Summary
B0800710
Building Permit - Commercial
Certificate of Occupancy
RAZMJZ DEVELOPMENT LLC
NEW COMMERCIAL
CONVERT AND ADD TO AN EXISTING GARAGE FOR A DAYCARE
05/23/2008
07/29/2008
12/20/2009
06/25/2009
Locations
Contacts
ARCHITECTURAL DESIGN CONCEPTS, Address:10650 W 115TH ST  
CENTURY PLUMBING, Address:14001 CENTURY LANE  
ARROW CIRCLE ELECTRIC, Address:7801 BLUE RIDGE BLVD  
CHIEF HEATING AND COOLING, Address:920 NW TECHNOLOGY  
RAZMJZ DEVELOPMENT, Address:816 SW LAKE PINES DR  
RAZMJZ DEVELOPMENT LLC, Address:604 SW JEFFERSON  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/25/2009 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - 2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Correction

Codes Administration - The details on the plans for the rated wall construction don't match the construction requirements for wall type U303.
Correction

Codes Administration - 2006 IBC 704.2.3 - Combustible projections. Combustible projections located where openings are not permitted or where protection of openings is required shall be of at least 1-hour fire-resistance-rated construction, Type IV construction, fire-retardant-treated wood ar as required by Section 1406.3.
Correction

Codes Administration - I am unable to locate information on the mounting height of the water/drinking fountains. Section 1109.5.1 requires that one meet the requirments for people who use a wheel chair and one shall meet the requirements for standing persons.
Correction

Fire Department- In addition to meeting local codes, this facility shall meet State fire safety requlations. I do not see many of this requirements.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $415.15 $415.15 Paid 07/29/2008
89 Sewer Tap Fees $150.00 $150.00 Paid 07/29/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 08/01/2008
Correction
Partial Correction
08/01/2008
NORTH ADDITION OK TO POUR FOOTING FOR NORTH ADDITION. SOUTH ADDITION NOT READY FOR INSPECTION.
Footing Inspection - Commercial Passed 08/06/2008
Correction
Resolved
08/06/2008
FOOTING FOR SOUTH ADDITION OK TO POUR WHEN READY
Correction
Resolved
08/06/2008
NORTH ADDITION FOOTING @ NORTH ADDITION OK TO POUR
Underslab Plumbing Inspection - Commercial Failed 08/13/2008
Correction
Corrective Action Required
08/13/2008
UNDER-SLAB WASTE, SOIL, VENT PIPING NOT PER APPROVED DRWGS FLOW APPARENTLY REVERSED
Underslab Plumbing Inspection - Commercial Passed 08/22/2008
Correction
Resolved
08/22/2008
UNDER-SLAB WASTE, SOIL, VENT PIPING PER REVISED DRAWING OK TO COVER WHEN READY
Underground Plumbing Inspection - Commercial Passed 08/22/2008
Correction
Resolved
08/22/2008
WATER FEEDER LINE OK TO COVER WHEN READY FROM NEW BUILDING ENTRY TO EXISTING BUILDING
Correction
Resolved
08/22/2008
SANITARY DRAIN LINE FROM EJECTOR PUMP TO EXISTING BUILDING OK TO COVER WHEN READY
Water Service Inspection - Commercial Request Complete 8/22/2008 8/22/2008 08/22/2008
Sewer Service Inspection - Commercial Request Complete 8/22/2008 8/22/2008 08/22/2008
