Permit Application Status

B0702178


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0702178
Building Permit - Commercial
Certificate of Occupancy
TRD REAL ESTATE LLC
NEW COMMERCIAL
RELOCATION OF EXISTING CAR DEALERSHIP AND SERVICE CENTER DUE TO THE RELOCATION OF BLUE PARKWAY. PART OF THE SUMMIT FAIR PROJECT.
10/02/2007
11/26/2007
04/25/2010
01/13/2010
Locations
Contacts
ROSE CONSTRUCTION COMPANY INC, Address:1805 E 123RD ST  
ROSE CONSTRUCTION CO., INC., Address:ATTN: CHRIS HERRE  
BOB D CAMPBELL & CO INC, Address:4338 BELLEVIEW  
HEARTLAND PLUMBING INC, Address:800 S CREEKSIDE DR  
HERITAGE ELECTRIC, LLC., Address:1802 E 123RD STREET  
METRO AIR CONDITIONING COMPANY, Address:10035 LACKMAN RD  
TRD REAL ESTATE LLC, Address:607 NW BLUE PARKWAY  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/19/2008 10/29/2010
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - Plans for the pre-cast panels have not been provided.
Correction

Codes Administration - Plans for the site utilities, sanitary and water, have not been provided to the Codes Administration Department for review and approval.
Correction

Codes Administration - The type of fire automatic sprinkler system being installed has not been indicated on the plans.
Correction

Codes Administration - An exiting plan has not been provided for the project.
Correction

Codes Administration - Details on the parts room storage system have not been provided.
Correction

Codes Administration - The finish schedule indicates that the frp installed in the restrooms is fire resistant panels.
Correction

Codes Administration - Specifications for the electrical system have not been provided.
Correction

Codes Administration - Note 12 of the General Plumbing Notes refers to the Olathe Waste Water Department.
Correction

Fire Department- 2006 IFC 2211.2.2 - Waste oil, motor oil and other Class IIIB liquids. Waste oil, motor oil and other Class IIIB liquids shall be stored in approved tanks or containers, which are allowed to be stored and dispensed from inside repair garages.
Correction

Fire Department- 2006 IFC 2211.7 Repair garages for vehicles fueled by lighter-than-air fuels. Repair garages for the conversion and repair of vehicles which use CNG, liquefied natural gas (LNG), hydrogen or other lighter-than-air motor fuels shall be in accordance with Sections 2211.7 through 2211.7.2.3 in addition to the other requirements of Section 2211.
Correction

Fire Departemnt- 2006 IFC 906.2 -General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Correction

Fire Department- The 2006 International Fire Code with local amendments is the adopted fire code for the City of Lee's Summit .
Correction

Fire Department- 2006 IFC 907.1.1 Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 2006 IFC 901.5 Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. 901.5.1 Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 901.2 -Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 407.5 Hazardous Materials Inventory Statement. Where required by the fire code official, each application for a permit shall include a Hazardous Materials Inventory Statement (HMIS) in accordance with Section 2701.5.2.
Correction

Fire Department- 2006 IFC 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. 506.1.1 Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official.
Correction

Fire Department- 2006 IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 1011.1- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Fire Department- 2006 IFC 1006.2 -Illumination level. The means of egress illumination level shall not be less than 1 foot-candle (11 lux) at the walking surface level. 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Correction

Fire Department- 2006 IFC 903.3.7 Fire department connections.The location of fire department connections shall be approved by the fire code official. Connections shall be a 4' Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the fire code official.
Correction

Fire Department- 2006 IFC 508.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Correction

Codes Administration - 2006 IBC 1704.1.2 - Report Requirement. Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon by the permit applicant and the building official prior to the start of work.
Correction

Codes Administration - 2006 IBC 1704.1.1 - Statement of special inspections. The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with 106.1 as a condition for permit issuance. This statement shall be in accordance with Section 1705. Exceptions: 1. A statement of special inspections is not required for structures designed and constructed in accordance with the conventional construction provisions of Section 2308. 2. The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
Correction

Codes Administration - 2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Correction

Codes Administration - 2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible.
Correction

Codes Administration - 2006 IBC 1015.1 - Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exist: 1. The occupant load of the space exceeds the values in Table 1015.1. 2. The common path of egress travel exceeds the limitations of Section 1014.3. 3. Where required by Sections 1015.3, 1015.4 and 1015.5. Exception: Group I-2 occupancies shall comply with Section 1014.2.2.
Correction

