electrical Inspection - Commercial Request Complete 5/14/2009 5/15/2009 05/15/2009
Underground Electrical Inspection - Commercial Failed 05/19/2009
Correction
Partial Correction
05/19/2009
None 14-LIGHT POLE TRENCH- EAST SIDE PARKING LOT LIGHTS -APPROVED
Piers/Caissons Inspection - Commercial Failed 05/19/2009
Correction
Partial Correction
05/19/2009
LIGHT POLE PIERS 14 PIERS EAST SIDE LIGHT POLE BASE & UNDERGROUND ELECTRIC- APPROVED SEE BELOW
Piers/Caissons Inspection - Commercial Passed 06/02/2009
Correction
Resolved
06/02/2009
LIGHT POLE PIERS LIGHT POLE BASE COMPLETE SEE BELOW
Rough Plumbing Inspection - Commercial Failed 06/24/2009
Correction
Corrective Action Required
06/24/2009
BASEMENT LEVEL DWV IN WALL - PARTIAL APPROVAL
Sewer Service Inspection - Commercial Request Complete 7/1/2009 7/1/2009 07/01/2009
Water Service Inspection - Commercial Request Complete 7/2/2009 7/2/2009 07/02/2009
Water Service Inspection Failed 07/07/2009
Correction
Partial Correction
07/07/2009
None building to backflow pit at road side.
Water Service Inspection - Commercial Request Complete 7/7/2009 7/7/2009 07/07/2009
Sewer Service Inspection Failed 07/08/2009
Correction
Partial Correction
07/08/2009
None BUILDING TO METER PIT AT STREET
Sewer Service Inspection - Commercial Request Complete 7/8/2009 7/8/2009 07/08/2009
Water Service Inspection Passed 07/10/2009
Correction
Resolved
07/10/2009
None
Sewer Service Inspection Passed 07/13/2009
Correction
Resolved
07/13/2009
None
Rated Assembly Inspection Failed 07/24/2009
Correction
Corrective Action Required
07/24/2009
STAGE FRAMING PLAN CALLS FOR L BRACKETS AT CONNECTION OF JOISTS TO RIM. THE TOP OF JOISTS ARE INSTEAD WELDED TO THE TOP FLANGE OF RIM. HAVE ENGINEER LOOK AT THIS OR REDO PER PLAN
Electrical Service Inspection Passed 08/19/2009
Correction
Resolved
08/19/2009
None
Rated Assembly Inspection Failed 09/01/2009
Correction
Resolved
09/01/2009
ELEVATOR SHAFT INSIDE LAYER APPROVED
All Rough Inspection - Commercial Failed 09/04/2009
Correction
Resolved
09/04/2009
FRAMING/ELECTRICAL/PLUMBING WALL APPROVED TO COVER-002;003;104;107;108;110;111;112;113;115;STAIR WALL- BSMT TO TOP OF CEILING 1ST FLOOR. SEE APPROVED ROOMS BELOW
Correction
Corrective Action Required
09/04/2009
CORRECTIONS SUPPORT PLMB PIPING 48" O.C.- 105-106; COMPLETE/SECURE ELECTRICAL -109
All Rough Inspection - Commercial Failed 09/08/2009
Correction
Resolved
09/08/2009
FRAMING/ELECTRICAL/PLUMBING WALL APPROVED TO COVER- -BSMT ONLY 4 ROOMS 002;003;005;006;104;105;106;107;108;109;110;111;112;113;115;STAIR WALL- BSMT TO TOP OF CEILING 1ST FLOOR. ***FROM ELEVATOR NORTH- ROUGH INSPECTION COMPLETE SEE APPROVED ROOMS BELOW
Correction
Partial Correction
09/08/2009
CORRECTIONS COMPLETE
All Rough Inspection - Commercial Failed 09/14/2009
Correction
Resolved
09/14/2009
FRAMING/ELECTRICAL/PLUMBING WALL APPROVED TO COVER- -BSMT ONLY 4 ROOMS 002;003;005;006;104;105;106;107;108;109;110;111;112;113;115;STAIR WALL- BSMT TO TOP OF CEILING 1ST FLOOR. 116;117;118;119;120;121A-121B;125 A-D; SEE APPROVED ROOMS BELOW
All Rough Inspection - Commercial Failed 09/18/2009
Correction
Resolved
09/18/2009
FRAMING/ELECTRICAL/PLUMBING WALL APPROVED TO COVER- -BSMT ONLY 4 ROOMS 002;003;005;006;104;105;106;107;108;109;110;111;112;113;115;STAIR WALL- BSMT TO TOP OF CEILING 1ST FLOOR. 116;117;118;119;120;121A-121B;125 A-D;STAGE, VESTIBULE HARD CEILING. SEE APPROVED ROOMS BELOW
