Permit Application Status

B0701299


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0701299
Building Permit - Commercial
Certificate of Occupancy
SNUGBEE LEES SUMMIT LLC
NEW TENANT FINISH
TENANT FINISH
06/11/2007
08/01/2007
03/11/2008
09/17/2007
Locations
Contacts
AFC HEATING & COOLING INC, Address:824 NW MAIN ST  
VALOR CONSTRUCTION INC, Address:5602 E 139TH ST  
COPPER CRAFT PLUMBING, INC., Address:PO BOX 32581  
RSA ARCHITECTURE INC, Address:6355 WEST 110TH ST  
TK ELECTRIC, Address:#3 MERLE RD  
SNUGBEE LEES SUMMIT LLC, Address:7206 SILVER LODE LN  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/28/2008 10/29/2010
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Fire Departmnent- IFC 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- The building shall comply with Lee's Summit amendments to the adopted codes, not the City of Gladstone as listed.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $285.74 $285.74 Paid 08/01/2007
89 Sewer Tap Fees $150.00 $150.00 Paid 08/01/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 08/02/2007
Correction
Partial Correction
08/02/2007
IN-WALL SYSTEMS PLUMBING@ N DEMISING WALL OK TO COVER WHEN READY
Underslab Plumbing Inspection - Commercial Passed 08/02/2007
Correction
Resolved
08/02/2007
UNDER-SLAB DWV PIPING OK TO COVER WHEN READY
All Rough Inspection - Commercial Passed 08/08/2007
Correction
Resolved
08/08/2007
IN-WALL SYSTEMS
Correction
Resolved
08/08/2007
FRAMING OF WALLS & BULKHEADS + IN-WALL SYSTEMS ROUGH OK TO COVER WHEN READY
Electrical Service Inspection Passed 08/13/2007
Correction
Resolved
08/13/2007
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE SUITE 1134 (SUBWAY)
Above Ceiling Inspection Passed 09/13/2007
Correction
Resolved
09/13/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 09/13/2007
Correction
Corrective Action Required
09/13/2007
Receive Fire Department approval
Correction
Corrective Action Required
09/13/2007
ELECTRICAL PANEL SCHEDULE NOT FOUND IN PLACE
Correction
Corrective Action Required
09/13/2007
INSTALLATION OF PENDANT LUMINAIRES INCOMPLETE SUBJECT TO APPROVAL
Correction
Corrective Action Required
09/13/2007
HANDICAPPED ACCESSIBLE RESTROOM SIGNS NOT IN PLACE PER ADA/ANSI
Correction
Corrective Action Required
09/13/2007
BACKFLOW PREVENTION DEVICE AT SODA DISPENSING EQUIPMENT NOT IN PLACE PER ASSE 1022 LISTING
Correction
Corrective Action Required
09/13/2007
CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VA OR 1/8 HP NEC 422.31B: IF NOT WITHIN SIGHT OF PANELBOARD IF TO SERVE AS DISCONNECT MUST BE LOCKABLE
Correction
Corrective Action Required
09/13/2007
USE / OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FOR BUSINESS NO PUBLIC ENTRY
Occupancy Inspection - Codes Commercial Passed 09/14/2007
Correction
Resolved
09/14/2007
Receive Fire Department approval PER JOE DIR
Correction
Resolved
09/14/2007
ELECTRICAL PANEL SCHEDULE
Correction
Resolved
09/14/2007
INSTALLATION OF PENDANT LUMINAIRES
Correction
Resolved
09/14/2007
HANDICAPPED ACCESSIBLE RESTROOM SIGNS
Correction
Resolved
09/14/2007
BACKFLOW PREVENTION DEVICE AT SODA DISPENSING EQUIPMENT DOCUMENTATION PROVIDED PER ASSE 1022 LISTING
Correction
Resolved
09/14/2007
CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VA OR 1/8 HP
Correction
Resolved
09/14/2007
USE / OCCUPANCY APPROVAL STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home