Codes Administrations - 2006 IBC 1009.3 - Stair treads and risers. Stair riser heights shall be 7 inches maximum and 4 inches minimum. Stair tread depths shall be 11 inches minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. Winder treads shall have a minimum tread depth of 11 inches measured at a right angle to the tread's leading edge at a point 12 inches from the side where the treads are narrower and a minimum tread depth of 10 inches.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - The civil plans do not indicate the size of the water meter to be installed.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

Codes Administration - 2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $13,894.89 $13,894.89 Paid 11/26/2007
89 Sewer Tap Fees $660.00 $660.00 Paid 11/26/2007
84 Water Meters $1,325.93 $1,325.93 Paid 07/17/2008
Right of Way Permit $35.00 $35.00 Paid 07/17/2008
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 04/21/2008
Correction
Partial Correction
04/21/2008
WALL FRAMING + IN-WALL SYSTEMS WALLS @ MEZZANINE; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Plumbing Inspection - Commercial Partial 04/21/2008
Correction
Partial Correction
04/21/2008
DWV PLUMBING IN CMU WALLS TWO 1-1/2" PVC DRAINS/VENTS @ 138 N WALL; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Failed 05/21/2008
Correction
Partial Correction
05/21/2008
WALL FRAMING + IN-WALL SYSTEMS WALLS @ MEZZANINE; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Corrective Action Required
05/21/2008
CONNECTIONS OF LIGHT GUAGE FRAMING WITHIN WIDTH OF WALL OPENINGS EXCEPT @ TOP SLIP TRACKS SCREW ALL CONNECTIONS FULL HEIGHT OF WALL
Correction
Corrective Action Required
05/21/2008
PROTECTION OF PVC PIPING FROM PENETRATION IPC 305.8: INSTALL SHIELD PLATES AT STUDS / TRACKS. WHERE < 1-1/2" FROM FACE OF FRAMING TO RECEIVE GWB
Correction
Corrective Action Required
05/21/2008
ELECTRICAL BOX STAND-OFFS EXTEND TO MAKE CONTACT WHERE WALL GAPS OCCUR
All Rough Inspection - Commercial Partial 05/23/2008
Correction
Partial Correction
05/23/2008
WALL FRAMING + IN-WALL SYSTEMS WALLS @ MEZZANINE; 1ST FLOOR WALLS EXCEPT @ TWO ELEVATED ROOMS; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Resolved
05/23/2008
CONNECTIONS OF LIGHT GUAGE FRAMING WITHIN WIDTH OF WALL OPENINGS
Correction
Resolved
05/23/2008
PROTECTION OF PVC PIPING FROM PENETRATION
Correction
Resolved
05/23/2008
ELECTRICAL BOX STAND-OFFS
All Rough Inspection - Commercial Partial 06/09/2008
Correction
Partial Correction
06/09/2008
WALL FRAMING + IN-WALL SYSTEMS WALLS @ MEZZANINE; 1ST FLOOR WALLS INCLUDING 101; 103 S & E; 107 OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 06/16/2008
Correction
Partial Correction
06/16/2008
WALL FRAMING + IN-WALL SYSTEMS WALLS @ MEZZANINE; 1ST FLOOR WALLS INCLUDING 101; 103 S & E; 107; STAIRWELL 124; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rated Assembly Inspection Partial 06/19/2008
Correction
Partial Correction
06/19/2008
RATED WALL SURROUNDING STAIRWELL 124 1ST LAYER 5/8" TYPE X GWB; OK TO COVER WHEN READY FOLLOWING PORTIONS:
Rated Assembly Inspection Passed 06/23/2008
Correction
Resolved
06/23/2008
RATED WALL SURROUNDING STAIRWELL 124 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 5/8" TYPE X GWB; OK TO COVER WHEN READY FOLLOWING PORTIONS:
Sewer Service Inspection Partial 06/25/2008
Correction
Partial Correction
06/25/2008
SANITARY SEWER SERVICE INSTALLATION FROM CONN TO TRENCH DRAIN @ CAR WASH EAST TO SAND/OIL INTERCEPTOR; FROM (BB)/(7) EAST TO CONNECTION TO MAIN: OK TO COVER WHEN READY FOLLOWING SEGMENTS:
Sewer Service Inspection - Commercial Request Complete 6/25/2008 6/25/2008 06/25/2008
Sewer Service Inspection Passed 06/26/2008
Correction
Resolved
06/26/2008
SANITARY SEWER SERVICE INSTALLATION FROM CONN TO TRENCH DRAIN @ CAR WASH EAST TO SAND/OIL INTERCEPTOR; FROM (BB)/(7) EAST TO CONNECTION TO MAIN; SAND/OIL INTERCEPTOR (M.H. RINGS + COVERS YET TO BE SET) + COMPLETION OF ABS & PVC PIPING TO & FROM INTERCEPTOR OK TO COVER WHEN READY FOLLOWING SEGMENTS:
Sewer Service Inspection - Commercial Request Complete 6/26/2008 6/26/2008 06/26/2008
Gas Service Inspection - Commercial Passed 07/09/2008
Correction
Resolved
07/09/2008
TEST PRESSURE LEVEL RELEASE GAS SERVICE HELD STEADY AT >= 10 PSI FOR >=30 MIN
Gas Piping Inspection - Commercial Failed 07/09/2008
Correction
Corrective Action Required
07/09/2008
SUPPORT OF RIGID STEEL PIPING @ ROOFTOP PER TABLE @ IFGC 415 SOME HORIZONTAL RUNS SPACING > IFGC MAX
Water Service Inspection Partial 07/11/2008
Correction
Partial Correction
07/11/2008
None 2 INCH COPPER FROM NORTH SIDE OF THE BUILDING TO EAST SIDE OF BACKFLOW PIT
Water Service Inspection Partial 07/11/2008
Correction
Partial Correction
07/11/2008
None 2 INCH COPPER FROM BACKFLOW PIT TO METER LOCATION.
Correction
Partial Correction
07/11/2008
None 2 INCH COPPER FROM NORTH SIDE OF THE BUILDING TO EAST SIDE OF BACKFLOW PIT
Underground Electrical Inspection - Commercial Partial 07/11/2008
Correction
Partial Correction
07/11/2008
None -UNDERGROUND ELECTRICAL FROM TRANSFORMER PAD TO CT CABINET -ABOUT 20 FT OF CONDUITS TO LIGHT POLES FROM SERVICE LOCATION OK TO BACKFILL WHERE OK
Water Service Inspection - Commercial Request Complete 7/11/2008 7/11/2008 07/11/2008
Water Service Inspection - Commercial Request Complete 7/11/2008 7/11/2008 07/11/2008
Above Ceiling Inspection Failed 07/30/2008
Correction
Corrective Action Required
07/30/2008
SUPPORT LIGHT FIXTURES MAIN FL: FRONT OFFICES, SOUTH ROOM
Correction
Corrective Action Required
07/30/2008
OVERFILLED BOXES 2ND FL
Electrical Service Inspection Failed 07/30/2008
Correction
Corrective Action Required
07/30/2008
EQUIPMENT GROUNDING CONDUCTORS EACH PARALLEL EGC SHALL BE SIZED PER T250.122 BASED ON 400 AMP BREAKER #1 AL OR #3 CU REQUIRED PARALLEL TO 400 AMP SUB
Correction
Corrective Action Required
07/30/2008
GROUNDING OF TRANSFORMERS 250.30- GROUNDING ELECTRODE CONDUCTORS AND SYSTEM BONDING JUMPERS SHALL BE SIZE PER 250.66 BASED ON DERIVED PHASED CONDUCTORS ALL TRANSFORMERS
Correction
Corrective Action Required
07/30/2008
GROUNDING ELECTRODE CONDUCTORS NOT CONTINUOUS 250.64 INSIDE MAIN DISCONNECT
Correction
Corrective Action Required
07/30/2008
SERVICE SIZE UPGRADE NOT ON PLAN 800 AMP SERVICE IS UPGRADED TO 1000 AMP SERVICE. DESIGNER TO SUBMIT UPDATED PLAN TO CITY FOR APPROVAL AND HAVE PLAN AVAILABLE FOR NEXT INSPECTION
Electrical Service Inspection Passed 08/01/2008
Correction
Resolved
08/01/2008
EQUIPMENT GROUNDING CONDUCTORS
Correction
Resolved
08/01/2008
GROUNDING OF TRANSFORMERS
Correction
Resolved
08/01/2008
GROUNDING ELECTRODE CONDUCTORS NOT CONTINUOUS
