Permit Application Status

B0702540


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0702540
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
LEES SUMMIT AIRPORT MODULAR UNITS
12/05/2007
08/04/2008
01/31/2009
05/15/2009
Locations
Contacts
RF FISHER ELECTRIC COMPANY LLC, Address:1707 W 39TH AVE  
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/10/2009 10/29/2010
Correction

Codes Administration - 2006 IBC 1012.5 - Handrail Extensions. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight or ramp run. At stairways where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser. At ramps where handrails are not continuous between runs, the handrail shall extend horizontally above the landing 12 inches minimum beyond the top and bottom ramps.
Correction

Codes Administration - 2006 IBC 1013.1 Guards. Guards shall be located along open-sided walking surfaces, mezzanines, industrial equipment platforms, stairways, ramps and landings which are located more than 30 inches above the floor or grade below. Guards shall be adequate in strength and attachment in accordance with Sectoin 1607.7. Guards shall also be located along glazed sides of stairways, ramps and landings that are located more than 30 inches above the floor or grade below where the glazing provided does not meet the strength and attachment requirements in Section 1607.7. In addition, guards are required at retaining walls over 30 inches above grade when walking surfaces are within ten (10) feet of the high side of the retaining wall. (As ammended by the City of Lee's Summit.)
Correction

Codes Administration - All plans submitted for review on or after July 9, 2007 shall be designed to the requirements of the 2006 International Building Code, 2006 International Mechanical Code, 2006 International Plumbing Code, 2006 International Fuel Gas Code, 2006 International Fire Code, 2005 National Electric Code and the ANSI A117.1-2003 as amended and adopted by the City of Lee's Summit.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Codes Administration - 2006 IBC 1008.1.4 - Floor elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal (2-percent slope).
Correction

Codes Administrations - 2006 IBC 1009.3 - Stair treads and risers. Stair riser heights shall be 7 inches maximum and 4 inches minimum. Stair tread depths shall be 11 inches minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. Winder treads shall have a minimum tread depth of 11 inches measured at a right angle to the tread's leading edge at a point 12 inches from the side where the treads are narrower and a minimum tread depth of 10 inches.
Correction

Codes Administration - 2006 IBC 1009.3.3 - Profile. The radius of curvature at the leading edge of the tread shall be not greater than 0.5 inch. Beveling of nosings shall not exceed 0.5 inch. Risers shall be solid and vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 degrees from the vertical. The leading edge (nosings) of treads shall project not more than 1.25 inches beyond the tread below and all projections of the leading edges shall be of uniform size, including the leading edge of the floor at the top of a flight.
Correction

Codes Administration - 2006 IBC 1012.3 - Handrail graspability. Handrails with a circular cross-section shall have an outside diameter of at least 1.25 inches and not greater than 2 inches or shall provide equivalent graspability. If the handrail is not circular, it shall have a perimeter dimension of at least 4 inches and not greater than 6.25 inches with a maximum cross-section dimension of 2.25 inches. Edges shall have a minimum radius of 0.01 inch.
Correction

Codes Administration - 2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

Codes Administration - The plans for the piers have not been provided.
Correction

Codes Administration - An electrical riser diagram was not provided with the application.
Correction

Codes Administration - Plans for the new stairs and ramp have not been provided.
Correction

Fire Department- 2006 IFC 2206.2.3 Above-ground tanks located outside, above grade. Above-ground tanks shall not be used for the storage of Class I, II or IIIA liquid motor fuels except as provided by this section. 1. Above-ground tanks used for outside, above-grade storage of Class I liquids shall be listed and labeled as protected above-ground tanks and be in accordance with Chapter 34. Such tanks shall be located in accordance with Table 2206.2.3. 2. Above-ground tanks used for above-grade storage of Class II or IIIA liquids are allowed to be protected above-ground tanks or, when approved by the fire code official, other above-ground tanks that comply with Chapter 34. Tank locations shall be in accordance with Table 2206.2.3. 3. Tanks containing fuels shall not exceed 12,000 gallons (45 420 L) in individual capacity or 48,000 gallons (181 680 L) in aggregate capacity. Installations with the maximum allowable aggregate capacity shall be separated from other such installations by not less than 100 feet (30 480 mm). 4. Tanks located at farms, construction projects, or rural areas shall comply with Section 3406.2.
Correction

Codes Administration - The plans for the stairs and ramps do not include any detail for their construction.
Correction

