Permit Application Status

B0702588


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0702588
Building Permit - Commercial
Certificate of Occupancy
CHAPEL RIDGE RETAIL LLC
NEW TENANT FINISH
FOXY NAILS TENANT FINISH
12/19/2007
02/15/2008
11/05/2008
05/12/2008
Locations
Contacts
IDEAL ELECTRICAL SERVICES, Address:607 NE APPLEWOOD ST  
NEEDHAM PLUMBING & MECHANICAL, Address:PO BOX 3341  
C & E HEATING AND COOLING, Address:5501 MAPLE  
STEPHEN P MASLAN & CO, Address:8011 PASEO SUITE 201  
CHAPEL RIDGE RETAIL LLC, Address:3215 NE CARNEGIE DR STE 200  
ROCKY TOP HOLDINGS LLC, Address:244 W MILL ST STE 101  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/13/2008 10/29/2010
Correction

Fire Department- 2006 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - 2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.
Correction

Codes Administration - 2006 IBC 1014.4.1 - Aisles in Group B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - 2006 IBC 504.4 - Exhaust installation. Dryer exhaust ducts for clothes dryers shall terminate on the outside of the building and shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Ducts shall not be connected or installed with sheet metal screws or other fasteners that will obstruct the exhaust flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent or chimney. Clothes dryer exhaust ducts shall not extend into or through ducts or plenums.
Correction

Code Administration - 2006 IBC 504.6 - Domestic clothes dryer ducts. Exhaust ducts for domestic clothes dryers shall be constructed of metal and shall have a smooth interior finish. The exhaust duct shall be a minimum nominal size of 4 inches in diameter. The entire exhaust system shall be supported and secured in place. The male end of the duct at overlapped duct joints shall extend in the direction of airflow. Clothes dryer transition ducts used to connect the appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 feet and ahsll be listed and labeled for the application. Transition ducts shall not be concealed within construction.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

Codes Administration - 2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
Correction

Fire Department- 2006 IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - All companies working in Lee's Summit shall have a business license with the City.
Correction

Codes Administration - The address provided on the application was Suite I. The owner of the property has requested that the suites be identified numerically and therefore this space is Suite 116.
Correction

Codes Administration - A door and hardware schedule has not been provided.
Correction

Codes Administration - A finish schedule has not been provided.
Correction

Codes Administration - I am unable to locate information on the materials to be used in the mechanical installation.
Correction

Codes Administration - I am unable to locate the information for the materials and specs for the installation of the electrical system.
Correction

Codes Administration - An electrical panel schedule has not been provided.
Correction

Codes Administration - Footnote b of Table 403.3 does not allow for the recirculation of the required outside air or any outside air exceeding the required amount. The return air duct can not be located in the common hall.
Correction

Codes Administration - Footnote i of Table 403.3 states that the required exhaust system shall capture the contaminants and odors at their source.
Correction