Driveway Inspection Partial 09/25/2009
Rated Assembly Inspection Failed 09/28/2009
Correction
Partial Correction
09/28/2009
STAGE 1ST LAYER UNDER STAGE OK
Above Ceiling Inspection Failed 09/28/2009
Correction
Partial Correction
09/28/2009
HARD CEILING EASTSIDE OF STAGE, WEST STORAGE ROOM OF STAGE. APPROVED AREAS HARD CEILING OK TO COVER
Above Ceiling Inspection Failed 10/01/2009
Correction
Partial Correction
10/01/2009
HARD CEILING EASTSIDE OF STAGE, WEST STORAGE ROOM OF STAGE. 123;124A, OK TO COVER APPROVED AREAS HARD CEILING OK TO COVER
Rated Assembly Inspection Failed 10/01/2009
Correction
Resolved
10/01/2009
STAGE 1ST LAYER UNDER STAGE OK, 2ND LAYER OK
Above Ceiling Inspection Failed 10/02/2009
Correction
Partial Correction
10/02/2009
HARD CEILING EASTSIDE OF STAGE, WEST STORAGE ROOM OF STAGE. 123;124A,124B OK TO COVER APPROVED AREAS HARD CEILING OK TO COVER
Underslab Plumbing Inspection - Commercial Failed 10/19/2009
Correction
Partial Correction
10/19/2009
None LOWER BSMT - SUMP PUMP-AND LAV/SINK SOUTHWALL-APPROVED ADDITION BSMT
Above Ceiling Inspection Failed 10/20/2009
Correction
Partial Correction
10/20/2009
None 1ST FLOOR ABOVE CEILING-ALL AREAS APPROVED EXEPT ENTRY WAY(HIGH CEILING BETWEEN MAIN ENTRY DOORS. 1ST FLOOR
Correction
Corrective Action Required
10/20/2009
None NO INSPECTION IN BSMT - REMOVE TILES TO SEE LIGHT FIXTURES INSTALLED IN BSMT BATHROOMS AND STORAGE ROOM.
Above Ceiling Inspection Failed 10/29/2009
Correction
Partial Correction
10/29/2009
None - AREA BETWEEN MAIN ENTRANCE DOORS: - ONE (1) OPEN J-BOX AT EACH END. - ELECTRICAL CODUIT LAYING ON GRID THROUGH OUT 1ST FLOOR
All Rough Inspection - Commercial Passed 11/03/2009
Correction
Resolved
11/03/2009
FRAMING/ELECTRICAL/PLUMBING WALL APPROVED TO COVER- -BSMT ONLY 4 ROOMS 002;003;005;006;104;105;106;107;108;109;110;111;112;113;115;STAIR WALL- BSMT TO TOP OF CEILING 1ST FLOOR. 116;117;118;119;120;121A-121B;125 A-D;STAGE, VESTIBULE HARD CEILING. SEE APPROVED ROOMS BELOW
Correction
Resolved
11/03/2009
CORRECTIONS COMPLETE
Underslab Plumbing Inspection - Commercial Passed 11/03/2009
Correction
Resolved
11/03/2009
None LOWER LEVEL APPROVED. 6" FIRELINE AND MAIN LINE IN BUILDING LOWER LEVEL
Correction
Resolved
11/03/2009
None LOWER BSMT - SUMP PUMP-AND LAV/SINK SOUTHWALL-APPROVED ADDITION BSMT
Underslab Electrical Inspection - Commercial Passed 11/03/2009
Correction
Resolved
11/03/2009
BASEMENT LEVEL LOWER SLAB; EAST SECTION;REAR SECTION, GROUND TO FOOTING STEEL- APPROVED
Correction
Resolved
11/03/2009
MAIN FLOOR WEST SLAB AND EAST SLAB- APPROVED
Above Ceiling Inspection Failed 11/03/2009
Correction
Resolved
11/03/2009
HARD CEILING EASTSIDE OF STAGE, WEST STORAGE ROOM OF STAGE. 123;124A,124B OK TO COVER 1ST FLOOR HARD CEILING OK TO COVER
Correction
Resolved
11/03/2009
None 1ST FLOOR
Correction
Partial Correction
11/03/2009
None BSMT RESTOOMS- LIGHTING APPROVED -SET HVAC VENTS. JANITOR ROOM.
Correction
Corrective Action Required
11/03/2009
BASEMENT ADDITION BASEMENT ADDITION - NO INSPECTION AT THIS TIME
Rough Electrical Inspection - Commercial Failed 11/03/2009
Correction
Partial Correction
11/03/2009
BSMT ADDITION ROOMS-012-015-OK TO COVER EAST 010 CORRIDOR OK TO ONE SIDE.
