Permit Application Status

B0700715


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0700715
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
NEW TENANT FINISH
TENANT FINISH
04/10/2007
05/09/2007
03/16/2008
09/28/2007
Locations
Contacts
ANDERSON PROPERTY DEVELOPMENT, Address:PO BOX 30571  
DEANE ELECTRIC LLC, Address:9309 ROSNER  
QUALITY PLUMBING, INC., Address:1731 HOWELL ST.  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 210, Phone:(816) 645-2336  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/05/2007 10/29/2010
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Codes Administration - 2003 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in an occupancy in Group I-2 used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appliances.
Correction

Codes Administration - Plans and specifications for the mechanical, electrical and plumbing work have not been provided.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $593.46 $593.46 Paid 05/09/2007
89 Sewer Tap Fees $210.00 $210.00 Paid 05/09/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 05/10/2007
Correction
Corrective Action Required
05/10/2007
PERMIT REQUIREMENTS NOT MET PER NOTICE ON PERMIT: DO NOT PERFORM ANY ELECTRICAL, MECHANICAL OR PLUMBING INSPECTIONS UNTIL THE SUB-CONTRACTORS HAVE BEEN LISTED ON THE PERMIT.
Underslab Plumbing Inspection - Commercial Passed 05/11/2007
Correction
Resolved
05/11/2007
None
Correction
Resolved
05/11/2007
PERMIT REQUIREMENTS NOT MET
Rough Framing Inspection - Commercial Failed 05/23/2007
Correction
Partial Correction
05/23/2007
FASTENING METAL STUDS REQUIRED TO BE SCREWED TO TRACK BOTH SIDES. METAL STUDS
Rough Plumbing Inspection - Commercial Partial 05/23/2007
Correction
Partial Correction
05/23/2007
None ROUGH PLUMBING APPROVED TO ROOF
Rough Framing Inspection - Commercial Request Complete 5/22/2007 5/23/2007 05/23/2007
Miscellaneous Inspection Partial 05/25/2007
Correction
Resolved
05/25/2007
broken sprinkler head No damage to building as it only has concrete floor and metal stud framing. water in sprinkler room turned off. Sprinkler Co. called. No posting - no permits required for repair mens bathroom
Correction
Partial Correction
05/25/2007
BROKEN SPRINKLER HEAD Received a call from the fire dept. on a broken sprinkler head. Arrived at 12:40 pm - met Capt. Weston who stated a worker had broken the sprinkler head off. The building is a shell building with a tennant finish underway. MENS BATHROOM
Miscellaneous Inspection Passed 06/05/2007
Correction
Resolved
06/05/2007
broken sprinkler head No damage to building as it only has concrete floor and metal stud framing. water in sprinkler room turned off. Sprinkler Co. called. No posting - no permits required for repair mens bathroom
Correction
Resolved
06/05/2007
BROKEN SPRINKLER HEAD Received a call from the fire dept. on a broken sprinkler head. Arrived at 12:40 pm - met Capt. Weston who stated a worker had broken the sprinkler head off. The building is a shell building with a tennant finish underway. MENS BATHROOM
Rough Electrical Inspection - Commercial Partial 06/05/2007
Correction
Partial Correction
06/05/2007
None WALLS ONLY APPROVED. DO NOT ROCK ANY WALLS. WALLS ONLY
Above Ceiling Inspection Failed 07/12/2007
Correction
Corrective Action Required
07/12/2007
CEILING TILE REMOVE CEILING TILE FOR INSPECTION CEILING
Rough Electrical Inspection - Commercial Partial 07/12/2007
Correction
Partial Correction
07/12/2007
None WALLS ONLY APPROVED. DO NOT ROCK ANY WALLS. WALLS ONLY
Rough Plumbing Inspection - Commercial Partial 07/12/2007
Correction
Partial Correction
07/12/2007
None ROUGH PLUMBING APPROVED TO ROOF
Rough Framing Inspection - Commercial Failed 07/12/2007
Correction
Partial Correction
07/12/2007
FASTENING METAL STUDS REQUIRED TO BE SCREWED TO TRACK BOTH SIDES. METAL STUDS
Above Ceiling Inspection Failed 07/16/2007
Correction
Corrective Action Required
07/16/2007
ACCESS ALL DOORS LOCKED. NO ONE ON SITE TO PROVIDE ACCESS.
Correction
Corrective Action Required
07/16/2007
CEILING TILE CEILING
Above Ceiling Inspection Failed 07/20/2007
Correction
Corrective Action Required
07/20/2007
OPEN BOX REPLACE KNOCKOUT IN ABOVE CEILING BOXS. THIS MAY NOT BE ALL THE REQUIRED CORRECTIONS AS OWNER TO SUPPLY A LADDER TO COMPLETE THE INSPECTION. ABOVE CEILING
Correction
Corrective Action Required
07/20/2007
WIRING AND SUPPORT SUPPORT CONDUCTORS PER NEC REQUIREMENTS ABOVE CEILING
Correction
Corrective Action Required
07/20/2007
