Permit Application Status

B0800453


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0800453
Building Permit - Commercial
Certificate of Occupancy
REORGANIZED SCHOOL DIST NO 7
ADDITION COMMERCIAL
3 STORY CLASSROOM ADDITION ON THE NORTHWEST END OF THE BUILDING. APPROXIMATELY 9,000 SQURE FEET PER FLOOR
04/21/2008
07/22/2008
01/18/2009
01/15/2010
Locations
Contacts
HORST TERRILL & KARST ARCHITECTS, Address:9300 W 110TH ST SUITE 150  
J E DUNN CONSTRUCTION, Address:929 HOLMES  
CIMMARON ELECTRIC, INC., Address:1831 SW MARKET ST.  
VHC-VAN HOECKE CONTRACTING INC, Address:14150 SANTA FE TRAIL DR  
ALL STATE MECHANICAL INC, Address:12604 N 6TH ST  
REORGANIZED SCHOOL DIST NO 7, Address:301 NE Tudor Rd, Phone:(816) 986-1000  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/17/2008 10/29/2010
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1003.3.3 - Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches over any walking surface between the heights of 27 inches and 80 inches above the walking surface.
Correction

Codes Administration - 2006 IBC 1009.3.3 - Profile. The radius of curvature at the leading edge of the tread shall be not greater than 0.5 inch. Beveling of nosings shall not exceed 0.5 inch. Risers shall be solid and vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 degrees from the vertical. The leading edge (nosings) of treads shall project not more than 1.25 inches beyond the tread below and all projections of the leading edges shall be of uniform size, including the leading edge of the floor at the top of a flight.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2006 IBC 1704.1.1 - Statement of special inspections. The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with 106.1 as a condition for permit issuance. This statement shall be in accordance with Section 1705. Exceptions: 1. A statement of special inspections is not required for structures designed and constructed in accordance with the conventional construction provisions of Section 2308. 2. The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
Correction

Codes Administration - 2006 IBC 1704.1.2 - Report Requirement. Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon by the permit applicant and the building official prior to the start of work.
Correction

Codes Administration - 2006 IBC 508.2.2 - Separation. Incidential use areas shall be separated or protected, or both, in accordance with Table 508.2. 508.2.2.1 Constrction. Where Table 508.2 requires a fire-resistance-rated separation, the incidental use area shall be separated from the remainder of the building by a fire barrier constructed in accordance with Section 706 or a horizontal assembly constructed in accordance with Section 711, or both. Where Table 508.2 permits an automatic fire-extinguishing system without a fire barrier, the incidental use area shall be separated from the remainder of the building by construction capable of resisting the passage of smoke. The partitions shall extend from the floor to the underside of the fir-resistance-rated floor/ceiling assembly of fire-resistance-rated roof/ceiling assembly above or the underside of the roof sheathing, or sub deck above. Doors shall be self- or automatic closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permited in accordance with NFPA 80.
Correction

Codes Administration - 2006 IBC 707.2 - Shaft enclosure required. Openings through a floor/ceiling assembly shall be protected by a shaft enclosure complying with this section.
Correction

Fire Department- 2006 IFC 1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building. Exception: Approved temporary means of egress systems and facilities.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $19,518.84 $19,518.84 Paid 07/22/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 09/03/2008
Correction
Partial Correction
09/03/2008
None SHEET P1.1 4" SANITARY SEWER @ 2.6 BETWEEN LINE C & D - MOVED APPROX. 10' NORTH OF LINE 3. LENGTH 10' STUBBED UNDER GRADE BEAM LOCATION.
Correction
Resolved
09/03/2008
None 6" STORM WATER LINE @ LINE 4.5
Footing Inspection - Commercial Not Ready 09/09/2008
Correction
Corrective Action Required
09/09/2008
READINESS FOR INSPECTION REQUEST CANCELED BY P.H.
Footing Inspection - Commercial Partial 09/10/2008
Correction
Partial Correction
09/10/2008
READINESS FOR INSPECTION REQUEST CANCELED BY P.H.
