Permit Application Status

B0702561


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0702561
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
LEGACY PARK BASEBALL VENUE CONCESSION/RESTROOMS BUILDING AND BLEACHERS
12/12/2007
06/17/2008
12/14/2008
07/02/2009
Locations
Contacts
BOWMAN BOWMAN NOVICK INC, Address:411 NICHOLS RD SUITE 246  
JENKINS & ASSOCIATES INC, Address:5600 MERRIAM DR  
LARRY D STRATE PLUMBING, Address:926 SW 465TH RD  
CAPITAL ELECTRIC CONSTRUCTION OF KC, Address:PO BOX 410079  
CUSTOM MECHANICAL INC, Address:709 SQUIRE CT  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/09/2008 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $2,101.02 $2,101.02 Paid 06/17/2008
89 Sewer Tap Fees $510.00 $510.00 Paid 06/17/2008
0120 Building Permit Fee ($2,101.02) ($2,101.02) $0.00 N/A
89 Sewer Tap Fees ($510.00) ($510.00) $0.00 N/A
0120 Building Permit Fee $2,101.02 $2,101.02 Paid 06/17/2008
89 Sewer Tap Fees $510.00 $510.00 Paid 06/17/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Not Ready 09/09/2008
Correction
Corrective Action Required
09/09/2008
Not Ready
Underground Electrical Inspection - Commercial Partial 09/09/2008
Correction
Partial Correction
09/09/2008
None WEST SIDE OF FOOTING - 3 - 3 1/2", 2 - 3", 3 - 2", 2 - 1" PVC INSTALLED
Footing Inspection - Commercial Passed 09/09/2008
Correction
Resolved
09/09/2008
None 2 - SOUTH EAST/WEST LINES, 2 NORTH/SOUTH LINES AT SOUTH END
Correction
Resolved
09/09/2008
None FOOTING COMPLETED
Underground Electrical Inspection - Commercial Request Complete 9/10/2008 9/11/2008 09/11/2008
Piers/Caissons Inspection - Commercial Partial 09/17/2008
Correction
Resolved
09/17/2008
Not Ready
Correction
Partial Correction
09/17/2008
None NORTH PIER ON NORTH-SOUTH LINE AS PER MANUFACTURER'S SPECIFICATIONS.
Piers/Caissons Inspection - Commercial Partial 09/18/2008
Correction
Partial Correction
09/18/2008
None NORTH PIER ON NORTH-SOUTH LINE. 2nd PIER FROM NORTH END OF NORTH SOUTH LINE. AS PER MANUFACTURER'S SPECIFICATIONS. North/South Line
Correction
Partial Correction
09/18/2008
None TWO PIER ON EAST SIDE OF EAST/WEST LINE AS PER MANUFACTURER'S SPECIFICATIONS East/West Line
Footing Inspection - Commercial Partial 09/18/2008
Correction
Resolved
09/18/2008
None 2 - SOUTH EAST/WEST LINES, 2 NORTH/SOUTH LINES AT SOUTH END Concession Stand
Correction
Resolved
09/18/2008
None FOOTING COMPLETED Concession Stand
Correction
Partial Correction
09/18/2008
None APPROVED EXCEPT FOR THE TOP LEVEL OF REBAR Signage
Underground Electrical Inspection - Commercial Request Complete 9/18/2008 9/18/2008 09/18/2008
Underground Electrical Inspection - Commercial Request Complete 9/18/2008 9/18/2008 09/18/2008
Piers/Caissons Inspection - Commercial Partial 09/19/2008
Correction
Partial Correction
09/19/2008
None NORTH PIER ON NORTH-SOUTH LINE. TWO PIERS SOUTH END OF NORTH SOUTH LINE. AS PER MANUFACTURER'S SPECIFICATIONS. North/South Line
Correction
Partial Correction
09/19/2008
None TWO PIERS ON EAST SIDE OF EAST/WEST LINE. TWO PIERS ON WEST SIDE OF EAST/WEST LINE. AS PER MANUFACTURER'S SPECIFICATIONS East/West Line
Underground Electrical Inspection - Commercial Partial 09/23/2008
Correction
Partial Correction
09/23/2008