Gas Piping Inspection - Commercial Passed 09/09/2008
Correction
Resolved
09/09/2008
UNDERGROUND GAS FEEDER TUBING OK TO COVER WHEN READY FROM NEW BUILDING TO EXISTING BUILDING
Miscellaneous Inspection Partial 09/25/2008
Correction
Partial Correction
09/25/2008
COURTESY OBSERVATION PERFORMED W/ BOB Z 9/25
Gas Piping Inspection - Commercial Not Ready 10/03/2008
Correction
Corrective Action Required
10/03/2008
TEST PRESSURE LEVEL PRESSURIZE SYSTEM TO HOLD STEADY AT OR ABOVE 10 PSI REQUIRED MINIMUM BELOW REQUIRED MINIMUM GUAGE READS ZERO
Gas Piping Inspection - Commercial Not Ready 10/08/2008
Correction
Corrective Action Required
10/08/2008
TEST PRESSURE LEVEL PRESSURIZE SYSTEM TO HOLD STEADY AT OR ABOVE 10 PSI REQUIRED MINIMUM BELOW REQUIRED MINIMUM GUAGE READS 0.5 PSI
Gas Piping Inspection - Commercial Passed 10/22/2008
Correction
Resolved
10/22/2008
TEST PRESSURE LEVEL PRESSURE HELD STEADY AT >20 PSI FOR >15 MIN
All Rough Inspection - Commercial Failed 10/23/2008
Correction
Corrective Action Required
10/23/2008
FIRE-BLOCKING OF HVAC WALL PLENUMS M1601.3.3: FIRE-BLOCK ALL HOLES/BORES STUDS BOUNDING RETURN AIR PLENUMS
Correction
Corrective Action Required
10/23/2008
FIRE-BLOCKING OF LEVEL-TO-LEVEL OPENINGS M1601.3.3: FIRE-BLOCK ALL HOLES/BORES HOLES IN TOP PLATE VARIOUS LOCATIONS
Correction
Corrective Action Required
10/23/2008
HEADER BEARING SHIM GAPS @ TOP OF JACK STUDS WHERE HEADER BEARS. EAST WALL @ DOOR HEADER + WINDOW NORTH OF DOOR
All Rough Inspection - Commercial Failed 10/31/2008
All Rough Inspection - Commercial Not Ready 11/14/2008
Correction
Corrective Action Required
11/14/2008
READINESS FOR INSPECTION IBC 109.1, 109.5; IRC R109.3: NOT READY PROPERTY LOCKED INTERIOR NOT ACCESSIBLE
All Rough Inspection - Commercial Passed 11/19/2008
Correction
Resolved
11/19/2008
HEADER BEARING
Correction
Resolved
11/19/2008
FIRE-BLOCKING OF LEVEL-TO-LEVEL OPENINGS
Correction
Resolved
11/19/2008
FIRE-BLOCKING OF HVAC WALL PLENUMS
Correction
Resolved
11/19/2008
READINESS FOR INSPECTION
Miscellaneous Inspection Partial 03/12/2009
Correction
Partial Correction
03/12/2009
COURTESY OBSERVATION PERFORMED W/ MARION 3/12
Occupancy Inspection - Codes Commercial Failed 04/28/2009
Correction
Corrective Action Required
04/28/2009
GRAB BARS AT RESTROOM INSTALLATION NOT PER ANSI ANSI/ICC 604.5.1
Correction
Corrective Action Required
04/28/2009
ELECTRICAL PANEL SCHEDULE NEC 110-22; 384-13; IRC E36O6.2. EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. LABEL UNUSED BREAKERS "SPARE" INCOMPLETE/IMPROPER SERVICE PANEL
Correction
Corrective Action Required
04/28/2009
NON-METALLIC ELECTRICAL CONDUIT SECURE TO WALL WITHIN 12" OF ENTRY TO DISCONNECT ENCLOSURE AC CONDENSER WHIP NOT SECURED TO STRUCTURE
Correction
Corrective Action Required
04/28/2009
ELECTRICAL RECEPTACLE UNDER SINK WALL GAP NOT ALLOWED
Correction
Corrective Action Required
04/28/2009
WATER HEATER EXPANSION TANK NOT INSTALLED PER DRAWING
Correction