Codes Administration - 2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $169.73 $169.73 Paid 02/15/2008
89 Sewer Tap Fees $900.00 $900.00 Paid 02/15/2008
91 EFHB Maybrook Water Shed $1,278.30 $1,278.30 Paid 02/15/2008
0122 Permit Reinspection Fees $30.00 $30.00 Paid 05/05/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 02/27/2008
Correction
Corrective Action Required
02/27/2008
VENTING DRAIN LINES SERVING CHAIRS ARE CIRCUIT VENTED. MUST BE INSTALLED PER 2006 IPC SECTION 911. I.E. MAX. 8 FIXTURES PER CIRCUIT & VENT CONNECTION BETWEEN UPPER 2 FIXTURES
Correction
Corrective Action Required
02/27/2008
INSTALLATION PER PLANS DRAIN INSTALLATION NOT PER PLANS. RE-ROUTE PIPING OR REVISE DRAWINGS TO REFLECT ACTUALL INSTALLATION. DO NOT COVER
Miscellaneous Inspection Failed 02/29/2008
Correction
Corrective Action Required
02/29/2008
CONTRACTOR LICENSING NOTE FROM PERMIT FILE: Do not provide plumbing and electrical inspections until license contractors are proviced and verified. RESCHEDULE INSPECTIONS AFTER SUB-CONTRACTORS ARE LISTED AND VERIFIED.
Underslab Plumbing Inspection - Commercial Passed 03/05/2008
Correction
Resolved
03/05/2008
VENTING
Correction
Resolved
03/05/2008
INSTALLATION PER PLANS
Rough Electrical Inspection - Commercial Passed 03/07/2008
Rough Plumbing Inspection - Commercial Failed 03/07/2008
Correction
Corrective Action Required
03/07/2008
STANDPIPE REQUIREMENTS TOP OF LAUNDRY STANDPIPE MUST BE MINIMUM 18" ABOVE WIER OF TRAP Laundry Room
Correction
Corrective Action Required
03/07/2008
Vent Connection (IRC) S-TRAP IS PROHIBITED. VENT CONNECTION MUST BE ABOVE WIER OF TRAP Laundry Room AT WASHING MACHINE
Correction
Corrective Action Required
03/07/2008
Water Hammer (IPC) PROVIDE WATER HAMMER ARRESTOR(S). IF NOT AT INDIVIDUAL QUICK CLOSING VALVES, MAY BE AT WATER ENTRY OR WATER HEATER (CHECK AT FINAL)
Correction
Corrective Action Required
03/07/2008
Piping Support (IRC) ALL DWV 2" & SMALLER REQUIRES MID-STUD SUPPORT THROUGHOUT
Rough Framing Inspection - Commercial Failed 03/07/2008
Correction
Corrective Action Required
03/07/2008
COVERING APPROVALS OK TO ROCK 1 SIDE OF WALLS
Correction
Corrective Action Required
03/07/2008
GRAB BAR SUPPORT PROVIDE BRACING IN WALLS FOR GRAB BAR SUPPORT RESTROOMS
Rough Framing Inspection - Commercial Passed 03/10/2008
Correction
Resolved
03/10/2008
COVERING APPROVALS OK ROCK - WALLS ONLY
Correction
Resolved
03/10/2008
GRAB BAR SUPPORT RESTROOMS
Rough Plumbing Inspection - Commercial Failed 03/10/2008
Correction
Resolved
03/10/2008
STANDPIPE REQUIREMENTS Laundry Room
Correction
Resolved
03/10/2008
Vent Connection (IRC) Laundry Room AT WASHING MACHINE
Correction
Resolved
03/10/2008
Piping Support (IRC) THROUGHOUT
Rough Electrical Inspection - Commercial Partial 03/10/2008
Correction
Partial Correction
03/10/2008
None WALLS ONLY
Miscellaneous Inspection Failed 03/20/2008
Correction
Corrective Action Required
03/20/2008
CONTRACTOR LICENSING ISSUES HAVE BEEN PRESENTED REGARDING WORK PERFORMED BY SUB-CONTRACTORS LISTED ON PERMIT. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL ISSUES ARE RESOLVED.
Rough Electrical Inspection - Commercial Partial 03/27/2008
Correction
Partial Correction
03/27/2008
None WALLS & CHAIR COLUMNS ONLY
Rough Mechanical Inspection - Commercial Not Ready 03/27/2008
Correction
Corrective Action Required
