Permit Application Status

B0800516


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0800516
Building Permit - Commercial
Certificate of Occupancy
REORGANIZED SCHOOL DIST NO 7
ADDITION COMMERCIAL
BUILDING ADDITION FOR ALL-DAY KINDERGARTEN
04/29/2008
05/07/2008
09/23/2009
08/26/2009
Locations
Contacts
J E DUNN CONSTRUCTION, Address:929 HOLMES  
EDWARDS MCDOWELL, Address:400 EAST 10TH AVE  
REORGANIZED SCHOOL DIST NO 7, Address:600 SE MILLER ST  
ACI FRANGKISER HUTCHENS INC, Address:1421 E 104TH ST  
CRAWFORD MECHANICAL CONTRACTOR INC, Address:2033 SE M 291 HWY  
NORTH KANSAS CITY ELECTRIC CO INC, Address:PO BOX 12442  
REORGANIZED SCHOOL DIST NO 7, Address:301 NE TUDOR RD, Phone:(816) 986-1000  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/02/2008 10/29/2010
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Codes Administration - An egress plan has not been provided.
Correction

Codes Administration - The restrooms do not meet the requirements for accessiblity, even with allowances for children.
Correction

Codes Administration - The required clearances are indicated on in the restrooms but deminsions are not provided.
Correction

Codes Administration - The wall separating the structure into two separate buildings is mislabled as a fire barrier on the code plan. Only a fire wall can separate a building into two separate buildings.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building's fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Correction

Fire Department- 2006 IFC 1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building. Exception: Approved temporary means of egress systems and facilities.
Correction

Fire Department- 2006 IFC 901.7 Systems out of service. Where a required fire protection system is out of service, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. Where utilized, fire watches shall be provided with at least one approved means for notification of the fire department and their only duty shall be to perform constant patrols of the protected premises and keep watch for fires.
Correction

Codes Administration - 2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,864.43 $1,864.43 Paid 05/07/2008
89 Sewer Tap Fees $180.00 $180.00 Paid 05/07/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 06/17/2008
Correction
Partial Correction
06/17/2008
UNDER EXISTING CORIDOOR 6 INCH STORM LINE RUNS EAST AND TRANSITIONS TO 8 INCH AND TIES IN TO EXISTING STORM LINE UNDER CORIDOOR DOOR. 4 INCH SANITARY LINE RUNS EAST FROM WEST SIDE EXISTING FOOTING HEADS EAST AND TIES INTO EXISTING 4 INCH SANITARY. FROM W. EXISTING FOOTING TO END OF CORIDOOR
Underslab Plumbing Inspection - Commercial Passed 06/24/2008
Correction
Resolved
06/24/2008
None UNDERSLAB AT NEW ADDITION APPROVED
Correction
Resolved
06/24/2008
UNDER EXISTING CORIDOOR 6 INCH STORM LINE RUNS EAST AND TRANSITIONS TO 8 INCH AND TIES IN TO EXISTING STORM LINE UNDER CORIDOOR DOOR. 4 INCH SANITARY LINE RUNS EAST FROM WEST SIDE EXISTING FOOTING HEADS EAST AND TIES INTO EXISTING 4 INCH SANITARY. FROM W. EXISTING FOOTING TO END OF CORIDOOR
Footing Inspection - Commercial Partial 07/08/2008
Correction
Partial Correction
07/08/2008
None BUILDING WALL WEST THEN SOUTH TO MAIN ENTRANCE. NORTH FOOTING WEST WALL FOOTING PART.
Footing Inspection - Commercial Passed 07/09/2008
Correction
Resolved
07/09/2008
None BUILDING WEST WALL FROM WEST ENTRANCE SOUTH THEN EAST BACK TO BUILDING. FOOTING
Above Ceiling Inspection Failed 07/21/2008
Correction
Corrective Action Required
07/21/2008
None ABOVE CEILING AND CONDUIT INSPECTION ONLY, IN HALLWAY. WIRE NOT PULLED BOXES STILL OPEN. WOOD WALL TO EAST APPROVED TO INSTALL TILE. EXISTING BUILDING ONLY FROM WOOD WALL EAST
Rough Plumbing Inspection - Commercial Partial 07/25/2008
Correction
Partial Correction
07/25/2008
None -PLUMBING ROUGH APPROVED -RELOCATE EXISTING STORM DRAIN BEHIND NORTH BATH
Gas Service Inspection - Commercial Passed 10/07/2008
Correction
Resolved
10/07/2008
None GAS APPROVED TEST PRESSURE 10 PSI THIS IS AN ADDITION TO EXISTING GAS PIPE.
Gas Piping Inspection - Commercial Passed 10/07/2008
Correction
Resolved
10/07/2008
None TWO ROOF TOP UNITS FOR NEW ADDITION
Rough Electrical Inspection - Commercial Partial 10/17/2008
Correction
Partial Correction
10/17/2008
None ENTRY WAY CAN LIGHT - OUTSIDE WEST DOOR
Rough Electrical Inspection - Commercial Partial 10/21/2008
Correction
Partial Correction
10/21/2008
None EAST WALL ROOM CCO2 AND CCO4 APPROVED
Above Ceiling Inspection Partial 11/14/2008
Correction
Partial Correction
11/14/2008
OPEN J-BOX EAST END HALL CCO1 BELOW POWER SUPPLY BOX AND ABOVE NORTH WEST DOOR. OK TO INSTALL TILE EXCEPT AT ABOVE LOCATIONS
Correction
Corrective Action Required
11/14/2008
EXIT LIGHT EXIT LIGHT REQUIRED INSIDE WEST DOOR. CEILING EAST OF BLUE DOOR NOT INSPECTED. HALL - CCO1
Rough Electrical Inspection - Commercial Passed 02/11/2009
Correction
Resolved
02/11/2009
None
Above Ceiling Inspection Passed 02/11/2009
Correction
Resolved
02/11/2009
None EXISTING BUILDING ONLY FROM WOOD WALL EAST
Correction
Resolved
02/11/2009
EXIT LIGHT HALL - CCO1
Correction
Resolved
02/11/2009
OPEN J-BOX
Occupancy Inspection - Codes Commercial Failed 02/11/2009
Correction
Corrective Action Required
02/11/2009
EXTERIOR ITEMS FINAL GRADE SOD AND LANDSCAPING
Correction
Corrective Action Required
02/11/2009
LABEL ROOMS CLASS ROOMS
Correction
Corrective Action Required
02/11/2009
CLASS ROOM DOORS DOORS REQUIRES 20 MINUTE RATING HALL
Correction
Corrective Action Required
02/11/2009
EXTERIOR LIGHTS LIGHTS NOT INSTALLED OUTSIDE EXTERIOR DOORS. OUTSIDE DOORS
Rough Plumbing Inspection - Commercial Passed 02/11/2009
Correction
Resolved
02/11/2009
None
Occupancy Inspection - Codes Commercial Failed 03/27/2009
Correction
Resolved
03/27/2009
EXTERIOR LIGHTS
Correction
Resolved
03/27/2009
LABEL ROOMS CLASS ROOMS
Correction
Corrective Action Required
03/27/2009
Receive Planning & Development Approval
Occupancy Inspection - Codes Commercial Passed 08/05/2009
Correction
Resolved
08/05/2009
CLASS ROOM DOORS HALL
Correction
Resolved
08/05/2009
EXTERIOR ITEMS
Correction
Resolved
08/05/2009
Receive Planning & Development Approval 6-26-09
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home