Summary
B0702119
Building Permit - Commercial
Certificate of Occupancy
PREMIERLIFE REAL ESTATE HOLDING
NEW TENANT FINISH
GENERAL OFFICE TENANT FINISH FOR LAND PLANNING FIRM
09/24/2007
10/22/2007
07/06/2008
01/10/2008
Locations
Contacts
A L HUBER, Address:10770 EL MONTE  
LEXINGTON PLUMBING & HEATING, Address:4105 INDEPENDENCE  
GASTINGER WALKER HARDEN ARCHITECTS, Address:817 WYANDOTTE  
CITY WIDE SHEET METAL, INC., Address:2824 ROE LN  
TEAGUE ELECTRIC CONSTRUCTION, INC., Address:11325 STRANG LINE RD.  
PREMIERLIFE REAL ESTATE HOLDING, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/19/2008 10/29/2010
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Codes Administration - Adequate space shall be provided for the testing and/or replacement of the water heater and the backflow device.
Correction

Codes Administration - Electrical plans and specifications have not been provided for this project.
Correction

Fire Department-2006 IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Correction

Fire Department- 2006 IFC 1008.1.8- Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Correction

Fire Department- 2006 IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Correction

Codes Administration - 2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $879.20 $879.20 Paid 10/22/2007
89 Sewer Tap Fees $300.00 $300.00 Paid 10/22/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 10/24/2007
Correction
Resolved
10/24/2007
UNDER-SLAB PVC DWV PIPING OK TO COVER WHEN READY
Above Ceiling Inspection Not Ready 11/06/2007
Correction
Corrective Action Required
11/06/2007
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS NOT READY FOR INSPECTION
All Rough Inspection - Commercial Failed 11/06/2007
Correction
Corrective Action Required
11/06/2007
PROTECTION OF COPPER PIPING INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL. ACCEPTABLE ALTERNATIVE: SPRAY FOAM AT PENETRATION OF STEEL FRAMING MEMBERS
Correction
Corrective Action Required
11/06/2007
FASTENING OF LIGHT GUAGE STEEL STUDS TO TRACKS / HEADERS EXCEPT TO SLIP TRACKS. IBC 2205; AISI; ASTM WITHIN WIDTH OF OPENINGS SCREW BOTH FLANGES
All Rough Inspection - Commercial Failed 11/21/2007
Correction
Resolved
11/21/2007
PROTECTION OF COPPER PIPING PLUMBING IN BATH WALL- APPROVED AT PENETRATION OF STEEL FRAMING MEMBERS
Electrical Service Inspection Failed 11/21/2007
Correction
Corrective Action Required
11/21/2007
Grounded and ungrounded service conductor size. (IRC) SEE ELECTRICAL PLAN- NUMBERS 5,7. PROVIDE #4 GROUND WHERE REQUIRED TO DISCONNECT , BUILDING STEEL, TO SUB-PANEL
Electrical Service Inspection Passed 11/27/2007
Correction
Resolved
11/27/2007
Grounded and ungrounded service conductor size. (IRC)
Correction
Resolved
11/27/2007
ELECTRICAL SERVICE INSTALLATION ENSURE PANEL FRONT IS IN PLACE BEFORE REQUESTING SERVICE ACTIVATION. 200 AMPS RELEASE SERVICE
All Rough Inspection - Commercial Passed 11/27/2007
Correction
Resolved
11/27/2007
FASTENING OF LIGHT GUAGE STEEL STUDS TO TRACKS / HEADERS
Correction
Resolved
11/27/2007
PROTECTION OF COPPER PIPING
Above Ceiling Inspection Failed 11/27/2007
Correction
Corrective Action Required
11/27/2007
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS + CONNECT RR VENT FAN DISCHARGE HOSES + INSTALL HVAC SUPPLY AIR DIFFUSERS INSULATE WATER PIPING PER PLMBG SPECIFICATION
Rough Plumbing Inspection - Commercial Passed 11/30/2007
Above Ceiling Inspection Passed 12/27/2007
Correction
Resolved
12/27/2007
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS INSULATE WATER PIPING PER PLMBG SPECIFICATION
Correction
Resolved
12/27/2007
None
Occupancy Inspection - Codes Commercial Failed 01/04/2008
Correction
Corrective Action Required
01/04/2008
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Passed 01/09/2008
Correction
Resolved
01/09/2008
Receive Fire Department approval PER JOE DIR 1/9/08
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.