Permit Application Status

B0702189


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0702189
Building Permit - Commercial
Final Completion
LBP III LLC
NEW SHELL BUILDING
NEW SHELL BUILDING FOR A SPECULATIVE OFFICE/WAREHOUSE OCCUPANCY. THE SPACE SHALL ACCOMODATE USES FOR BOTH OFFICE SPACE AND WAREHOUSE SPACE TO BE DETERMINED AT A LATER DATE.
10/03/2007
11/21/2007
05/19/2008
05/15/2009
Locations
Contacts
KLEINFELDER, Address:7802 BARTON  
BLUE SPRINGS ELECTRICAL, Address:3402 LAKESHORE DR  
CAPITAL CONSTRUCTION SERVICES, Address:2642 NE HAGAN RD  
CLEARLINE PLUMBING, Address:14922 KNORPP RD  
DAVIDSON BROWN, Address:11301 STRANG LINE ROAD  
UNITED HEATING & COOLING, Address:301 DUCK RD  
LBP III LLC, Address:3215 NE CARNEGIE DR STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/11/2008 10/29/2010
Correction

Fire Department- 2006 IFC 901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5 Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. 901.5.1 Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 901.4.1- Required fire protection systems. Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - The project cost has not been provided.
Correction

Codes Administration - A copy of the soils report has not been provided.
Correction

Codes Administration - The possible tenant addresses for this structure are 2700, 2704, 2708, 2712, 2716 and 2720 NE Independence Ave.
Correction

Codes Administration - 2006 IBC 1007.1 - Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1015.1 or 1019.1 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress.
Correction

Codes Administration - 2006 IBC 1704.1.1 - Statement of special inspections. The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with 106.1 as a condition for permit issuance. This statement shall be in accordance with Section 1705. Exceptions: 1. A statement of special inspections is not required for structures designed and constructed in accordance with the conventional construction provisions of Section 2308. 2. The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
Correction

Codes Administration - 2006 IBC 1704.1.2 - Report Requirement. Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon by the permit applicant and the building official prior to the start of work.
Correction

Fire Department- 2006 IFC 907.1.1 -Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - Copies of the engineered steel building package were not provided at the time of permit application.
Correction

Codes Administration - I am unable to locate information relating to the water meter vault and installation.
Correction

Codes Administration - I am unable to locate information on the design of the pressurized sanitary sewer system.
Correction

Codes Administration - A complete code analysis has not been provided.
Correction