None WEST SIDE OF FOOTING - 3 - 3 1/2", 2 - 3", 3 - 2", 2 - 1" PVC INSTALLED
Correction
Partial Correction
09/23/2008
None PVC STUBBED AT MONUMENT PIER Monument
Footing Inspection - Commercial Passed 09/23/2008
Correction
Resolved
09/23/2008
None Monument
Piers/Caissons Inspection - Commercial Passed 09/23/2008
Correction
Resolved
09/23/2008
None NORTH PIER ON NORTH-SOUTH LINE. TWO PIERS - SOUTH END OF NORTH/SOUTH LINE. TWO PIERS - NORTH END OF NORTH/SOUTH LINE. AS PER MANUFACTURER'S SPECIFICATIONS. North/South Line
Correction
Resolved
09/23/2008
None TWO PIERS ON EAST SIDE OF EAST/WEST LINE. TWO PIERS ON WEST SIDE OF EAST/WEST LINE. AS PER MANUFACTURER'S SPECIFICATIONS East/West Line
Underground Electrical Inspection - Commercial Request Complete 9/22/2008 9/23/2008 09/23/2008
Footing Inspection - Commercial Not Ready 09/24/2008
Correction
Corrective Action Required
09/24/2008
Not Ready
Piers/Caissons Inspection - Commercial Partial 09/25/2008
Correction
Resolved
09/25/2008
None PERIMETER LIGHTS COMPLETED SE Field
Correction
Partial Correction
09/25/2008
None EAST PIER ON PERIMETER LIGHTS SW Field
Piers/Caissons Inspection - Commercial Partial 09/26/2008
Correction
Resolved
09/26/2008
None EAST PIER ON PERIMETER LIGHTS PIERS COMPLETED SW Field
Correction
Resolved
09/26/2008
None PIERS COMPLETED NE Field
Correction
Partial Correction
09/26/2008
None WEST PIER COMPLETED NW Field
Piers/Caissons Inspection - Commercial Passed 09/29/2008
Correction
Resolved
09/29/2008
None WEST PIER COMPLETED EAST PIER COMPLETED NW Field
Underground Electrical Inspection - Commercial Partial 10/03/2008
Correction
Partial Correction
10/03/2008
None FROM EXISTING LINES TO MDP - 3 - 3", 3 - 2", 2 - 1 1/2" PVC. NO APPROVED PLANS ON SITE - COVER AT OWN RISK
Underground Electrical Inspection - Commercial Request Complete 10/2/2008 10/3/2008 10/03/2008
Underground Electrical Inspection - Commercial Partial 10/06/2008
Correction
Partial Correction
10/06/2008
None WEST SIDE OF FOOTING - 3 - 3 1/2", 2 - 3", 3 - 2", 2 - 1" PVC INSTALLED Light Poles
Correction
Partial Correction
10/06/2008
None FROM EXISTING LINES TO MDP - 3 - 3", 3 - 2", 2 - 1 1/2" PVC. NO APPROVED PLANS ON SITE - COVER AT OWN RISK Light Poles
Correction
Partial Correction
10/06/2008
None SEE DIAGRAM Light Poles
Underground Electrical Inspection - Commercial Request Complete 10/6/2008 10/6/2008 10/06/2008
Underground Electrical Inspection - Commercial Partial 10/08/2008
Correction
Partial Correction
10/08/2008
None SEE DIAGRAM Light Poles
Correction
Partial Correction
10/08/2008
See Sketch Light Poles
Water Service Inspection Partial 10/08/2008
Correction
Partial Correction
10/08/2008
None FIRST 100' FROM CONCESSION STAND TO FOUNTAIN SITE Drinking Fountain
Sewer Service Inspection Passed 10/08/2008
Correction
Resolved
10/08/2008
None
Underslab Plumbing Inspection - Commercial Partial 10/08/2008
Correction
Partial Correction
10/08/2008
None GREASE TRAP & PIPING NOT INSTALLED
Underground Electrical Inspection - Commercial Request Complete 10/7/2008 10/8/2008 10/08/2008
Sewer Service Inspection - Commercial Request Complete 10/7/2008 10/8/2008 10/08/2008
Water Service Inspection Partial 10/09/2008
Correction
Partial Correction
10/09/2008