03/27/2008
TEXT AT CHAIR COLUMNS: NOT READY FOR INSPECTION
Rough Mechanical Inspection - Commercial Failed 03/28/2008
Correction
Corrective Action Required
03/28/2008
CONTRACTOR LICENSING ISSUES REMAIN WITH MECHANICAL CONTRACTOR. NO INSPECTIONS UNTIL RESOLVED.
Rough Mechanical Inspection - Commercial Failed 04/01/2008
Correction
Corrective Action Required
04/01/2008
CONTRACTOR LICENSING ISSUES REMAIN WITH MECHANICAL CONTRACTOR. NO INSPECTIONS UNTIL RESOLVED. 4/1/08 - ISSUES STILL UNRESOLVED, INSPECTION DENIED
Rough Mechanical Inspection - Commercial Passed 04/03/2008
Correction
Resolved
04/03/2008
CONTRACTOR LICENSING
Correction
Resolved
04/03/2008
TEXT AT CHAIR COLUMNS:OK TO COVER
Rough Framing Inspection - Commercial Passed 04/03/2008
Correction
Resolved
04/03/2008
COVERING APPROVALS OK ROCK - WALLS AND CHAIR COLUMNS
Rough Electrical Inspection - Commercial Passed 04/03/2008
Correction
Resolved
04/03/2008
None WALLS & CHAIR COLUMNS ONLY
Miscellaneous Inspection Passed 04/03/2008
Correction
Resolved
04/03/2008
CONTRACTOR LICENSING
Above Ceiling Inspection Not Ready 04/16/2008
Correction
Corrective Action Required
04/16/2008
SEE NOTE REMOVE ALL TILES FOR INSPECTION
Above Ceiling Inspection Failed 04/17/2008
Correction
Corrective Action Required
04/17/2008
DRYER DUCT - SUPPORT DRYER DUCT FROM STRUCTURE ABOVE - NO SCREWS ALLOWED IN DRYER DUCTS. (SEAL HOLES AFTER REMOVAL)
Correction
Corrective Action Required
04/17/2008
PLENUM ALL MATERIALS IN PLENUM MUST PLENUM RATED (NO PVC OR PEX) IF PLENUM IS ELIMINATED (RETURN DUCTED) COLD WATER PIPING AND SUPPLY AIR DUCTS WILL NEED TO BE INSULATED
Correction
Corrective Action Required
04/17/2008
FIRE PROTECTION EXTEND FIRE SPRINKLERS TO CEILING (COORDINATE WITH FIRE MARSHALL)
Correction
Corrective Action Required
04/17/2008
SEE NOTE DO NOT COVER
Above Ceiling Inspection Failed 04/24/2008
Correction
Corrective Action Required
04/24/2008
SEE NOTE 4/24/08 - ONLY 1 OF 3 VIOLATIONS ADDRESSED. REINSPECT FEE APPLIED DO NOT COVER
Correction
Resolved
04/24/2008
FIRE PROTECTION
Correction
Corrective Action Required
04/24/2008
DRYER DUCT - SUPPORT DRYER DUCT FROM STRUCTURE ABOVE - NO SCREWS ALLOWED IN DRYER DUCTS. (SEAL HOLES AFTER REMOVAL) 4/24/08 - SCREWS STILL IN DUCT AND COVERED BY TAPE
Above Ceiling Inspection Passed 04/25/2008
Correction
Resolved
04/25/2008
SEE NOTE
Correction
Resolved
04/25/2008
PLENUM
Correction
Resolved
04/25/2008
DRYER DUCT
Occupancy Inspection - Codes Commercial Failed 04/30/2008
Correction
Corrective Action Required
04/30/2008
NO SMOKING ORDINANCE PROVIDE NO-SMOKING SIGNAGE AT ENTRY DOORS Exterior DOORS
Correction
Corrective Action Required
04/30/2008
CONDUCTOR PROXIMITY TO COMBUSTIBLES AT WOOD COLUMNS: PROVIDE SPARK RINGS AT RECEPTACLES SALON
Correction
Corrective Action Required
04/30/2008
PLUMBING FINISH AT DOUBLE SINK IN SALON & SINK IN UTILITY ROOM: - PIPES MUST SLOPE TO DRAIN - TEE FITING MUST BE DIRECTIONAL TYPE
Correction
Corrective Action Required
04/30/2008
EQUIPMENT INSTALLATION PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR PEDI-CHAIRS. NOTE: BACKFLOW PREVENTION REQUIRED. SALON
Correction
Corrective Action Required
04/30/2008
TOILET INSTALLATION PROVIDE OPEN FRONT SEATS RESTROOMS
Correction
Corrective Action Required
04/30/2008
ACCESSIBILITY REQUIREMENTS PROVIDE ADA SIGNAGE RESTROOMS
Correction