Correction
Resolved
08/01/2008
SERVICE SIZE UPGRADE NOT ON PLAN APPROVED FOR RELEASE OF 1000 AMP SERVICE
Above Ceiling Inspection Passed 08/01/2008
Correction
Resolved
08/01/2008
SUPPORT LIGHT FIXTURES
Correction
Resolved
08/01/2008
OVERFILLED BOXES
Occupancy Inspection - Codes Commercial Not Ready 08/08/2008
Correction
Corrective Action Required
08/08/2008
PAYMENT OF EXCISE TAX
Correction
Corrective Action Required
08/08/2008
Receive Fire Department approval
Correction
Corrective Action Required
08/08/2008
Receive Planning & Development Approval
Correction
Corrective Action Required
08/08/2008
Receive Public Works Approval
Correction
Corrective Action Required
08/08/2008
Receive Water Utilities Approval
Correction
Corrective Action Required
08/08/2008
ROOFTOP INSPECTION RECOMMEND PAINTING OF ROOFTOP GAS PIPING ELECTRICAL RECEPTACLES NOT PROTECTED PER NEC 406.8 SEAL GAS LINE ENTRIES TO RTU's OPEN NEUTRAL AT RECEPT @ RTU-10 CLOSE/SECURE RTU ACCESS PANELS CLEAR/CLEAN OF MATERIAL& DEBRIS; + ISSUES BELOW:
Correction
Corrective Action Required
08/08/2008
VERTICAL GRAB BAR AT RESTROOM SIDE WALL ANSI/ICC 604.5.1 NOT INSTALLED
Correction
Corrective Action Required
08/08/2008
WATER CLOSET FLUSH HANDLE PER ADA / ANSI 604.6 NOT AT FREE SIDE OF TANK EXAMPLE: 202
Correction
Corrective Action Required
08/08/2008
SPRINKLER FIRE PROTECTION ESCUTCHEONS SOME NOT IN PLACE EXAMPLE: 208; SALES EAST
Correction
Corrective Action Required
08/08/2008
REQUIRED HANDRAILS AT COMMERCIAL STAIR IBC 1009.10 REQUIRED BOTH SIDES OF ST STAIR 124 + STAIR TO 107
Correction
Corrective Action Required
08/08/2008
STAIR TREAD / RISER / GUARD TRIANGULAR OPENINGS OPEN SIDE(S) OF STAIRWAY >= 6" SPHERE
Correction
Corrective Action Required
08/08/2008
SET-BACK OF ELECTRICAL RECEPTACLE/SWITCH BOXES IN WALL NEC 370-20: SEE RESTROOMS BOXES > 1/4" FROM NON-COM WALL SURFACE
Correction
Corrective Action Required
08/08/2008
FIRE-RATED DOORS / FRAMES TO BE CHECKED
Correction
Corrective Action Required
08/08/2008
BACKFLOW PREVENTION AT WATER-SUPPLIED EQUIPMENT ICE-MAKERS; COFFEE MAKERS;.. TO BE INSPECTED WHEN INSTALLED
Correction
Corrective Action Required
08/08/2008
STATE OF COMPLETION OF FINAL INSPECTION INITIATED 8/8/08 TO BE CONTINUED 8/12
Miscellaneous Inspection Not Ready 08/08/2008
Correction
Corrective Action Required
08/08/2008
READINESS FOR FINAL INSPECTION
Underground Electrical Inspection - Commercial Partial 08/12/2008
Correction
Partial Correction
08/12/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 24-29; 44; CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Occupancy Inspection - Codes Commercial Failed 08/12/2008
Correction
Partial Correction
08/12/2008
Receive Fire Department approval CONTACT CPT JOE DIR PHONE 816-969-1313
Correction
Partial Correction
08/12/2008
Receive Planning & Development Approval CONTACT CHRISTINA PHONE 816-969-1600
Correction
Partial Correction
08/12/2008
Receive Public Works Approval CONTACT BRIAN BIRD
Correction
Partial Correction
08/12/2008
Receive Water Utilities Approval CONTACT BEN HASKAMP PHONE 816-969-1930
Correction
Resolved
08/12/2008
VERTICAL GRAB BAR AT RESTROOM SIDE WALL
Correction
Resolved
08/12/2008
WATER CLOSET FLUSH HANDLE ALLOWED AS EXCEPTION TO ADA / ANSI 604.6 DUE TO ROUGH-IN DIMENSIONS NOT AT FREE SIDE OF TANK RESTROOM 202