None TO A POINT APPROX. 20' FROM OUTFIELF FENCING AT NE FIELD Drinking Fountain
Correction
Resolved
10/09/2008
None 2" COPPER LINE TO CONCESSION STAND Service Entrance
Underground Electrical Inspection - Commercial Partial 10/09/2008
Correction
Partial Correction
10/09/2008
None FROM EXISTING LINES TO MDP - 3 - 3", 3 - 2", 2 - 1 1/2" PVC. NO APPROVED PLANS ON SITE - COVER AT OWN RISK Light Poles
Correction
Partial Correction
10/09/2008
None SEE DIAGRAM Light Poles
Correction
Partial Correction
10/09/2008
See Sketch Light Poles/Outlets
Correction
Resolved
10/09/2008
None Light Poles
Underground Electrical Inspection - Commercial Request Complete 10/9/2008 10/9/2008 10/09/2008
Water Service Inspection - Commercial Request Complete 10/9/2008 10/9/2008 10/09/2008
Underground Plumbing Inspection - Commercial Request Complete 10/9/2008 10/9/2008 10/09/2008
Underground Electrical Inspection - Commercial Partial 10/13/2008
Correction
Partial Correction
10/13/2008
None Light Pole Ground Rods
Underground Electrical Inspection - Commercial Request Complete 10/13/2008 10/13/2008 10/13/2008
Water Service Inspection Partial 10/14/2008
Correction
Partial Correction
10/14/2008
None TO A POINT APPROX. 20' FROM OUTFIELD FENCING AT NE FIELD Drinking Fountain
Correction
Partial Correction
10/14/2008
None TO A POINT OPPOSITE THE SOUTH LIGHT POLE BETWEEN THE TWO NORTH FIELDS Drinking Fountain
Correction
Resolved
10/14/2008
None TO A POINT APPROX. 15' FROM FOUNTAIN Drinking Fountain
Water Service Inspection - Commercial Request Complete 10/14/2008 10/14/2008 10/14/2008
Underground Electrical Inspection - Commercial Partial 10/21/2008
Correction
Partial Correction
10/21/2008
None ALL BETWEEN FIELD LIGHT POLES COMPLETED Light Pole Ground Rods
Underslab Electrical Inspection - Commercial Passed 10/21/2008
Correction
Resolved
10/21/2008
None
Underground Electrical Inspection - Commercial Request Complete 10/20/2008 10/21/2008 10/21/2008
Underground Electrical Inspection - Commercial Not Ready 11/04/2008
Correction
Corrective Action Required
11/04/2008
Not Ready Light Pole Ground Rods
Underground Electrical Inspection - Commercial Request Complete 11/3/2008 11/4/2008 11/04/2008
Underground Electrical Inspection - Commercial Passed 11/05/2008
Correction
Resolved
11/05/2008
None WEST SIDE OF FOOTING - 3 - 3 1/2", 2 - 3", 3 - 2", 2 - 1" PVC INSTALLED Light Poles
Correction
Resolved
11/05/2008
None PVC STUBBED AT MONUMENT PIER Monument
Correction
Resolved
11/05/2008
None FROM EXISTING LINES TO MDP - 3 - 3", 3 - 2", 2 - 1 1/2" PVC. NO APPROVED PLANS ON SITE - COVER AT OWN RISK Light Poles
Correction
Resolved
11/05/2008
None SEE DIAGRAM Light Poles
Correction
Resolved
11/05/2008
See Sketch Light Poles/Outlets
Correction
Resolved
11/05/2008
None ALL BETWEEN FIELD LIGHT POLES COMPLETED Light Pole Ground Rods
Correction
Resolved
11/05/2008
Not Ready ALL OUTFIELD POLES COMPLETED Light Pole Ground Rods
Correction
Resolved
11/05/2008
None POWER LINES FROM CONCESSION STAND TO MONUMENT STAND Monument
Underground Electrical Inspection - Commercial Request Complete 11/4/2008 11/5/2008 11/05/2008
Water Service Inspection Passed 11/20/2008
Correction
Resolved
11/20/2008
None Drinking Fountain
Correction