Corrective Action Required
04/28/2009
WATER SERVICE ASSEMBLY NOT PER DRAWING
Correction
Corrective Action Required
04/28/2009
SEALING OF EXTERIOR WALLS BEHIND ALL EQUIPMENT DISCONNECTS, RECEPTS, ETC
Correction
Corrective Action Required
04/28/2009
TESTING OF EXTERIOR ELECTRICAL RECEPTACLES COMPLETE FINISH SITEWORK. NOTE RECEPTACLE AT SOUTH WALL HAS NOT BEEN INSTALLED. SUBJECT TO APPROVAL WHEN SITE IS PASSABLE
Correction
Corrective Action Required
04/28/2009
PENETRATIONS/HOLES IN EXTERIOR WALL SEAL HOLES / ANNULAR SPACES SOME NOT SEALED PIPE, CONDUIT, CABLES#
Correction
Corrective Action Required
04/28/2009
Receive Water Utilities Approval
Correction
Corrective Action Required
04/28/2009
Receive Public Works Approval
Correction
Corrective Action Required
04/28/2009
Receive Planning & Development Approval
Correction
Corrective Action Required
04/28/2009
Receive Fire Department approval
Miscellaneous Inspection Passed 04/28/2009
Correction
Resolved
04/28/2009
COURTESY OBSERVATION
Occupancy Inspection - Codes Commercial Failed 05/28/2009
Correction
Resolved
05/28/2009
Receive Fire Department approval PER CPT JOE DIR 5/28/09
Correction
Corrective Action Required
05/28/2009
Receive Planning & Development Approval PHONE 816-969-1604 CONTACT HECTOR SOTO FOR INSPECTION WHEN READY
Correction
Corrective Action Required
05/28/2009
Receive Public Works Approval PHONE 816-969-1827 CONTACT SHAWN GRAFF WHEN READY FOR INSPECTION
Correction
Corrective Action Required
05/28/2009
Receive Water Utilities Approval REINSPECTION PENDING
Correction
Corrective Action Required
05/28/2009
TESTING OF EXTERIOR ELECTRICAL RECEPTACLES IS PROTECTION REDUNDANT? LOCATION OF RE-SET(S)? SUBJECT TO APPROVAL CLARIFY GFCI CIRCUITING
Correction
Corrective Action Required
05/28/2009
WATER SERVICE ASSEMBLY SUBJECT TO INSPECTION BU WATER DEPT
Correction
Resolved
05/28/2009
WATER HEATER EXPANSION TANK
Correction
Resolved
05/28/2009
ELECTRICAL RECEPTACLE UNDER SINK
Correction
Resolved
05/28/2009
NON-METALLIC ELECTRICAL CONDUIT
Correction
Resolved
05/28/2009
ELECTRICAL PANEL SCHEDULE
Correction
Resolved
05/28/2009
GRAB BARS AT RESTROOM ALLOWED AS EXCEPTION DUE TO INTERFERENCE BY WINDOW INSTALLATION NOT PER ANSI ANSI/ICC 604.5.1
Occupancy Inspection - Codes Commercial Passed 06/24/2009
Correction
Resolved
06/24/2009
Receive Planning & Development Approval PER HECTOR SOTO
Correction
Resolved
06/24/2009
Receive Public Works Approval PER SHAWN GRAFF 6/24/09
Correction
Resolved
06/24/2009
Receive Water Utilities Approval PER BEN HASKAMP 6/24/09
Correction
Resolved
06/24/2009
PENETRATIONS/HOLES IN EXTERIOR WALL SEALING OF HOLES / ANNULAR SPACES IN PROGRESS. SOME NOT SEALED PIPE, CONDUIT, CABLES#
Correction
Resolved
06/24/2009
TESTING OF EXTERIOR ELECTRICAL RECEPTACLES
Correction
Resolved
06/24/2009
SEALING OF EXTERIOR WALLS IN PROGRESS BEHIND ALL EQUIPMENT DISCONNECTS, RECEPTS, ETC
Correction
Resolved
06/24/2009
WATER SERVICE ASSEMBLY
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home