Codes Administration - The building plans show multiple exits but the plans provided only cover the landing, ramp and stairs on the east side of the building.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $144.40 $144.40 Paid 08/04/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Passed 08/08/2008
Correction
Resolved
08/08/2008
None FOUNDATION PIERS APPROVED PER APPROVED DRAWING.
Piers/Caissons Inspection - Commercial Passed 08/13/2008
Correction
Resolved
08/13/2008
None FOUNDATION PIERS APPROVED PER APPROVED DRAWING.
Electrical Service Inspection Failed 11/26/2008
Correction
Corrective Action Required
11/26/2008
Protect Grounding Electrode Conductor Protect bare copper from physical damage if not going to be buried. At grade below disconnects
Correction
Corrective Action Required
11/26/2008
Bonding Metal Frame Metal framed required to be bonded to either grounding electrode conductor or service equipment enclosure.
Correction
Corrective Action Required
11/26/2008
Conductor Sizing 125 amp breaker installed, #3 copper used for ungrounded conductor. Must be minimum #2 copper. NOTE: If breaker were 100 amp>only 2 #10 equipment grounds would have to be changed to #8. All Disconnects
Correction
Corrective Action Required
11/26/2008
Insulating Bushing Provide insulating bushings. Required when #4 or larger conductors are used. Bottom of 4 Disconnects
Correction
Corrective Action Required
11/26/2008
Identify Conductors 3rd from right and far right enclosure, identify equipment gounding conductor...tape green.
Correction
Corrective Action Required
11/26/2008
Equipment Bonding Jumper Equipment bonding jumper and equipment grounding conuctor shall be minimum of #6 for 125 amp disconnect. table 250.122 2005 NEC
Correction
Corrective Action Required
11/26/2008
Bonding Of Enclosures Where all lugs installed for equipment grounds, bolts used that are not of the bonding type. Paint must be stripped if this application is used for bonding enclosure. Bonding bushings required for 3rd from right and far right enclosures (no lugs). 4 Disconnects South of Building
Occupancy Inspection - Codes Commercial Not Ready 12/01/2008
Correction
Corrective Action Required
12/01/2008
None NOT READY FOR INSPECTION
Electrical Service Inspection Failed 12/01/2008
Correction
Resolved
12/01/2008
Protect Grounding Electrode Conductor
Correction
Resolved
12/01/2008
Bonding Metal Frame
Correction
Resolved
12/01/2008
Conductor Sizing SERVICE DISCONNECT BREAKERS ARE 100 AMPS, SERVICE AND FEEDER CONDUCTORS ARE #3 CU-OK
Correction
Partial Correction
12/01/2008
Insulating Bushing INSIDE ALL SUBPANELS, INSTALL BUSHINGS AT ENTRANCE FOR ALL #4 OR BIGGER CONDUCTORS
Correction
Partial Correction
12/01/2008
Identify Conductors -INSIDE ALL SUBPANELS, ID ALL EQUIPMENT GROUNDING CONDUCTORS
Correction
Corrective Action Required
12/01/2008
Equipment Bonding Jumper #8 CU BONDING JUMPERS INSTALLED FOR 100 AMP BREAKERS-OK -INSIDE GUTTER BOX NEAR THE RIGHT SIDE, HAVE THE WHOLE #8 JUMPER CONDUCTOR FULLY IN CONTACT WITH THE BONDING LUG. -CLEAN OUT DIRT/DEBRIS -AT FINAL, PLEASE LABEL ALL SERVICE DISCONNECTS
Correction
Resolved
12/01/2008
Bonding Of Enclosures SERVICE DISCONNECT ENCLOSURES ARE BONDED
Electrical Service Inspection Passed 12/02/2008
Correction
Resolved
12/02/2008
Insulating Bushing
Correction
Resolved
12/02/2008
Identify Conductors
Correction
Resolved
12/02/2008
Equipment Bonding Jumper
Occupancy Inspection - Codes Commercial Failed 01/13/2009
Correction
Corrective Action Required
01/13/2009
Receive Planning & Development Approval
Correction
Corrective Action Required
01/13/2009
EXIT SIGN DIRECTION HAVE SIGN AT SIDE OF BUILDING POINTING TO EXIT DOOR AS REQUIRED
Correction
Corrective Action Required
01/13/2009
FRONT ENTRANCE DOOR ACCESSIBILITY PROVIDE RAMP/BEVEL AT LEVEL CHANGE AT DOOR THRESHOLD.
Correction
Resolved
01/13/2009
None TCO APPROVED FOR 60 DAYS
Occupancy Inspection - Codes Commercial Failed 03/25/2009
Correction
Resolved
03/25/2009
FRONT ENTRANCE DOOR ACCESSIBILITY PROVIDE RAMP/BEVEL AT LEVEL CHANGE AT DOOR THRESHOLD.
Occupancy Inspection - Codes Commercial Failed 04/30/2009
Correction
Resolved
04/30/2009
EXIT SIGN DIRECTION
Occupancy Inspection - Codes Commercial Passed 05/04/2009
Correction
Resolved
05/04/2009
Receive Planning & Development Approval
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home