Permit Application Status

B0702111


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0702111
Building Permit - Commercial
Certificate of Occupancy
COLE CV LEES SUMMIT MO LLC
NEW COMMERCIAL
NEW RETAIL STORE
09/21/2007
12/07/2007
06/04/2008
01/14/2009
Locations
Contacts
GEOTECHNOLOGY INC, Address:9136 CODY  
TRI-C CONSTRUCTION CO, Address:1765 MERRIMAN RD  
WESCO HEATING & COOLING LLC, Address:806 CREEKSIDE DR  
CLAYCO ELECTRIC COMPANY, Address:319 E 11TH AVE  
FIVE STAR MECHANICAL CONTRACT INC, Address:10402 E 350 HWY  
LHE PA, Address:15335 WEST 95TH STREET  
COLE CV LEES SUMMIT MO LLC, Address:ONE CVS DR  
W PHARMACY I DST, Address:1 CVS DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/03/2008 10/29/2010
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2006 IBC 1209.2 - Attic spaces. An opening not less than 20 inches by 30 inches shall be provided to any attic area having a clear height of over 30 inches. A 30-inch minimum clear headroom in the attic space shall be provided at or above the access opening.
Correction

Codes Administration - 2006 IBC 1704.1.1 - Statement of special inspections. The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with 106.1 as a condition for permit issuance. This statement shall be in accordance with Section 1705. Exceptions: 1. A statement of special inspections is not required for structures designed and constructed in accordance with the conventional construction provisions of Section 2308. 2. The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
Correction

Codes Administration - 2006 IBC 1704.1.2 - Report Requirement. Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon by the permit applicant and the building official prior to the start of work.
Correction

Fire Department- 2006 IFC 901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
Correction

Fire Department- 2006 IFC 901.5.1 Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1 Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Correction

Fire Department- 2006 IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Correction

Fire Department- 2006 IFC 508.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. IFC 903.3.7 Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be 4" Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the fire code official.
Correction

Fire Department- The 2006 International Fire Code and local amendments is the adopted fire code for the City of Lee's Summit.
Correction

Upon issuance of a certificate of substantial completion for the Phase I Improvements, the Developer may receive Certificate of Occupancy for Phase I of the Development.
Correction

Codes Administration - Keynot 3 on Sheet C5 is in regards to the sanitary sewer but is identifying the domestic waster.
Correction

Codes Administration - Keynote 8 on Sheet C5 calls for a 1.5 inch water service pipe and meter. I am assuming that this project is using a 1.5 in meter assembly. The tap on the main for this size service 2 inches with adapters to 1.5 inch for the meter assembly.
Correction