Correction
Resolved
08/12/2008
SPRINKLER FIRE PROTECTION ESCUTCHEONS
Correction
Partial Correction
08/12/2008
REQUIRED HANDRAILS AT COMMERCIAL STAIR IBC 1009.10 -- IN PROGRESS REQUIRED BOTH SIDES OF ST STAIR 124 + STAIR TO 107
Correction
Corrective Action Required
08/12/2008
STAIR TREAD / RISER / GUARD TRIANGULAR OPENINGS OPEN SIDE OF STAIR TO 107 >= 6" SPHERE
Correction
Resolved
08/12/2008
SET-BACK OF ELECTRICAL RECEPTACLE/SWITCH BOXES IN WALL
Correction
Resolved
08/12/2008
FIRE-RATED DOORS / FRAMES
Correction
Corrective Action Required
08/12/2008
BACKFLOW PREVENTION AT WATER-SUPPLIED EQUIPMENT ICE-MAKERS; COFFEE MAKERS;... TO BE DETERMINED TO BE INSPECTED WHEN INSTALLED
Correction
Partial Correction
08/12/2008
STATE OF COMPLETION OF FINAL INSPECTION CA COMPLETED 8/12/08 PW & P&D IN PROGRESS
Correction
Partial Correction
08/12/2008
LABELING OF ELECTRICAL EQUIPMENT IN PROGRESS
Correction
Corrective Action Required
08/12/2008
TEMPORARY DROP-OFF'S @ EXTERIOR DOORS UNTIL EXTERIOR WORK IS COMPLETED AND DROP-OFF'S ARE ELIMINATED DOORS 45-P; 45-Q RENDER IMPASSABLE
Underground Electrical Inspection - Commercial Request Complete 8/12/2008 8/12/2008 08/12/2008
Miscellaneous Inspection Partial 08/13/2008
Correction
Partial Correction
08/13/2008
READINESS FOR FINAL INSPECTION
Occupancy Inspection - Codes Commercial Failed 08/13/2008
Correction
Resolved
08/13/2008
PAYMENT OF EXCISE TAX PAID 8/12/08
Occupancy Inspection - Codes Commercial Failed 08/14/2008
Correction
Resolved
08/14/2008
TEMPORARY DROP-OFF'S @ EXTERIOR DOORS UNTIL EXTERIOR WORK IS COMPLETED AND DROP-OFF'S ARE ELIMINATED DOORS 45-P; 45-Q RENDERED IMPASSABLE
Underground Electrical Inspection - Commercial Partial 08/22/2008
Correction
Partial Correction
08/22/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 24-29; 44; NOTE: POLE BASES NUMBERED 13-17; 49-52 WERE CONSTRUCTED WITHOUT INSPECTION NOR APPROVAL. CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Partial 08/27/2008
Correction
Resolved
08/27/2008
None -UNDERGROUND ELECTRICAL FROM TRANSFORMER PAD TO CT CABINET -ABOUT 20 FT OF CONDUITS TO LIGHT POLES FROM SERVICE LOCATION OK TO BACKFILL WHERE OK
Correction
Partial Correction
08/27/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 24-29; 44; 19; 30-33 INCLUDING BURIED CONDUIT BETWEEN; NOTES: 1) POLE BASES NUMBERED 13-17; 49-52 WERE CONSTRUCTED WITHOUT INSPECTION NOR APPROVAL. 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Occupancy Inspection - Codes Commercial Failed 08/27/2008
Correction
Partial Correction
08/27/2008
Receive Fire Department approval TO RESOLVE REMAINING ISSUES CONTACT CPT JOE DIR PHONE 816-969-1313
Correction
Partial Correction
08/27/2008
STATE OF COMPLETION OF FINAL INSPECTION AWAITING DEMO OF OLD BUILDING + COMPLETION OF FINISH SITEWORK NEW BUILDING SUBSTANTIALLY COMPLETED
Correction
Resolved
08/27/2008
LABELING OF ELECTRICAL EQUIPMENT
Underground Electrical Inspection - Commercial Request Complete 8/26/2008 8/27/2008 08/27/2008
Underground Electrical Inspection - Commercial Partial 09/02/2008
Correction
Partial Correction
09/02/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 24-29; 44; 19; 30-33; 35; 36 INCLUDING BURIED CONDUIT BETWEEN; NOTES: 1) POLE BASES NUMBERED 13-17; 49-52 WERE CONSTRUCTED WITHOUT INSPECTION NOR APPROVAL. 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 9/2/2008 9/2/2008 09/02/2008