Correction
Partial Correction
09/10/2008
None
Correction
Partial Correction
09/10/2008
None C LINE 3 TO 5
Rough Plumbing Inspection - Commercial Failed 09/10/2008
Correction
Corrective Action Required
09/10/2008
None NOT READY
Footing Inspection - Commercial Partial 09/10/2008
Correction
Partial Correction
09/10/2008
None B - LINE 4 TO 5 APPROVED
Footing Inspection - Commercial Partial 09/17/2008
Correction
Partial Correction
09/17/2008
None FOOTING APPROVED 3 LINE C TO D C LINE 2.3 TO 3 4 LINE 2.6 TO B 3 LINE A.6 TO A.9 A.6 LINE 2.3 TO 5
Footing Inspection - Commercial Partial 09/18/2008
Correction
Resolved
09/18/2008
None FOOTING APPROVED A3 LINE - 2.3 TO 5 LINE. 3 LINE A6 TO B B LINE 2.3 TO 3
Concrete Walls and Columns Inspection Partial 09/19/2008
Correction
Partial Correction
09/19/2008
None WALL SECTION APPROVED C LINE 5 TO 3.5 PILASTERS AT C4 AND C5
Footing Inspection - Commercial Partial 09/19/2008
Correction
Partial Correction
09/19/2008
READINESS FOR INSPECTION REQUEST CANCELED BY P.H.
Correction
Partial Correction
09/19/2008
None
Correction
Partial Correction
09/19/2008
None
Correction
Partial Correction
09/19/2008
None
Correction
Partial Correction
09/19/2008
None
Correction
Partial Correction
09/19/2008
None 2 LINE - A.6 TO B.8 B LINE 2 TO 2.5 A.9 LINE 2 TO 2 .5 A. LINE 6 2 TO 2.5
Footing Inspection - Commercial Partial 09/22/2008
Correction
Partial Correction
09/22/2008
None A LINE 2.3 TO 5 APPROVED
Footing Inspection - Commercial Partial 09/23/2008
Correction
Partial Correction
09/23/2008
None C LINE - C.5 TO D D LINE - 2.3 TO 3 2.3 LINE - D TO D.4 4.4 LINE - 0 TO 2.3 APPROVED
Footing Inspection - Commercial Partial 09/26/2008
Correction
Partial Correction
09/26/2008
None FOOTING APPROVED 2 LINE - A TO A.3 A LINE - 2 TO 2.3 A 3 LINE 2 TO 2.3 A 2 LINE 0.8 TO 2 0.8 LINE A.2 TO A.6 1 LINE A.6 TO B.8 B.8 LINE 1 TO 2 2 LINE B.8 TO C C LINE 2 TO 2.3
Underslab Plumbing Inspection - Commercial Partial 09/26/2008
Correction
Partial Correction
09/26/2008
None CONTINUATION OF SEWER TO ROOM NUMBERS A 009, A 010, A 011 AND A 012 APPROVED.
Correction
Resolved
09/26/2008
None
Foundation Inspection - Commercial Partial 09/29/2008
Correction
Partial Correction
09/29/2008
None WALL SECTION FROM C TO D ON 3 LINE APPROVED PER PLANS.
Underslab Plumbing Inspection - Commercial Partial 09/30/2008
Correction
Partial Correction
09/30/2008
None
Correction
Partial Correction
09/30/2008
None
Correction
Partial Correction
09/30/2008
None STORM DRAIN APPROVED PER PLANS FROM A TO B.2 BETWEEN 1 AND 2 LINES.
Foundation Inspection - Commercial Partial 10/01/2008
Correction
Partial Correction
10/01/2008
None WALL SECTION D LINE 2.4 TO 3. APPROVED
Foundation Inspection - Commercial Passed 10/02/2008
Correction
Resolved
10/02/2008
None FOUNDATION WALL APPROVED 2.3 LINE D TO D.4. FOUNDATION WALL COMPLET. PROVIDE SPECIAL INSPECTION REPORTS.