Codes Administration - 2006 IBC 1203.2 - Attic spaces. Enclosed attics and enclosed rafter spaces formed where ceiling are applied directly to the underside of roof framing members shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain and snow. Blocking and bridging shall be arranged so as not to interfere with the movement of air. A minimum of 1 inch of airspace shall be provided between the insulation and the roof sheathing. The net free ventilating area shall not be less than 1/150 of the area of the space ventilated, with 50 percent of the required ventilating area provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet above eave or cornice vents with the balance of the required ventilation provided by eave or cornice vents.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $5,415.00 $5,415.00 Paid 12/07/2007
84 Water Meters $1,325.93 $1,325.93 Paid 12/07/2007
85 Water Taps $9,523.00 $9,523.00 Paid 12/07/2007
89 Sewer Tap Fees $330.00 $330.00 Paid 12/07/2007
License Tax $11,727.01 $11,727.01 Paid 12/07/2007
Right of Way Permit $35.00 $35.00 Paid 12/07/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection Failed 01/28/2008
Correction
Partial Correction
01/28/2008
None FROM STUB EAST TO "WYE" NORTH TO N.W. CORNER EAST TO END. REVISE PLANS TO SHOW WHERE SEWER EXITS BUILDING. 4" SDR 26. REVISE PALSN TO SHOW CHANGE IN PIPE SIZE. RECALL WHEN COMPLETE TO SOUTHEAST OUTLET. PARTIAL APPROVAL
Water Service Inspection - Commercial Request Complete 1/28/2008 1/28/2008 01/28/2008
Sewer Service Inspection - Commercial Request Complete 1/28/2008 1/28/2008 01/28/2008
Footing Inspection - Commercial Partial 01/29/2008
Correction
Partial Correction
01/29/2008
PREPARATION TO POUR GRADE BEAM + INTEGRAL COLUMN FOOTINGS A/5 TO E.7/5 TO F/4.4; OK TO POUR WHEN READY SECTIONS DESCRIBED BELOW:
Water Service Inspection Partial 01/29/2008
Correction
Partial Correction
01/29/2008
DOMESTIC WATER SERVICE INSTALLATION TO 60' SOUTHWEST -- KINK AT SWEEP @ BLDG LINE TO BE CUT OUT. OK TO COVER WHEN READY FROM BUILDING ENTRY
Sewer Service Inspection Partial 01/29/2008
Correction
Partial Correction
01/29/2008
None FROM STUB EAST TO "WYE" NORTH TO N.W. CORNER EAST TO END. REVISE PLANS TO SHOW WHERE SEWER EXITS BUILDING. 4" SDR 26. REVISE PALSN TO SHOW CHANGE IN PIPE SIZE. PARTIAL APPROVAL
Correction
Resolved
01/29/2008
BUILDING SEWER SOUTHWEST BRANCH TO TIE-IN AT MAIN LINE OK TO COVER WHEN READY FROM C.O. OUTSIDE RM 114
Water Service Inspection - Commercial Request Complete 1/29/2008 1/29/2008 01/29/2008
Sewer Service Inspection - Commercial Request Complete 1/29/2008 1/29/2008 01/29/2008
Footing Inspection - Commercial Partial 01/30/2008
Correction
Partial Correction
01/30/2008
None FOOTING APPROVED A - 6 ON 1 LINE WEST TO 4.4 ON A LINE.
Underground Plumbing Inspection - Commercial Partial 01/30/2008
Correction
Partial Correction
01/30/2008
None 10 INCH SDR 35 PIPE INSTALLED FOR ROOF DRAINS NORTH END OF THE BUILDING.DRAIN PIPE CAN NOT BE APPROVED UNTIL THE SIZE AND TYPE OF PIPE APPROVED.
Water Service Inspection Passed 01/31/2008
Correction
Resolved
01/31/2008
DOMESTIC WATER SERVICE INSTALLATION
Erosion Control Inspection Residential Passed 01/31/2008
Footing Inspection - Commercial Partial 01/31/2008
Correction
Partial Correction
01/31/2008
None FOOTING APPROVED A LINE 4.4 TO 5. 5 LINE A TO E.7. PROVIDE SPECIAL INSPECTION REPORT.
