Summary
B0702166
Building Permit - Commercial
Certificate of Occupancy
DOUGLAS STATION SHOPPING CENTER LLC
CHANGE OF TENANT
THAISPICE RESTAURANT TENANT FINISH
09/28/2007
10/12/2007
05/12/2008
11/19/2007
Locations
Contacts
STEVE WILLEY CONSTRUCTION, Address:1808 NE PEREGRIN CIR  
JACK MCINTOSH AND COMPANY, Address:4316 WASHINGTON AVE  
ACCU-PLUMBING, Address:PO BOX 683  
BUTTERWORTH ELECTRIC SERVICE, Address:4001 N KOGER RD  
DOUGLAS STATION SHOPPING CENTER LLC, Address:1725 NE RICE RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/07/2008 10/29/2010
Correction

Fire Department- 2006 IFC 901.4 -Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
Correction

Fire Department- 2006 IFC 904.4 Inspection and testing. Automatic fire-extinguishing systems shall be inspected and tested in accordance with the provisions of this section prior to acceptance. 904.4.1 Inspection. Prior to conducting final acceptance tests, the following items shall be inspected: 1. Hazard specification for consistency with design hazard. 2. Type, location and spacing of automatic- and manual-initiating devices. 3. Size, placement and position of nozzles or discharge orifices. 4. Location and identification of audible and visible alarm devices. 5. Identification of devices with proper designations. 6. Operating instructions.
Correction

Fire Department- 2006 IFC 904.11.5 -Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Correction

Fire Department- All existing exit and emergency lighting shall be operable.
Correction