Resolved
11/20/2008
None Drinking Fountain
Correction
Resolved
11/20/2008
None Service Entrance
Correction
Resolved
11/20/2008
None Drinking Fountain
Correction
Resolved
11/20/2008
None Drinking Fountain
Water Service Inspection - Commercial Request Complete 11/20/2008 11/20/2008 11/20/2008
Rough Framing Inspection - Commercial Passed 12/22/2008
Rough Framing Inspection - Commercial Request Complete 12/19/2008 12/22/2008 12/22/2008
All Rough Inspection - Commercial Partial 01/07/2009
Correction
Partial Correction
01/07/2009
None - SOUTH SIDE - IN WALL PVC - ENSURE ACCESS TO CLEANOUTS. - NORTH SIDE - PVC - WASTE & VENT LINES. Top Rough
Footing Inspection - Commercial Passed 01/07/2009
Correction
Resolved
01/07/2009
Not Ready
All Rough Inspection - Commercial Passed 01/09/2009
Correction
Resolved
01/09/2009
None - SOUTH SIDE - IN WALL PVC - ENSURE ACCESS TO CLEANOUTS. - NORTH SIDE - PVC - WASTE & VENT LINES. Top Rough
Correction
Resolved
01/09/2009
None SINK WATER & DWV - NE ROOM Concession
Footing Inspection - Commercial Passed 01/09/2009
Correction
Resolved
01/09/2009
None Trash Enclosure
Underslab Plumbing Inspection - Commercial Passed 01/12/2009
Correction
Resolved
01/12/2009
None see letter from Larry Strate Plumbing dated 12 Jan 09.
Above Ceiling Inspection Passed 02/11/2009
Correction
Resolved
02/11/2009
None
Electrical Service Inspection Passed 02/19/2009
Correction
Resolved
02/19/2009
Not Ready
Occupancy Inspection - Codes Commercial Failed 04/10/2009
Correction
Corrective Action Required
04/10/2009
SOD/SEED DISTURBED AREA
Correction
Corrective Action Required
04/10/2009
Receive Fire Department approval
Correction
Corrective Action Required
04/10/2009
Receive Water Utilities Approval
Correction
Corrective Action Required
04/10/2009
Receive Public Works Approval
Correction
Corrective Action Required
04/10/2009
Receive Planning & Development Approval
Correction
Corrective Action Required
04/10/2009
Outdoor GFCI Receptacles (IRC) PROVIDE WEATHER-PROOF COVERS
Correction
Corrective Action Required
04/10/2009
INSTALL RESTROOM SIGNAGE
Correction
Corrective Action Required
04/10/2009
INSTALL VACUMN BREAKERS FOR ALL HOSE BIBBS
Underground Electrical Inspection - Commercial Passed 04/15/2009
Occupancy Inspection - Codes Commercial Failed 05/06/2009
Correction
Resolved
05/06/2009
SOD/SEED DISTURBED AREA
Correction
Resolved
05/06/2009
Receive Water Utilities Approval DISTRICT 13
Correction
Partial Correction
05/06/2009
Receive Planning & Development Approval
Correction
Resolved
05/06/2009
Outdoor GFCI Receptacles (IRC)
Correction
Resolved
05/06/2009
INSTALL RESTROOM SIGNAGE
Correction
Resolved
05/06/2009
INSTALL VACUMN BREAKERS FOR ALL HOSE BIBBS
Occupancy Inspection - Codes Commercial Failed 06/25/2009
Correction
Resolved
06/25/2009
Receive Public Works Approval see email from S. Graff dated 6-25-09
Occupancy Inspection - Codes Commercial Failed 06/26/2009
Correction
Resolved
06/26/2009
Receive Planning & Development Approval see email - H. Soto - 26 Jun 09
Occupancy Inspection - Codes Commercial Passed 07/01/2009
Correction
Resolved
07/01/2009
Receive Fire Department approval see email from J. Dir dated 1 July 09
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home