Underground Electrical Inspection - Commercial Passed 11/03/2009
Correction
Resolved
11/03/2009
DATA-PHONE WEST SIDE OF BUILDING- STREET TO REAR LOT
Correction
Resolved
11/03/2009
None 14-LIGHT POLE TRENCH- EAST SIDE PARKING LOT LIGHTS -APPROVED
Rated Assembly Inspection Passed 11/03/2009
Correction
Resolved
11/03/2009
STAGE FRAMING
Above Ceiling Inspection Failed 11/12/2009
Correction
Partial Correction
11/12/2009
None BSMT RESTOOMS- LIGHTING APPROVED -3 RESTROOMS. JANITOR ROOM. APPROVED
Rough Electrical Inspection - Commercial Passed 11/23/2009
Correction
Resolved
11/23/2009
BSMT ADDITION ROOMS-012-015-OK TO COVER EAST 010 CORRIDOR OK TO ONE SIDE. BSMT ROOMS COMPLETE.
Occupancy Inspection - Codes Commercial Failed 12/02/2009
Correction
Resolved
12/02/2009
None REPORT ON FILE
Correction
Resolved
12/02/2009
ELEVATOR ELEVATOR REPORT ON FILE
Correction
Resolved
12/02/2009
Receive Water Utilities Approval PER BEN APPROVED
Correction
Corrective Action Required
12/02/2009
Receive Planning & Development Approval
Correction
Corrective Action Required
12/02/2009
Receive Fire Department approval PEND APPROVAL FOR TCO
Correction
Corrective Action Required
12/02/2009
Electrical Equipment Mounting (IRC) RECEPTACLE REQUIRED 25' FROM AC UNIT LOWER NORTH END NORTH LOWER AC UNIT
Correction
Corrective Action Required
12/02/2009
EGRESS BASEMENT EGRESS CORRIDOR LIGHTING REQUIRED FOR TCO. BASEMENT FINISH ADDED TO PERMIT BASEMENT
Correction
Corrective Action Required
12/02/2009
BASEMENT FINISH NO INSPECTION ON FINISHED CLASSROOMS IN BSMT-UNDER CONSTRUCTION. BMST FINISH
Correction
Corrective Action Required
12/02/2009
BASEMENT RESTROOM NORTH SINGLE RESTROOM VERTICAL GRAB BAR REQUIRED NORTH SINGLE
Correction
Corrective Action Required
12/02/2009
OCCUPANCY 1ST FLOOR ONLY WILL BE APPROVED FOR TCO (PENDING OTHER DEPARTMENTS) CORRIDOR CONSTRUCTION SHALL BE COMPLETE FOR BASEMENT CORRIDOR TCO.
Occupancy Inspection - Codes Commercial Failed 12/03/2009
Correction
Corrective Action Required
12/03/2009
Receive Fire Department approval 1ST FLOOR APPROVED FOR TCO ONLY PEND APPROVAL FOR TCO
Correction
Corrective Action Required
12/03/2009
Electrical Equipment Mounting (IRC) RECEPTACLE REQUIRED 25' FROM AC UNIT LOWER NORTH END NORTH LOWER AC UNIT
Correction
Corrective Action Required
12/03/2009
EGRESS BASEMENT EGRESS CORRIDOR LIGHTING REQUIRED FOR TCO. BASEMENT FINISH ADDED TO PERMIT BASEMENT
Correction
Corrective Action Required
12/03/2009
BASEMENT FINISH NO INSPECTION ON FINISHED CLASSROOMS IN BSMT-UNDER CONSTRUCTION. BMST FINISH
Correction
Resolved
12/03/2009
BASEMENT RESTROOM 3 RESTROOMS MECHANICAL ROOM-JANITOR ROOM INSPECTED WITH 1ST FLOOR- NOT APPROVD TO OCCUPY BASEMENT
Correction
Corrective Action Required
12/03/2009
OCCUPANCY 1ST FLOOR APPROVED BY FIRE AND CODES FOR TCO--- (PENDING OTHER DEPARTMENTS) CORRIDOR CONSTRUCTION SHALL BE COMPLETE FOR BASEMENT CORRIDOR TCO. ***NO TCO ISSUED*** SEE OTHER DEPARTMENTS BEFORE ISSUING TCO***
Occupancy Inspection - Codes Commercial Failed 12/08/2009
Correction
Partial Correction
12/08/2009
Receive Planning & Development Approval TCO ONLY
Correction
Corrective Action Required
12/08/2009
Receive Fire Department approval 1ST FLOOR APPROVED FOR TCO ONLY PEND APPROVAL FOR TCO
Correction
Corrective Action Required
12/08/2009
Electrical Equipment Mounting (IRC) RECEPTACLE REQUIRED 25' FROM AC UNIT LOWER NORTH END ON BSMT FINISH PERMIT NORTH LOWER AC UNIT
Correction
Corrective Action Required
12/08/2009
EGRESS BASEMENT EGRESS CORRIDOR LIGHTING REQUIRED FOR TCO OF BSMT. BASEMENT FINISH ADDED TO PERMIT BASEMENT
Correction
Corrective Action Required
12/08/2009
BASEMENT FINISH NO FINAL INSPECTION ON FINISHED CLASSROOMS IN BSMT-UNDER CONSTRUCTION. BMST FINISH
Correction
Resolved
12/08/2009
BASEMENT RESTROOM 3 RESTROOMS ,MECHANICAL ROOM,-JANITOR ROOM, INSPECTED WITH 1ST FLOOR-APPROVED FOR INSPECTION*** NOT APPROVD TO OCCUPY BASEMENT**PENDING CORRIDOR APPROVAL FOR EGRESS*
Correction
Corrective Action Required
12/08/2009
OCCUPANCY 1ST FLOOR ONLY APPROVED FOR TCO. BASEMENT CORRIDOR CONSTRUCTION SHALL BE COMPLETE FOR BASEMENT TCO.