Fire Department- No comments on the revision submitted 1/04/08
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $6,298.20 $6,298.20 Paid 11/21/2007
84 Water Meters $1,326.77 $1,326.77 Paid 11/21/2007
85 Water Taps $18,582.00 $18,582.00 Paid 11/21/2007
85 Water Taps $465.00 $465.00 Paid 11/21/2007
Right of Way Permit $35.00 $35.00 Paid 11/21/2007
0120 Building Permit Fee $5,798.20 $5,798.20 Paid 11/21/2007
84 Water Meters $1,326.77 $1,326.77 Paid 11/21/2007
85 Water Taps $19,047.00 $19,047.00 Paid 11/21/2007
Right of Way Permit $35.00 $35.00 Paid 11/21/2007
0120 Building Permit Fee $500.00 $500.00 Paid 11/21/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Failed 12/20/2007
Correction
Corrective Action Required
12/20/2007
Premises Identification (IRC) PROPERTY TO BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS
Underslab Plumbing Inspection - Commercial Partial 12/20/2007
Correction
Partial Correction
12/20/2007
COMMENT 6" MAIN RUNNING NORTH-SOUTH APPROVED TO COVER
Erosion Control Inspection Residential Failed 12/20/2007
Correction
Corrective Action Required
12/20/2007
Tracking Mud, Debris STREET CLEANUP REQUIRED. 2 DAYS TO COMPLY
Correction
Resolved
12/20/2007
Erosion Control
Miscellaneous Inspection Failed 02/04/2008
Correction
Corrective Action Required
02/04/2008
Premises Identification (IRC) PROPERTY TO BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS
Water Service Inspection Partial 02/04/2008
Correction
Partial Correction
02/04/2008
None APPROVED FROM MAIN (INCLUDING METER) TO 5' FROM BUILDING
Water Service Inspection - Commercial Request Complete 2/4/2008 2/4/2008 02/04/2008
Miscellaneous Inspection Passed 04/16/2008
Correction
Resolved
04/16/2008
Premises Identification (IRC) PROPERTY TO BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS
Erosion Control Inspection Residential Passed 04/16/2008
Correction
Resolved
04/16/2008
Tracking Mud, Debris
Footing Inspection - Commercial Partial 04/16/2008
Correction
Partial Correction
04/16/2008
SEE TEXT ALL FOOTINGS APPROVED TO POUR EXCEPT: - INTERIOR PADS - LINE D, 4-7 - LINE 7 - LINE J, 5.5-7 NOTE: UFER GROUND PRESENT IN NORTH WALL ON COLUMN LINE 'A' APPROX. 5' FROM WEST CORNER
Footing Inspection - Commercial Partial 04/21/2008
Correction
Partial Correction
04/21/2008
SEE TEXT ALL FOOTINGS APPROVED TO POUR EXCEPT: - LINE D, 4-7 - LINE 7 - LINE J, 5.5-7 INTERIOR PADS APPROVED TO POUR NOTE: UFER GROUND PRESENT IN NORTH WALL ON COLUMN LINE 'A' APPROX. 5' FROM WEST CORNER
Footing Inspection - Commercial Partial 05/13/2008
Correction
Partial Correction
05/13/2008
SEE TEXT ALL FOOTINGS APPROVED TO POUR INTERIOR PADS APPROVED TO POUR. 2 PADS ON LINE 7 APPROVED NOTE: UFER GROUND PRESENT IN NORTH WALL ON COLUMN LINE 'A' APPROX. 5' FROM WEST CORNER
Underslab Plumbing Inspection - Commercial Partial 05/15/2008
Correction
Partial Correction
05/15/2008
COMMENT 6" MAIN RUNNING NORTH-SOUTH APPROVED TO COVER 6" MAIN RUNNING EAST-WEST APPROVED TO COVER (EXCEPT FLOOR DRAIN AND C.O. IN SPRINKLER ROOM)
Underslab Electrical Inspection - Commercial Partial 05/20/2008
Correction
Partial Correction
05/20/2008
None ALL APPROVED TO COVER EXCEPT IN FRONT OF DOCK BAYS
Underslab Plumbing Inspection - Commercial Partial 05/23/2008
Correction
Partial Correction
05/23/2008
COMMENT 6" MAIN RUNNING NORTH-SOUTH APPROVED TO COVER 6" MAIN RUNNING EAST-WEST APPROVED TO COVER
Underslab Electrical Inspection - Commercial Partial 05/29/2008
Correction
Partial Correction
05/29/2008
None ALL APPROVED TO COVER EXCEPT IN FRONT OF DOCK BAYS
Underground Electrical Inspection - Commercial Failed 09/19/2008
Correction
Partial Correction
09/19/2008
None -CONDUITS TO 4 S. POLES AND TO 1 SW POLE *NEED DETAIL SHEET ON PIERS OK TO BACKFILL BELOW LIGHT POLES
Underground Electrical Inspection - Commercial Request Complete 9/18/2008 9/19/2008 09/19/2008
Underground Electrical Inspection - Commercial Request Complete 9/18/2008 9/19/2008 09/19/2008
Underground Electrical Inspection - Commercial Partial 09/22/2008
Correction
Partial Correction
09/22/2008
None 5 LIGHT POLE BASES APPROVRD.4 SOUTH OF BUILDING AND 1 WEST SIDE SOUTH END. OK TO BACKFILL BELOW LIGHT POLES
Underslab Electrical Inspection - Commercial Passed 09/22/2008
Correction
Resolved
09/22/2008
None UNDER SLAB ELECT APPROVED IN FRONT OF DOCK DOORS. 7 -1INCH CANTEX FOR COMMUNICATION THROUGH NORTH WALL APP.
Underground Electrical Inspection - Commercial Request Complete 9/22/2008 9/22/2008 09/22/2008
Underground Electrical Inspection - Commercial Request Complete 9/22/2008 9/22/2008 09/22/2008
Underground Electrical Inspection - Commercial Partial 10/01/2008
Correction
Partial Correction
10/01/2008
None -UNDERGROUND CONDUITS BETWEEN LIGHT POLES FROM SE CORNER, ALONG SOUTH AND WEST SIDE TO NW CORNER -9 LIGHT POLE BASES APPROVRD-4 SOUTH AND 5 WEST OF BUILDING OK TO BACKFILL BELOW LIGHT POLES
Driveway Inspection Partial 10/01/2008
Underground Electrical Inspection - Commercial Partial 10/21/2008