Fire Department- 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $102.13 $102.13 Paid 10/12/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Failed 10/19/2007
Correction
Corrective Action Required
10/19/2007
ELECTRICAL BOX LOW ON WING WALL NEC 370-20: INSTALL MUD RING TO WITHIN 1/4" FROM FACE OF WALL SETBACK > 1/4" NON-COM WALL SURFACE
Correction
Corrective Action Required
10/19/2007
ELECTRICAL SYSTEMS ABOVE CEILING NOT READY FOR INSPECTION SUPPORT MC CABLE PER NEC
Above Ceiling Inspection Not Ready 10/19/2007
Correction
Corrective Action Required
10/19/2007
ABOVE-CEILING SYSTEMS LEAVE REMOVED CEILING TILE OUT UNTIL APPROVED NOT READY FOR INSPECTION SUBJECT TO APPROVAL
Rough Plumbing Inspection - Commercial Failed 10/19/2007
Correction
Corrective Action Required
10/19/2007
PROTECTION OF COPPER PIPING INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL AT PENETRATIONS OF STEEL FRAMING MEMBERS
Correction
Corrective Action Required
10/19/2007
VENTING OF PLUMBING @ KITCHEN N.E. AIR ADMITTANCE VALVES NOT APPROVED NOT EXTENDEDTO ATMOSPHERE
Correction
Corrective Action Required
10/19/2007
WATER PIPING ABOVE CEILING SUPPORT, ISOLATION, INSULATION NOT COMPLETED NOT READY FOR INSPECTION
Underslab Plumbing Inspection - Commercial Not Ready 10/19/2007
Correction
Corrective Action Required
10/19/2007
DRAIN FROM CHINESE RANGE MAY REQUIRE GREASE TRAP PROVIDE DOCUMENTATION
Rough Mechanical Inspection - Commercial Not Ready 10/19/2007
Correction
Corrective Action Required
10/19/2007
HVAC SYSTEM ABOVE CEILING NOT READY FOR INSPECTION DUCTWORK DISCONTINUOUS
Rough Electrical Inspection - Commercial Partial 10/24/2007
Correction
Partial Correction
10/24/2007
ELECTRICAL BOX LOW ON WING WALL
Correction
Corrective Action Required
10/24/2007
ELECTRICAL SYSTEMS ABOVE CEILING NOT READY FOR INSPECTION LADDER REQUIRED
Above Ceiling Inspection Not Ready 10/24/2007
Correction
Corrective Action Required
10/24/2007
ABOVE-CEILING SYSTEMS LADDER NOT ON SITE NOT READY FOR INSPECTION SUBJECT TO APPROVAL
Rough Mechanical Inspection - Commercial Not Ready 10/24/2007
Correction
Corrective Action Required
10/24/2007
HVAC SYSTEM ABOVE CEILING NOT READY FOR INSPECTION LADDER REQUIRED
Underslab Plumbing Inspection - Commercial Passed 10/24/2007
Correction
Resolved
10/24/2007
DRAIN FROM CHINESE RANGE
Rough Plumbing Inspection - Commercial Partial 10/24/2007
Correction
Partial Correction
10/24/2007
VENTING OF PLUMBING @ KITCHEN N.E. REQUIRES LADDER FOR INSPECTION OK BELOW CEILING ABOVE CEILING NOT READY
Correction
Corrective Action Required
10/24/2007
WATER PIPING ABOVE CEILING NOT READY FOR INSPECTION REQUIRES LADDER
Above Ceiling Inspection Passed 10/25/2007
Correction
Resolved
10/25/2007
ABOVE-CEILING SYSTEMS 1) LEAVE NO UNUSED MATERIAL OR DEBRIS ABOVE CEILING 2) CLEAR/CLEAN TOP OF EXHAUST HOOD, AND SECURE ALL ELECTRICAL WIRING AT LEAST 18" ABOVE CEILING GRID AND HOOD BODY. OK TO COVER WHEN READY AFTER FOLLOWING COMPLETED
Occupancy Inspection - Codes Commercial Failed 11/14/2007
Correction
Resolved
11/14/2007
Receive Fire Department approval PER JOE DIR 11/14/07
Correction
Corrective Action Required
11/14/2007
SMOKE CAPTURE TEST ON KITCHEN HOOD TO BE WITNESSED
Correction
Corrective Action Required
11/14/2007
BACKFLOW PROTECTION AT CARBONATED BEVERAGE DISPENSER NOT FOUND IN PLACE REQUIRED BY IPC 608
Correction
Corrective Action Required
11/14/2007
UL LISTING OF LIGHTED SIGNS PER NEC 600.3 NO UL LABEL FOUND AS INDICATION OF LISTING
Correction
Corrective Action Required
11/14/2007
ELEC TRICAL BOX FACE PLATES BEHIND COOKING EQUIPMENT USE METAL PLATES RATHER THAN PLASTIC
Hood/Duct Inspection Passed 11/15/2007
Correction
Resolved
11/15/2007
SMOKE CAPTURE TEST WITNESSED 11/15/07 PER IMC 507.16
Rough Plumbing Inspection - Commercial Passed 11/15/2007
Correction
Resolved
11/15/2007
PROTECTION OF COPPER PIPING
Correction
Resolved
11/15/2007
VENTING OF PLUMBING @ KITCHEN N.E.
Correction
Resolved
11/15/2007
WATER PIPING ABOVE CEILING
Rough Mechanical Inspection - Commercial Passed 11/15/2007
Correction
Resolved
11/15/2007
HVAC SYSTEM ABOVE CEILING
Rough Electrical Inspection - Commercial Passed 11/15/2007
Correction
Resolved
11/15/2007
ELECTRICAL BOX LOW ON WING WALL
Correction
Resolved
11/15/2007
ELECTRICAL SYSTEMS ABOVE CEILING
Occupancy Inspection - Codes Commercial Passed 11/15/2007
Correction
Resolved
11/15/2007
SMOKE CAPTURE TEST ON KITCHEN HOOD
Correction
Resolved
11/15/2007
BACKFLOW PROTECTION AT CARBONATED BEVERAGE DISPENSER
Correction
Resolved
11/15/2007
UL LISTING OF LIGHTED SIGNS
Correction
Resolved
11/15/2007
ELEC TRICAL BOX FACE PLATES BEHIND COOKING EQUIPMENT
Documents & Images
Date Uploaded File Type Document Name
08/13/2015 Activity Document DOC081315-002
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home