Above Ceiling Inspection Failed 12/10/2009
Correction
Corrective Action Required
12/10/2009
BASEMENT ADDITION BASEMENT ADDITION - CORRIDORS -ALL BSMT OPEN PLENUM RETURN AIR: WRAP OR REMOVE DWV. PROVIDE LISTING AND APPLICATION OF MATERIAL BEING USED AT TIME OF INSPECTION. -CLASS ROOMS NOT INSPECTED AT THIS TIME-
Above Ceiling Inspection Passed 12/23/2009
Correction
Resolved
12/23/2009
None BSMT RESTOOMS- LIGHTING APPROVED -3 RESTROOMS. JANITOR ROOM. APPROVED
Correction
Resolved
12/23/2009
BASEMENT ADDITION bsmt above ceiling approved
Occupancy Inspection - Codes Commercial Failed 01/04/2010
Correction
Resolved
01/04/2010
Receive Fire Department approval 1ST FLOOR APPROVED BSMT LEVEL APPROVED FOR OCCUPANCY
Correction
Resolved
01/04/2010
Electrical Equipment Mounting (IRC)
Correction
Corrective Action Required
01/04/2010
EGRESS INSTALL HANDRAILS AT RAMP AND SOUTH STAIRS BSMT HANDRAILS
Correction
Resolved
01/04/2010
BASEMENT FINISH
Correction
Resolved
01/04/2010
BASEMENT RESTROOM
Correction
Resolved
01/04/2010
OCCUPANCY
Miscellaneous Inspection Failed 04/07/2010
Correction
Corrective Action Required
04/07/2010
TCO CALLED -ASHLEY- 4-7-10-TCO WILL EXPIRE 5-1-10 524-7275
Occupancy Inspection - Codes Commercial Failed 04/26/2010
Correction
Resolved
04/26/2010
EGRESS
Driveway Inspection Passed 05/12/2010
Sidewalk Inspection Passed 05/12/2010
Occupancy Inspection - Codes Commercial Failed 05/13/2010
Correction
Partial Correction
05/13/2010
Receive Planning & Development Approval PENDING APPROVAL FROM CHRIS H. TCO ONLY
Correction
Corrective Action Required
05/13/2010
Receive Public Works Approval PENDING APPROVAL FROM BILL LYON- EAST SIDE GROUND COVER-BOND.
Occupancy Inspection - Codes Commercial Failed 06/08/2010
Correction
Resolved
06/08/2010
Receive Public Works Approval approved -6-3-10
Occupancy Inspection - Codes Commercial Passed 06/11/2010
Correction
Resolved
06/11/2010
Receive Planning & Development Approval APPROVED 6-11-10 TCO ONLY
Rough Plumbing Inspection - Commercial Passed 06/14/2010
Correction
Resolved
06/14/2010
BASEMENT LEVEL DWV IN WALL - PARTIAL APPROVAL
Footing Inspection - Commercial Passed 06/14/2010
Correction
Resolved
06/14/2010
None SEE FOOTING INSPECTIONS ON FOUNDATION ONLY PERMIT PENDING ENGINEERS REPORT. SEE BELOW
Correction
Resolved
06/14/2010
None FOOTING ON LOWER LEVEL COMPLETE-PENDING APPROVAL FROM ENGINEER REPORT. LOWER SECTION COMPLETE 2-6-9
Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home