Underslab Electrical Inspection - Commercial Passed 10/06/2008
Rough Plumbing Inspection - Commercial Passed 10/27/2008
Correction
Resolved
10/27/2008
None
Correction
Resolved
10/27/2008
None SHEET P1.5 LOWER LEVEL - DETAIL 1 Lower Level Restrooms
Underslab Electrical Inspection - Commercial Partial 11/24/2008
Correction
Partial Correction
11/24/2008
None ELECT. CONDUIT IN 2 ND. FLOOR SLAB APPROVED
Rough Plumbing Inspection - Commercial Partial 12/08/2008
Correction
Partial Correction
12/08/2008
None
Correction
Partial Correction
12/08/2008
None Lower Level Restrooms
Correction
Partial Correction
12/08/2008
None ROOM 109 AND 110 APPROVED
Footing Inspection - Commercial Partial 12/17/2008
Correction
Partial Correction
12/17/2008
None SHEET S1.1 LINE C - FROM LINE 5 TO 6. LINE D - FROM LINE 3 TO E6
Underslab Electrical Inspection - Commercial Partial 01/09/2009
Correction
Partial Correction
01/09/2009
None ELECT. CONDUIT IN 3 ND. FLOOR SLAB APPROVED
Rough Plumbing Inspection - Commercial Partial 01/26/2009
Correction
Partial Correction
01/26/2009
None DWV - APPROVED A 209 & A 210 SOUTH WALL
Rough Framing Inspection - Commercial Partial 03/19/2009
Correction
Partial Correction
03/19/2009
None FRAMING OF METAL STUD WALLS APPROVED PER PLANS AT THE FOLLOWING LOCATIONS. LOWER LEVEL, MAIN LEVEL. UPPER LEVEL EXTERIOR WALLS ONLY AND A 200. ROOF PARAPET WALL NORTH, WEST AND SOUTH.
Rough Electrical Inspection - Commercial Partial 03/19/2009
Correction
Partial Correction
03/19/2009
None ELECTRICAL APPROVED WALLS ONLY LOWER LEVEL, MAIN LEVEL. WALLS ONLY
Rough Framing Inspection - Commercial Request Complete 3/18/2009 3/19/2009 03/19/2009
Rough Framing Inspection - Commercial Partial 03/27/2009
Correction
Partial Correction
03/27/2009
None UPPER LEVEL EXTERIOR WALLS, PENT HOUSE AND EAST PARAPET WALL FRAMING APPROVED.
Rough Framing Inspection - Commercial Request Complete 3/26/2009 3/27/2009 03/27/2009
Rough Plumbing Inspection - Commercial Partial 04/01/2009
Correction
Resolved
04/01/2009
None
Correction
Resolved
04/01/2009
None DWV - APPROVED Lower Level Restrooms
Correction
Resolved
04/01/2009
None
Correction
Partial Correction
04/01/2009
None DWV - APPROVED. ROOF STORM DRAIN PIPE APPROVED.
Rough Framing Inspection - Commercial Partial 04/10/2009
Correction
Partial Correction
04/10/2009
None UPPER LEVEL INTERIOR WALLS ONLY APPROVED UPPER LEVEL
Rough Electrical Inspection - Commercial Partial 04/10/2009
Correction
Partial Correction
04/10/2009
None UPPER LEVEL WALLS ONLY AND PENTHOUSE ELECT. APPROVED. WALLS ONLY
Rated Assembly Inspection Failed 05/26/2009
Correction
Partial Correction
05/26/2009
Through Penetrations (IRC) 2 ND. AND 3 RD FLOOR ONLY PARTIAL APP.
Above Ceiling Inspection Failed 05/26/2009
Correction
Corrective Action Required
05/26/2009
NOT READY
Rough Mechanical Inspection - Commercial Failed 05/28/2009
Correction
Partial Correction
05/28/2009
FIRE DAMPER INSTALLATION FIRE DAMPERS APPROVED EXCEPT FOR THE TWO {2} ON THE LOWER LEVEL SE. AREA AND UPPER LEVEL THE BOOT AND ACCESS DOOR IS NOT INSTALLED ON THE FIRE DAMPER BY THE SW. DOOR.