Correction
Resolved
01/31/2008
None FOOTING APPROVED 5 LINE E.4 TO F. ---- F 1 TO 5.
Water Service Inspection - Commercial Request Complete 1/31/2008 1/31/2008 01/31/2008
Erosion Control Inspection Residential Passed 02/01/2008
Footing Inspection - Commercial Passed 02/01/2008
Correction
Resolved
02/01/2008
None
Correction
Resolved
02/01/2008
None
Correction
Resolved
02/01/2008
None 6 INTERIOR COLUMN PIER PADS AND 2 COLUMN PADS SOUTHEAST OUTSIDE CORNER FOR CANOPY DRIVE THRU.
Erosion Control Inspection Residential Passed 02/08/2008
Underslab Plumbing Inspection - Commercial Failed 02/08/2008
Correction
Corrective Action Required
02/08/2008
NOT READY NOT READY AT 9:15 AM - 2 - 8 - 08.
Underslab Plumbing Inspection - Commercial Failed 02/08/2008
Correction
Corrective Action Required
02/08/2008
NOT READY NOT READY 2:15 PM 2 - 8 - 08.
Erosion Control Inspection Residential Passed 02/11/2008
Underslab Plumbing Inspection - Commercial Passed 02/11/2008
Correction
Resolved
02/11/2008
NOT READY
Correction
Resolved
02/11/2008
NOT READY
Correction
Resolved
02/11/2008
None
Foundation Inspection - Commercial Passed 02/14/2008
Correction
Resolved
02/14/2008
None 2 PILASTERS PER DETAIL 7 - S /3.1 SE CORNER OF BUILDING
Underslab Electrical Inspection - Commercial Passed 03/05/2008
Underground Electrical Inspection - Commercial Request Complete 3/4/2008 3/5/2008 03/05/2008
Erosion Control Inspection Residential Passed 03/19/2008
Rough Framing Inspection - Commercial Failed 03/19/2008
Correction
Corrective Action Required
03/19/2008
NOIT READY
Rough Framing Inspection - Commercial Request Complete 3/18/2008 3/19/2008 03/19/2008
Erosion Control Inspection Residential Passed 03/25/2008
Underground Electrical Inspection - Commercial Passed 03/25/2008
Correction
Resolved
03/25/2008
None FROM BUILDING TO TRANSFORMER.
All Rough Inspection - Commercial Partial 03/25/2008
Correction
Corrective Action Required
03/25/2008
NOT READY NORTH WALL
Correction
Partial Correction
03/25/2008
None ELECT. WALLS ONLY 104 THRU 109, 112, 113, 114. OUTSIDE WALLS 1 LINE C TO F. F LINE 1 TO 4.2 AND 5 LINR A TO E.4.
Correction
Partial Correction
03/25/2008
None FRAMING APPROVED ROOMS 114, 106, 113, 112, 105, 106, 107, 108, 109, 112, 113 OK TO ROCK ONE SIDE OF ABOVE WALLS. BOTH SIDES OF 104. EXTERIOR WALLS 1 LINE C TO F, F LINE 1 TO 42 AND 5 LINE A TO E.4.
Rough Framing Inspection - Commercial Request Complete 3/24/2008 3/25/2008 03/25/2008
All Rough Inspection - Commercial Partial 03/31/2008
Correction
Partial Correction
03/31/2008
None FRAMING APPROVED EXCEPT AT ROOM 100 MAIN LEVEL
Correction
Partial Correction
03/31/2008
None ELECT. WALLS ONLY EXCEPT AT B/1, B/3 AND ROOM 100
Correction
Resolved
03/31/2008
NOT READY NORTH WALL
Correction
Partial Correction
03/31/2008
None MEZZANINE WALLS APPROVED FOR SHEETROCK MEZZANINE WALLS
Underground Electrical Inspection - Commercial Partial 04/02/2008
Correction
Resolved
04/02/2008
None FROM BUILDING TO TRANSFORMER.
Correction
Partial Correction
04/02/2008
None ELECTRICAL CONDUIT INSTALLED TO 7 PARKING LOT LIGHT POLE BASES. NOTE: LIGHT POLE BASE NOT READY. PARKING LOT
Underground Electrical Inspection - Commercial Request Complete 4/2/2008 4/2/2008 04/02/2008
All Rough Inspection - Commercial Partial 04/04/2008
Correction
Partial Correction