Underground Electrical Inspection - Commercial Partial 09/25/2008
Correction
Partial Correction
09/25/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 19; 24-33; 34; 35; 36 44 INCLUDING BURIED CONDUIT BETWEEN; NOTES: 1) POLE BASES NUMBERED 13-17; 49-52 WERE CONSTRUCTED WITHOUT INSPECTION NOR APPROVAL. 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 9/25/2008 9/25/2008 09/25/2008
Underground Electrical Inspection - Commercial Partial 09/29/2008
Correction
Partial Correction
09/29/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 19; 24-33; 34; 35; 36; 34; 38; 39; 40; 44; -- INCLUDING BURIED CONDUIT TO/FROM CONDUIT BETWEEN 50<>49<>12; 45<>46<>48; 46<>43<>42<>41; 40<>39<>38<>37; 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Correction
Resolved
09/29/2008
INSPECTION INFORMATION FOR RECORD POLE BASES NUMBERED 13-17; 49-52 -- AND BURIED CONDUIT CONNECTING BASES POLE BASES CONSTRUCTED W/O INSPECTION / APPROVAL
Underground Electrical Inspection - Commercial Request Complete 9/26/2008 9/29/2008 09/29/2008
Underground Electrical Inspection - Commercial Request Complete 9/29/2008 9/29/2008 09/29/2008
Underground Electrical Inspection - Commercial Partial 09/30/2008
Correction
Partial Correction
09/30/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 19; 24-33; 34; 35; 36; 34; 38; 39; 40; 44; 41;42; 43; 45; 46 -- INCLUDING BURIED CONDUIT TO/FROM CONDUIT BETWEEN 50<>49<>12; 45<>46<>48; 46<>43<>42<>41; 40<>39<>38<>37; 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 9/30/2008 9/30/2008 09/30/2008
Underground Electrical Inspection - Commercial Partial 10/01/2008
Correction
Partial Correction
10/01/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 19; 24-36; 38-46 -- INCLUDING BURIED CONDUIT TO/FROM CONDUIT BETWEEN 50<>49<>12; 45<>46<>48; 46<>43<>42<>41; 40<>39<>38<>37; 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 10/1/2008 10/1/2008 10/01/2008
Underground Electrical Inspection - Commercial Partial 10/09/2008
Correction
Partial Correction
10/09/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 1; 19; 24-36; 36<>37; 38-46; 47<>48 -- INCLUDING BURIED CONDUIT TO/FROM CONDUIT BETWEEN 50<>49<>12 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 10/8/2008 10/9/2008 10/09/2008
Underground Electrical Inspection - Commercial Partial 10/10/2008
Correction
Partial Correction
10/10/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 1; 10<>11<>12; 19; 24-36; 36<>37; 38-46; 47<>48 -- INCLUDING BURIED CONDUIT TO/FROM CONDUIT BETWEEN 50<>49<>12 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 10/10/2008 10/10/2008 10/10/2008
Underground Electrical Inspection - Commercial Partial 10/29/2008
Correction
Partial Correction
10/29/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 1; 10<>11<>12; 19; 24-36; 36<>37; 38-46; 47<>48 -- INCLUDING BURIED CONDUIT TO/FROM CONDUIT BETWEEN 50<>49<>12; 30 TO 1/2WAY NE TOWARD 23 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 10/29/2008 10/29/2008 10/29/2008
Miscellaneous Inspection Passed 11/06/2008
Correction
Resolved
11/06/2008
READINESS FOR FINAL INSPECTION
Underground Electrical Inspection - Commercial Partial 11/21/2008
Correction
Partial Correction