Rated Assembly Inspection Partial 06/02/2009
Correction
Partial Correction
06/02/2009
Through Penetrations (IRC) MECHANICAL SHAFT-1ST THROUGH 3RD FL. APPROVED
Above Ceiling Inspection Partial 06/10/2009
Correction
Partial Correction
06/10/2009
NOT READY
Correction
Partial Correction
06/10/2009
None ABOVE CEILING APPROVED 2 ND. AND 3 RD. FLOOR BATHROOMS {HARD CEILING}. OK TO INSTALL BORDER CEILING TILE 2 ND. AND 3 RD. FLOOR ONLY. BATHROOMS 2 ND & 3 RD FLOOR
Above Ceiling Inspection Partial 06/17/2009
Correction
Partial Correction
06/17/2009
None LOWER LEVEL BATHROOM ABOVE CEILING APPROVED ROOMS A009, AND A010. OK TO INSTALL BORDER TILE LOWER LEVEL. BATHROOMS LOWER LEVEL
Correction
Partial Correction
06/17/2009
None ABOVE CEILING APPROVED ROOMS A201,A202,A203,A204,A205,A206 LEAVE 1 TILE OUT IN FRONT OF DOOR TO A207.CORRIDOR C200, C201,C202. UPPER LEVEL
Correction
Partial Correction
06/17/2009
None ABOVE CEILING APPROVED A101,A102,A103,A104,A105,A106 LEAVE 1 TILE OUT EAST WALL TO A107. CORRIDORS C100,C101,C102. MAIN LEVEL
Above Ceiling Inspection Partial 06/25/2009
Correction
Partial Correction
06/25/2009
None BATHROOMS LOWER LEVEL
Correction
Partial Correction
06/25/2009
None UPPER LEVEL ABOVE CEILING APPROVED EXCEPT A200. UPPER LEVEL ROOM 207 & 208
Correction
Partial Correction
06/25/2009
None MAIN LEVEL ABOVE CEILING APPROVED EXCEPT A100. MAIN LEVEL ROOM 107 & 108
Correction
Partial Correction
06/25/2009
None LOWER LEVELROOM #s A001, A002, A003, A004, A005, A008, A009, A010, A011 AND A012. CORRIDORS C000 AND C001. NOTE: A000, A006 AND A007 NOT APPROVED. LOWER LEVEL
Electrical Service Inspection Passed 06/25/2009
Correction
Resolved
06/25/2009
None ELECT. SERVICE APPROVED PER PLANS. PP2H 480/ 277 VOLT. T1H, T2H, HBH, H1H, H2H, LBH1, L1H1 AND L2H1 APPROVED.
Above Ceiling Inspection Partial 07/08/2009
Correction
Partial Correction
07/08/2009
COMBUSTIBLES / LIGHT SUPPORT VESTIBULE A 000 - APPROVED TUTORIAL A 100 - REMOVE 2 X 4 ABOVE DROP CEILING TUTORIAL A 200 - 2 X 4 LAY IN FIXTURES REQUIRES HANGER SUPPORT WIRES AOOO, A100 & A200
Above Ceiling Inspection Partial 07/14/2009
Correction
Partial Correction
07/14/2009
COMBUSTIBLES / LIGHT SUPPORT
Correction
Partial Correction
07/14/2009
None TUTORIAL A 100 AND A 200 APPROVED.
All Rough Inspection - Commercial Partial 07/14/2009
Correction
Partial Correction
07/14/2009
None PENTHOUSE A 300 APPROVED.
Concrete Walls and Columns Inspection Passed 07/14/2009
Correction
Resolved
07/14/2009
None
Rated Assembly Inspection Passed 07/14/2009
Correction
Resolved
07/14/2009
Through Penetrations (IRC)
Rough Mechanical Inspection - Commercial Partial 07/14/2009
Correction
Partial Correction
07/14/2009
FIRE DAMPER INSTALLATION
Correction
Partial Correction
07/14/2009
None FIRE DAMPERS ROOM A 600 APPROVED EAST WALL. FIRE DAMPER INSTALLATION APPROVED.