Corrective Action Required
04/30/2008
DRYER DUCT TERMINATION REMOVE SCREEN FROM DRYER DUCT TERMINATION Exterior REAR
Correction
Corrective Action Required
04/30/2008
Panel Circuit Identification (IRC) - ALL BREAKERS MUST BE LABELLED (#16 LISTED AS SPACE, BUT THERE IS A BREAKER. - WHICH BREAKER SERVES ROOF TOP EXHAUST?
Correction
Corrective Action Required
04/30/2008
OVERCURRENT PROTECTION - BREAKER SERVING RTU IS OVERSIZED (MAX. 40A PER NAMEPLATE) NOTE: WHEN BREAKER IS DESIGNATED FOR EXHAUST FAN, MUST BE SIZED FOR 1/3HP MOTOR PANEL
Correction
Corrective Action Required
04/30/2008
ROOFTOP EQUIPMENT REQUIREMENTS - PROVIDE RECEPTACLE WITHIN 25' OF EQUIPMENT - PROVIDE DISCONNECT SWITCH FOR EXHAUST FAN - LABEL EQUIPMENT TO MATCH PANEL (SUITE #) - RESTROOM EXHAUST FAN TERMINATION TO BE 10' AWAY FROM INTAKES (OR 2' ABOVE) Roof
Correction
Corrective Action Required
04/30/2008
None DO NOT OCCUPY
Correction
Corrective Action Required
04/30/2008
Receive Fire Department approval UNDER SEPARATE COVER
Correction
Corrective Action Required
04/30/2008
Receive Water Utilities Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
04/30/2008
REINSPECT FEE PAYMENT OF OLD REINSPECT FEE REQUIRED PRIOR TO OCCUPANCY
Rough Plumbing Inspection - Commercial Passed 04/30/2008
Correction
Resolved
04/30/2008
Water Hammer (IPC)
Occupancy Inspection - Codes Commercial Failed 05/02/2008
Correction
Resolved
05/02/2008
Receive Fire Department approval
Correction
Corrective Action Required
05/02/2008
Receive Water Utilities Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
05/02/2008
REINSPECT FEE PAYMENT OF OLD REINSPECT FEE REQUIRED PRIOR TO OCCUPANCY
Correction
Corrective Action Required
05/02/2008
PLUMBING FINISH AT DOUBLE SINK IN SALON & SINK IN UTILITY ROOM: - PIPES MUST SLOPE TO DRAIN - TEE FITING MUST BE DIRECTIONAL TYPE
Correction
Resolved
05/02/2008
EQUIPMENT INSTALLATION
Correction
Resolved
05/02/2008
TOILET INSTALLATION
Correction
Resolved
05/02/2008
ACCESSIBILITY REQUIREMENTS
Correction
Resolved
05/02/2008
DRYER DUCT TERMINATION
Correction
Resolved
05/02/2008
Panel Circuit Identification (IRC)
Correction
Corrective Action Required
05/02/2008
OVERCURRENT PROTECTION - BREAKER SERVING RTU IS OVERSIZED (MAX. 40A PER NAMEPLATE) NOTE: WHEN BREAKER IS DESIGNATED FOR EXHAUST FAN, MUST BE SIZED FOR 1/3HP MOTOR PANEL
Correction
Corrective Action Required
05/02/2008
ROOFTOP EQUIPMENT REQUIREMENTS - PROVIDE RECEPTACLE WITHIN 25' OF EQUIPMENT - RESTROOM EXHAUST FAN TERMINATION TO BE 10' AWAY FROM INTAKES (OR 2' ABOVE) Roof
Occupancy Inspection - Codes Commercial Failed 05/05/2008
Correction
Resolved
05/05/2008
None 30 DAY TCO
Correction
Resolved
05/05/2008
Receive Water Utilities Approval
Correction
Resolved
05/05/2008
REINSPECT FEE
Correction
Resolved
05/05/2008
NO SMOKING ORDINANCE
Correction
Resolved
05/05/2008
CONDUCTOR PROXIMITY TO COMBUSTIBLES
Correction
Resolved
05/05/2008
PLUMBING FINISH
Correction
Resolved
05/05/2008
Panel Circuit Identification (IRC)
Correction
Resolved
05/05/2008
OVERCURRENT PROTECTION
Correction
Corrective Action Required
05/05/2008
ROOFTOP EQUIPMENT REQUIREMENTS - PROVIDE RECEPTACLE WITHIN 25' OF EQUIPMENT Roof
Occupancy Inspection - Codes Commercial Passed 05/09/2008
Correction
Resolved
05/09/2008
ROOFTOP EQUIPMENT REQUIREMENTS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home