Correction
Partial Correction
10/21/2008
None -UNDERGROUND CONDUITS BETWEEN LIGHT POLES FROM SE CORNER, ALONG SOUTH AND WEST SIDE TO NW CORNER, EAST CONDUITS TO CENTER NORTH (EXCEPT UNDER NE DRIVE) -9 LIGHT POLE BASES APPROVRD-4 SOUTH AND 5 WEST OF BUILDING OK TO BACKFILL BELOW LIGHT POLES
Underground Electrical Inspection - Commercial Request Complete 10/20/2008 10/21/2008 10/21/2008
Underground Electrical Inspection - Commercial Request Complete 10/20/2008 10/21/2008 10/21/2008
Underground Electrical Inspection - Commercial Partial 10/24/2008
Underground Electrical Inspection - Commercial Request Complete 10/24/2008 10/24/2008 10/24/2008
Underground Electrical Inspection - Commercial Request Complete 10/24/2008 10/24/2008 10/24/2008
Driveway Inspection Passed 10/28/2008
Underslab Electrical Inspection - Commercial Partial 10/29/2008
Correction
Partial Correction
10/29/2008
None -UNDER SLAB ELECT APPROVED IN FRONT OF DOCK DOORS. 7 -1INCH CANTEX FOR COMMUNICATION THROUGH NORTH WALL APP. APPROVED BELOW
Underground Electrical Inspection - Commercial Partial 10/29/2008
Correction
Partial Correction
10/29/2008
None -UNDERGROUND CONDUITS BETWEEN LIGHT POLES FROM SE CORNER, ALONG SOUTH AND WEST SIDE TO NW CORNER, EAST CONDUITS TO CENTER NORTH -15 LIGHT POLE BASES APPROVRD OK TO BACKFILL BELOW LIGHT POLES
Underground Electrical Inspection - Commercial Request Complete 10/28/2008 10/29/2008 10/29/2008
Underground Electrical Inspection - Commercial Request Complete 10/28/2008 10/29/2008 10/29/2008
Underground Electrical Inspection - Commercial Passed 10/31/2008
Correction
Resolved
10/31/2008
None -UNDERGROUND CONDUITS BETWEEN LIGHT POLES -16 LIGHT POLE BASES APPROVRD OK TO BACKFILL BELOW LIGHT POLES
Underground Electrical Inspection - Commercial Request Complete 10/31/2008 10/31/2008 10/31/2008
Underground Electrical Inspection - Commercial Request Complete 10/31/2008 10/31/2008 10/31/2008
Electrical Service Inspection Partial 11/04/2008
Correction
Partial Correction
11/04/2008
None 1600 AMP AND 1200 AMP SERVICES APPROVED -APPROVED FOR RELEASE OF METERS FOR HOUSEHOLD AND TOSHIBA TENANT
Gas Piping Inspection - Commercial Failed 11/21/2008
Correction
Corrective Action Required
11/21/2008
None NO PLAN ON SITE
Gas Service Inspection - Commercial Failed 11/21/2008
Correction
Corrective Action Required
11/21/2008
Gas Test Pressure (IRC) NO PRESSURE
Sidewalk Inspection Passed 11/21/2008
Gas Piping Inspection - Commercial Failed 11/25/2008
Correction
Corrective Action Required
11/25/2008
None PROVIDE 6" SUPPORTING BLOCKS UNDER GAS PIPING ROOF GAS LINE SUPPORT
Gas Service Inspection - Commercial Failed 11/25/2008
Correction
Corrective Action Required
11/25/2008
Gas Test Pressure (IRC) PRESSURE NOT HOLDING
Gas Service Inspection - Commercial Passed 11/26/2008
Correction
Resolved
11/26/2008
Gas Test Pressure (IRC) APPROVED FOR GAS RELEASE
Gas Piping Inspection - Commercial Passed 11/26/2008
Correction
Resolved
11/26/2008
None
Occupancy Inspection - Codes Commercial Failed 12/29/2008
Correction
Corrective Action Required
12/29/2008
Receive Fire Department approval
Correction
Corrective Action Required
12/29/2008
Receive Public Works Approval
Correction
Corrective Action Required
12/29/2008
Receive Planning & Development Approval
Correction
Corrective Action Required
12/29/2008
LICENSE TAX PAYMENT NO TYPE OF OCCUPANCY SHALL BE ISSUED UNTIL LICENSE TAX IS PAID
Correction
Corrective Action Required
12/29/2008
Required Inspections FOOTING NOT APPROVED. NOT ALL INTERIOR COLUMN PADS WERE INSPECTED. HAVE ENGINEER OF RECORD SEND IN LETTER FOR ALL ISSUES (SI AND FOOTING)
Water Service Inspection Passed 12/29/2008
Correction
Resolved
12/29/2008
None
Electrical Service Inspection Passed 12/29/2008
Correction
Resolved
12/29/2008
None 1600 AMP AND 1200 AMP SERVICES APPROVED -APPROVED FOR RELEASE OF METERS FOR HOUSEHOLD AND TOSHIBA TENANT
Footing Inspection - Commercial Passed 12/29/2008
Correction
Resolved
12/29/2008
SEE TEXT ALL FOOTINGS APPROVED TO POUR INTERIOR PADS APPROVED TO POUR. 2 PADS ON LINE 7 APPROVED NOTE: UFER GROUND PRESENT IN NORTH WALL ON COLUMN LINE 'A' APPROX. 5' FROM WEST CORNER
Underslab Plumbing Inspection - Commercial Passed 12/29/2008
Correction
Resolved
12/29/2008
COMMENT
Underslab Electrical Inspection - Commercial Passed 12/29/2008
Correction
Resolved
12/29/2008
None
Occupancy Inspection - Codes Commercial Failed 03/09/2009
Correction
Resolved
03/09/2009
Receive Fire Department approval
Correction
Resolved
03/09/2009
Receive Public Works Approval
Correction
Resolved
03/09/2009
Receive Planning & Development Approval
Correction
Resolved
03/09/2009
LICENSE TAX PAYMENT
Correction
Corrective Action Required
03/09/2009
Required Inspections PROVIDE SPECIAL INSPECTION REPORT
Occupancy Inspection - Codes Commercial Passed 05/14/2009
Correction
Resolved
05/14/2009
Required Inspections
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home