04/04/2008
None WALLS APPROVED
Correction
Partial Correction
04/04/2008
None WALLS APPROVED
Correction
Resolved
04/04/2008
NOT READY NORTH WALL
Correction
Partial Correction
04/04/2008
None MEZZANINE WALLS APPROVED FOR SHEETROCK MEZZANINE WALLS
Above Ceiling Inspection Failed 04/04/2008
Correction
Corrective Action Required
04/04/2008
NOT READY 106 THRU 109
Above Ceiling Inspection Partial 04/07/2008
Correction
Partial Correction
04/07/2008
NOT READY 106 THRU 109
Correction
Partial Correction
04/07/2008
None ROOM #s 107, 108 AND 109 APPROVED. ROOM 106 OPEN WATER PIPE ABOVE CEILING SW CORNER OF ROOM
Above Ceiling Inspection Partial 04/08/2008
Correction
Partial Correction
04/08/2008
None ROOM # 106 APPROVED.
Erosion Control Inspection Residential Passed 04/08/2008
Erosion Control Inspection Residential Passed 04/15/2008
Gas Service Inspection - Commercial Partial 04/15/2008
Correction
Partial Correction
04/15/2008
None GAS TEST [PARTIAL APPROVAL.] GAS PIPE WILL BE REQUIRED TO BE RETESTED AFTER DRIP LEGS ARE INSTALLED.
Gas Piping Inspection - Commercial Failed 04/15/2008
Correction
Corrective Action Required
04/15/2008
Gas Piping Design & Installation (IRC) DRIP LEGS REQUIRED ON ALL ROOF TOP UNITS AS SHOWN ON APPROVED PLANS ROOF
Electrical Service Inspection Failed 04/17/2008
Correction
Partial Correction
04/17/2008
None 3 /4 INCH GROUND ROD DRIVEN OUTSIDE BACK DOOR. INSPECTION FOR GROUND ROD ONLY.
Gas Piping Inspection - Commercial Passed 04/17/2008
Correction
Resolved
04/17/2008
None
Correction
Resolved
04/17/2008
Gas Piping Design & Installation (IRC) ROOF
Gas Service Inspection - Commercial Passed 04/17/2008
Correction
Resolved
04/17/2008
None GAS TEST APPROVED. TEST PRESSURE 22.5 PSI 5 ROOF TOP UNITS AND 1 INSIDE UNIT HEATER. RELEASE GAS.
Above Ceiling Inspection Partial 04/24/2008
Correction
Partial Correction
04/24/2008
None ROOM # 106 APPROVED.
Correction
Corrective Action Required
04/24/2008
Unused Openings (IRC) NOT READY- SPOKE WITH ELECTRICIAN AND SUPER, INSPECTION NOT READY. BORDERS INSTALL - BORDERS NOT APPROVED AND SHALL BE REMOVED. ELECTRICAL NOT COMPLETE. RECALL WHEN BORDERS REMOVED AND ELECTRICAL COMPLETE THROUGHOUT NOT READY 4-24
Above Ceiling Inspection Partial 04/28/2008
Correction
Corrective Action Required
04/28/2008
Unused Openings (IRC) THROUGHOUT NOT READY 4-24
Correction
Partial Correction
04/28/2008
None 100 VESTIBULE - APPROVED 101, 110 AND 111 PARTIAL APP. LEAVE 1 CEILING TILE OUT WEST SIDE. NORTH END AND 1 IN THE PHARMACY AREA. REMOVE TEMPORARY LIGHTING PRIOR TO INSTALLING CEILING TILE.
Erosion Control Inspection Residential Passed 04/28/2008
Driveway Inspection Passed 04/29/2008
Electrical Service Inspection Passed 05/01/2008
Correction
Resolved
05/01/2008
None 800 AMP MDP. APPROVED PANEL A -225 AMP. APP. PANEL B - 225 AMP. APP. PANEL C - 125 AMP. APP. PANEL D - 125 AMP. APP. RELEASE ELECT. SERVICE.
Correction
Resolved
05/01/2008
None
Piers/Caissons Inspection - Commercial Partial 05/02/2008
Correction
Partial Correction
05/02/2008
None 5 LIGHTPOLE BASES NORTH PARKING LOT APPROVED PER PLANS. PARKING LOT LIGHT POLE BASES
Underground Electrical Inspection - Commercial Request Complete 5/2/2008 5/2/2008 05/02/2008
Underground Plumbing Inspection - Commercial Passed 05/13/2008
Correction
Resolved
05/13/2008
None
Piers/Caissons Inspection - Commercial Passed 05/13/2008