COMBUSTIBLES NO COMBUSTIBLES ALLOWED IN THE ABOVE CEILING WHEN ABOVE CEILING IS USED FOR RETURN AIR. ABOVE CEILING
Correction
Corrective Action Required
07/20/2007
DUCT SUPPORT FLEX DUCT CAN NOT BE SUPPORTED WITH ZIP TIES. ABOVE CEILING
Correction
Resolved
07/20/2007
ACCESS
Correction
Resolved
07/20/2007
CEILING TILE CEILING
Rough Electrical Inspection - Commercial Partial 07/20/2007
Correction
Partial Correction
07/20/2007
None WALLS ONLY APPROVED. DO NOT ROCK ANY WALLS. WALLS ONLY
Correction
Corrective Action Required
07/20/2007
OUTLET REQUIRED OUTLET REQUIRED FOR SERVICE AND REPAIR OF ROOF TOP UNITS ROOF.
Correction
Corrective Action Required
07/20/2007
GROUND CONDUCTOR COLOR CODE GROUNDING CONDUCTOR ROOF TOP UNIT
Rough Framing Inspection - Commercial Failed 07/20/2007
Correction
Partial Correction
07/20/2007
FASTENING METAL STUDS REQUIRED TO BE SCREWED TO TRACK BOTH SIDES. METAL STUDS
Rough Electrical Inspection - Commercial Passed 07/26/2007
Correction
Resolved
07/26/2007
None WALLS ONLY
Correction
Resolved
07/26/2007
GROUND CONDUCTOR ROOF TOP UNIT
Correction
Resolved
07/26/2007
OUTLET REQUIRED ROOF.
Above Ceiling Inspection Passed 07/26/2007
Correction
Resolved
07/26/2007
DUCT SUPPORT ABOVE CEILING
Correction
Resolved
07/26/2007
COMBUSTIBLES ABOVE CEILING
Correction
Resolved
07/26/2007
WIRING AND SUPPORT ABOVE CEILING
Correction
Resolved
07/26/2007
OPEN BOX ABOVE CEILING
All Rough Inspection - Commercial Failed 07/26/2007
Correction
Corrective Action Required
07/26/2007
Landings at Doors (IRC) LANDING REQUIRED OM EACH SIDE OF EXTERIOR DOORS BACK DOOR
Rough Plumbing Inspection - Commercial Passed 07/26/2007
Correction
Resolved
07/26/2007
None
Rough Framing Inspection - Commercial Passed 07/26/2007
Correction
Resolved
07/26/2007
FASTENING METAL STUDS
All Rough Inspection - Commercial Passed 07/27/2007
Correction
Resolved
07/27/2007
Landings at Doors (IRC) BACK DOOR
Occupancy Inspection - Codes Commercial Failed 07/27/2007
Correction
Corrective Action Required
07/27/2007
EXHAUST FAN EXHAUST FAN REQUIRED TO OPERATE WHEN BATHROOM IS OCCUPIED BATHROOM
Correction
Corrective Action Required
07/27/2007
Electrical Listing & Labeling (IRC) LABEL ALL SERVICE PANEL BREAKERS SERVICE PANELS
Correction
Corrective Action Required
07/27/2007
EXIT SIGN REMOVE EXIT SIGN FROM CLOSET IN SIDE MIDDLE BACK DOOR CLOSET
Correction
Corrective Action Required
07/27/2007
EXIT SIGN INOPERATIVE EAST BACK DOOR
Correction
Corrective Action Required
07/27/2007
ADDRESS INSTALL ONLY THE CORRECT ADDRESS 3385 ON THE FRONT. LABEL BACK DOORS WITH CORRECT ADDRESS. FRONT / BACK
Correction
Corrective Action Required
07/27/2007
CEILING TILE INSTALL CEILING TILE DO NOT OCCUPY THROUGH OUT
Correction
Corrective Action Required
07/27/2007
Receive Fire Department approval COMPLETE FIRE DEPT. CORRECTIONS.
Occupancy Inspection - Codes Commercial Failed 08/02/2007
Correction
Resolved
08/02/2007
ADDRESS FRONT / BACK
Correction
Resolved
08/02/2007
CEILING TILE THROUGH OUT
Correction
Corrective Action Required
08/02/2007
Receive Fire Department approval COMPLETE FIRE DEPT. CORRECTIONS. DO NOT OCCUPY
Correction
Resolved
08/02/2007
EXIT SIGN EAST BACK DOOR
Correction
Resolved
08/02/2007
EXIT SIGN CLOSET
Correction
Corrective Action Required
08/02/2007
Electrical Listing & Labeling (IRC) LABEL ALL SERVICE PANEL BREAKERS PANEL B21C21 BREAKER NUMBERS ARE REQUIRED TO CORRESPOND WITH LABEL NUMBERS. EAST PANEL BY THE BATHROOM - LABEL ALL BREAKERS. SERVICE PANELS
Correction
Corrective Action Required
08/02/2007
EXHAUST FAN EXHAUST FAN REQUIRED TO OPERATE WHEN BATHROOM IS OCCUPIED. LABEL BREAKER. BATHROOM
Occupancy Inspection - Codes Commercial Failed 08/15/2007
Correction
Resolved
08/15/2007
EXHAUST FAN BATHROOM
Correction
Resolved
08/15/2007
Electrical Listing & Labeling (IRC) SERVICE PANELS
Electrical Service Inspection Passed 08/23/2007
Correction
Resolved
08/23/2007
None ELECTRIC SERVICE WAS APPROVED ON SHELL BUILDING AND RELEASED OCTO. OF 2005. NO NEW SERVICE PANELS WERE ADDED ON TENNANT FINISH PERMIT.
Electrical Service Inspection Passed 09/19/2007
Correction
Resolved
09/19/2007
RE-DESIGN OF SERVICE CONTRACTOR STATES 3385B METER AND 33 TO BE TERMINATED. TWO DISCONNECTS INSTALLED. 4 DISCONNECTS FOR BUILDING, LABEL ACCORDINGLY. RELEASE NEW METER FOR 3385. TWO METERS TO REMAIN: 3365 AND 3385A HOUSE PANEL. SOUTH SIDE OF 3365-3385
Occupancy Inspection - Codes Commercial Passed 09/27/2007
Correction
Resolved
09/27/2007
Receive Fire Department approval Approved per Captain Dir 9/28/07
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home