Footing Inspection - Commercial Passed 07/14/2009
Correction
Resolved
07/14/2009
READINESS FOR INSPECTION REQUEST CANCELED BY P.H.
Correction
Resolved
07/14/2009
None
Correction
Resolved
07/14/2009
None
Correction
Resolved
07/14/2009
None
Correction
Resolved
07/14/2009
None
Correction
Resolved
07/14/2009
None
Correction
Resolved
07/14/2009
None
Underslab Plumbing Inspection - Commercial Passed 07/14/2009
Correction
Resolved
07/14/2009
None
Correction
Resolved
07/14/2009
None
Correction
Resolved
07/14/2009
None
Underslab Electrical Inspection - Commercial Passed 07/14/2009
Correction
Resolved
07/14/2009
None
Rough Framing Inspection - Commercial Passed 07/14/2009
Correction
Resolved
07/14/2009
None
Correction
Resolved
07/14/2009
None UPPER LEVEL
Rough Plumbing Inspection - Commercial Passed 07/14/2009
Correction
Resolved
07/14/2009
None
All Rough Inspection - Commercial Partial 07/16/2009
Correction
Partial Correction
07/16/2009
None
Correction
Partial Correction
07/16/2009
None WALL BETWEEN A006 AND A007 APPROVED A013 WALLS APPROVED. PER PR# 10
Rough Electrical Inspection - Commercial Partial 07/16/2009
Correction
Partial Correction
07/16/2009
None WALL BETWEEN A006 AND A007 AND WALLS A013. WALLS ONLY
Occupancy Inspection - Codes Commercial Failed 07/21/2009
Correction
Corrective Action Required
07/21/2009
Receive Planning & Development Approval P & D has not inspected.
Correction
Corrective Action Required
07/21/2009
Receive Public Works Approval P.W. has not inspected.
Correction
Corrective Action Required
07/21/2009
Receive Water Utilities Approval W.U. has not inspected
Correction
Corrective Action Required
07/21/2009
Exterior Lights 4 LIGHTS NOT INSTALLED Corridor Courtyard Side Lower and Main Level
Correction
Corrective Action Required
07/21/2009
Lower Level Bathrooms Lower level bathrooms incomplete
Correction
Corrective Action Required
07/21/2009
Accessible Grab Bars Verticle grab bars required in all bathrooms. All Bathrooms
Correction
Corrective Action Required
07/21/2009
Signage All door and accessiblilty signage required.
Correction
Corrective Action Required
07/21/2009
FEEDER FOR TRAILOR REMOVE TEMPORARY FEEDER FOR CONSTRUCTION TRAILOR. UPPER LEVEL & ROOF
Correction
Corrective Action Required
07/21/2009
Concrete Expansion Joint Provide perm. hard surface for concrete expansion joint at 2nd level exterior walkway. Upper Level Exterior Walk
Correction
Corrective Action Required
07/21/2009
Plumbing Fixtures Fixtures incomplete. A206
Correction
Corrective Action Required
07/21/2009
Exit Signs Egress to exterior walkway. Exit signs not visable on account of furout for steel column. A206 & A106
Correction
Corrective Action Required
07/21/2009
Unused Conductor Unused conductor at south side of equipment. Terminate or remove. Rooftop Chiller Room
Correction
Corrective Action Required
07/21/2009
Sprinkler Heads Sprinkler heads not dropped in this area. A007
Correction
Corrective Action Required
07/21/2009
Rooms A006 and A007 Not complete.
Correction
Corrective Action Required
07/21/2009
Receive Fire Department approval Under separate cover.
Correction
Partial Correction
07/21/2009
BUILDING ADDITION STATUS Building addition is okay to stock owner supplied fixtures and furniture. School staff may use building addition. This excludes rooms A006/A007 Do not open building addition to the public.