Correction
Resolved
05/13/2008
None PARKING LOT LIGHT POLE BASES
Rough Framing Inspection - Commercial Passed 05/13/2008
Correction
Resolved
05/13/2008
NOIT READY
Underground Electrical Inspection - Commercial Partial 05/13/2008
Correction
Partial Correction
05/13/2008
None SOUTH LIGHT POLE NOT INSPECTED. NORTH AND WEST POLES NOT INSTALLED PARKING LOT
Above Ceiling Inspection Passed 05/13/2008
Correction
Resolved
05/13/2008
None
Correction
Resolved
05/13/2008
Unused Openings (IRC) THROUGHOUT NOT READY 4-24
Correction
Resolved
05/13/2008
None
Correction
Resolved
05/13/2008
NOT READY 106 THRU 109
All Rough Inspection - Commercial Passed 05/13/2008
Correction
Resolved
05/13/2008
None
Correction
Resolved
05/13/2008
None
Correction
Resolved
05/13/2008
NOT READY NORTH WALL
Correction
Resolved
05/13/2008
None MEZZANINE WALLS
Underground Electrical Inspection - Commercial Request Complete 5/13/2008 5/13/2008 05/13/2008
Sidewalk Inspection Partial 05/15/2008
Erosion Control Inspection Residential Passed 05/16/2008
Occupancy Inspection - Codes Commercial Partial 05/16/2008
Correction
Resolved
05/16/2008
None FIRE DEPT. APPROVED
Correction
Corrective Action Required
05/16/2008
SEE REPORT SEE FINAL INSPECTION REPORT FROM PLANNING DATED 5/15/08.
Correction
Corrective Action Required
05/16/2008
TRASH COMPACTOR DISCONECT SECURE DISCONECT TO WALL. BOND DISCONECT CASE. PROVIDE LISTING ON ANACONDA SEAL TITE FROM DISCONECT TO TRASH COMPACTOR. SOUTH OUTSIDE WALL
Correction
Corrective Action Required
05/16/2008
OUTLET BY MOP SINK OUTLET REQUIRED TO BE GFCI PROTECTED EAST WALL
Correction
Corrective Action Required
05/16/2008
GRAB BAR INSTALL VERTICLE GRAB BAR IN MENS BATHROOM MENS BATHROOM
Correction
Partial Correction
05/16/2008
Receive Public Works Approval COMPLETE PUBLIC WORKS REQUIREMENTS
Correction
Partial Correction
05/16/2008
Receive Water Utilities Approval
Underground Electrical Inspection - Commercial Passed 05/16/2008
Correction
Resolved
05/16/2008
None PARKING LOT
Driveway Inspection Passed 05/16/2008
Occupancy Inspection - Codes Commercial Partial 06/04/2008
Correction
Resolved
06/04/2008
None FIRE DEPT. APPROVED
Correction
Partial Correction
06/04/2008
SEE REPORT SEE FINAL INSPECTION REPORT FROM PLANNING DATED 5/22/08.
Correction
Resolved
06/04/2008
TRASH COMPACTOR DISCONECT SOUTH OUTSIDE WALL
Correction
Resolved
06/04/2008
OUTLET BY MOP SINK EAST WALL
Correction
Resolved
06/04/2008
GRAB BAR MENS BATHROOM
Correction
Partial Correction
06/04/2008
Receive Public Works Approval COMPLETE PUBLIC WORKS REQUIREMENTS
Correction
Resolved
06/04/2008
Receive Water Utilities Approval
Erosion Control Inspection Residential Passed 06/04/2008
Issue Temporary C of O Complete 6/3/2008 6/4/2008 06/04/2008
Sidewalk Inspection Partial 06/09/2008
Occupancy Inspection - Codes Commercial Passed 01/09/2009
Correction
Resolved
01/09/2009
SEE REPORT
Correction
Resolved
01/09/2009
Receive Public Works Approval
Correction
Resolved
01/09/2009
None OCCUPANCY APPROVED CLOSE PERMIT C. O.
Sewer Service Inspection Passed 01/12/2009
Correction
Resolved
01/12/2009
None PARTIAL APPROVAL
Correction
Resolved
01/12/2009
BUILDING SEWER SOUTHWEST BRANCH OK TO COVER WHEN READY FROM C.O. OUTSIDE RM 114
Sidewalk Inspection Passed 01/14/2009
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home