11/21/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES POLE #'s: 1; 1<CONDUIT>2; 10<>11<>12; 19; 20<>21<>22<>23; 24-36; 36<>37; 38-46; 47<>48 -- INCLUDING BURIED CONDUIT TO/FROM CONDUIT BETWEEN 50<>49<>12; 30 TO 1/2WAY NE TOWARD 23 2) #19 DELETED CLEAN/PUMP BOTTOMS OK TO POUR WHEN READY
Underground Electrical Inspection - Commercial Request Complete 11/21/2008 11/21/2008 11/21/2008
Underground Electrical Inspection - Commercial Partial 12/01/2008
Correction
Partial Correction
12/01/2008
SCREW-IN LIGHT POLE BASES TO CHECK PROCEDURE ALONG SE RETAINING WALL ONE INSTALLATION OBSERVED
Underground Electrical Inspection - Commercial Request Complete 12/1/2008 12/1/2008 12/01/2008
Underground Electrical Inspection - Commercial Passed 12/02/2008
Correction
Resolved
12/02/2008
None
Correction
Resolved
12/02/2008
PREPARATION FOR POUR OF CONCRETE LIGHT POLE BASES
Correction
Resolved
12/02/2008
SCREW-IN LIGHT POLE BASES CONDUIT PLACED IN TRENCH CONNECTING BASES #2 THRU #9; GROUND RODS LAID IN TRENCH @ #2 TRU #8 DUE TO DIFFICULTY OF DRIVING THROUGH RETAINING WALL GRANULAR BACKFILL -- OK TO COVER WHEN READY. ALONG SE RETAINING WALL BASES SCREWED INTO PLACE+
Underground Electrical Inspection - Commercial Request Complete 12/2/2008 12/2/2008 12/02/2008
Underground Electrical Inspection - Commercial Request Complete 12/2/2008 12/2/2008 12/02/2008
Occupancy Inspection - Codes Commercial Failed 12/10/2008
Correction
Resolved
12/10/2008
Receive Fire Department approval PER CPT JOE DIR 12/10/08
Correction
Partial Correction
12/10/2008
Receive Public Works Approval COORDINATE W/ BRIAN BIRD
Correction
Resolved
12/10/2008
Receive Water Utilities Approval PER BEN HASKAMP 12/10/08
Correction
Resolved
12/10/2008
ROOFTOP INSPECTION
Correction
Resolved
12/10/2008
WATER CLOSET FLUSH HANDLE ALLOWED AS EXCEPTION TO ADA / ANSI 604.6 DUE TO ROUGH-IN DIMENSIONS NOT AT FREE SIDE OF TANK RESTROOM 202
Correction
Resolved
12/10/2008
REQUIRED HANDRAILS AT COMMERCIAL STAIR
Correction
Resolved
12/10/2008
STAIR TREAD / RISER / GUARD TRIANGULAR OPENINGS
Correction
Resolved
12/10/2008
BACKFLOW PREVENTION AT WATER-SUPPLIED EQUIPMENT
Correction
Resolved
12/10/2008
STATE OF COMPLETION OF FINAL INSPECTION SEE TEMPORARY OCCUPANCY
Correction
Resolved
12/10/2008
TEMPORARY DROP-OFF'S @ EXTERIOR DOORS
Water Service Inspection Passed 12/10/2008
Correction
Resolved
12/10/2008
None
Correction
Resolved
12/10/2008
None
All Rough Inspection - Commercial Passed 12/10/2008
Correction
Resolved
12/10/2008
WALL FRAMING + IN-WALL SYSTEMS
Rough Plumbing Inspection - Commercial Passed 12/10/2008
Correction
Resolved
12/10/2008
DWV PLUMBING IN CMU WALLS
Gas Piping Inspection - Commercial Passed 12/10/2008
Correction
Resolved
12/10/2008
SUPPORT OF RIGID STEEL PIPING @ ROOFTOP
Occupancy Inspection - Codes Commercial Failed 05/01/2009
Occupancy Inspection - Codes Commercial Failed 06/24/2009
Occupancy Inspection - Codes Commercial Failed 10/28/2009
Correction
Resolved
10/28/2009
Receive Public Works Approval PER MIKE ANDERSON 10/19/09 NO REMAINING ISSUES THAT AFFECT THIS PERMIT
Occupancy Inspection - Codes Commercial Failed 10/28/2009
Occupancy Inspection - Codes Commercial Passed 01/12/2010
Correction
Resolved
01/12/2010
Receive Planning & Development Approval PER CHRISTINA ALEXANDER CONFIRMED 1/12/2010
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home