Above Ceiling Inspection Passed 07/28/2009
Correction
Resolved
07/28/2009
NOT READY
Correction
Resolved
07/28/2009
None BATHROOMS LOWER LEVEL
Correction
Resolved
07/28/2009
None UPPER LEVEL ABOVE CEILING APPROVED EXCEPT A200. UPPER LEVEL ROOM 207 & 208
Correction
Resolved
07/28/2009
None MAIN LEVEL ABOVE CEILING APPROVED EXCEPT A100. MAIN LEVEL ROOM 107 & 108
Correction
Resolved
07/28/2009
None LOWER LEVELROOM #s A001, A002, A003, A004, A005, A008, A009, A010, A011 AND A012. CORRIDORS C000 AND C001. NOTE: A000, A006 AND A007 NOT APPROVED. LOWER LEVEL
Correction
Resolved
07/28/2009
COMBUSTIBLES / LIGHT SUPPORT
Correction
Resolved
07/28/2009
None TUTORIAL A 100 AND A 200 APPROVED.
Occupancy Inspection - Codes Commercial Failed 08/07/2009
Correction
Resolved
08/07/2009
Receive Public Works Approval P.W. has not inspected.
Correction
Resolved
08/07/2009
Receive Water Utilities Approval W.U. has not inspected
Correction
Corrective Action Required
08/07/2009
Exterior Lights 3 lights above upper level stairs outside. 2 ground mounted lights in courtyard. Corridor Courtyard Side
Correction
Resolved
08/07/2009
Lower Level Bathrooms Lower level bathrooms incomplete
Correction
Resolved
08/07/2009
Accessible Grab Bars Verticle grab bars required in all bathrooms. All Bathrooms
Correction
Corrective Action Required
08/07/2009
Signage All door and accessiblilty signage required.
Correction
Resolved
08/07/2009
FEEDER FOR TRAILOR UPPER LEVEL & ROOF
Correction
Corrective Action Required
08/07/2009
Concrete Expansion Joint Provide perm. hard surface for concrete expansion joint at 2nd level exterior walkway. Upper Level Exterior Walk
Correction
Resolved
08/07/2009
Plumbing Fixtures A206
Correction
Resolved
08/07/2009
Exit Signs A206 & A106
Correction
Resolved
08/07/2009
Unused Conductor Rooftop Chiller Room
Correction
Resolved
08/07/2009
Sprinkler Heads A007
Correction
Resolved
08/07/2009
Rooms A006 and A007 Not complete.
Correction
Partial Correction
08/07/2009
Receive Fire Department approval Under separate cover
Correction
Resolved
08/07/2009
BUILDING ADDITION STATUS
Rough Electrical Inspection - Commercial Passed 08/14/2009
Correction
Resolved
08/14/2009
None WALL BETWEEN A006 AND A007 AND WALLS A013. WALLS ONLY
All Rough Inspection - Commercial Passed 08/14/2009
Correction
Resolved
08/14/2009
None
Correction
Resolved
08/14/2009
None WALL BETWEEN A006 AND A007 APPROVED A013 WALLS APPROVED. PER PR# 10
Occupancy Inspection - Codes Commercial Failed 08/14/2009
Correction
Resolved
08/14/2009
Receive Planning & Development Approval
Correction
Resolved
08/14/2009
Exterior Lights Corridor Courtyard Side
Correction
Corrective Action Required
08/14/2009
Signage All door and accessiblilty signage required.
Correction
Resolved
08/14/2009
Concrete Expansion Joint Provide perm. hard surface for concrete expansion joint at 2nd level exterior walkway. Upper Level Exterior Walk
Correction
Resolved
08/14/2009
Receive Fire Department approval
Correction
Resolved
08/14/2009
BUILDING ADDITION STATUS
Rough Mechanical Inspection - Commercial Passed 08/14/2009
Correction
Resolved
08/14/2009
FIRE DAMPER INSTALLATION
Correction
Resolved
08/14/2009
None FIRE DAMPERS ROOM A 600 APPROVED EAST WALL. FIRE DAMPER INSTALLATION APPROVED.
Occupancy Inspection - Codes Commercial Passed 01/12/2010
Correction
Resolved
01/12/2010
Signage All door and accessiblilty signage required.
Occupancy Inspection - Codes Commercial Passed 01/14/2010
Correction
Resolved
01/14/2010
Signage
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home