Permit Application Status

B0700596


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0700596
Building Permit - Residential
Certificate of Occupancy
HATHAWAY BROOKE M & RANDOL BRETT
NEW SINGLE FAMILY
HOUSE AND DECK
03/28/2007
04/02/2007
04/05/2009
01/06/2009
Locations
Contacts
BRIGHT PLUMBING, Address:220 NW COMMERCE CT  
BC NATIONAL BANKS, Address:360 SW M150 HWY  
SUMMIT ELECTRICAL & MECHANICAL LLC, Address:PO BOX 1573  
UNITED HEATING & COOLING, Address:301 DUCK RD  
HATHAWAY BROOKE M & RANDOL BRETT, Address:627 NE LONE HILL DR  
HATHAWAY BROOKE M & RANDOL BRETT, Address:13033 CATALINA DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/25/2007 10/29/2010
Correction

In a combined effort with both the R-4, and the R-7 School Districts the City of Lee's Summit is working together to educate the development community on a new program, the "Lee's Summit Voluntary Residential Development Surcharge". This is a program, which will help raise capital to build new schools for our community. Brochures are available at the front counter of both the Planning and Development and the Codes Administration departments. You can also find more information on the City of Lee's Summit web site at lees-summit.mo.us. (For more information please contact the Board of Education at 986-2400).
Correction

CA - The holder of this permit agrees and understands that the work authorized by this permit shall be performed in accordance with the 2003 International Residential Code as amended by Chapter 7 of the Lee's Summit Code of Ordinances.
Correction

All residential projects applied for after May 6, 2006 shall have a maximum stair rise of 7-3/4 inches and a minimum tread depth of 10". This project was applied for after May 6, 2006 and therefore must comply with this requirement.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-122 - Any excavation for foundations and/or footings of buildings and structures shall be backfilled within twenty-eight (28) days from the date of permit issuance unless otherwise approved by the building official.
Correction

CA - LSCO 7-128 (a)1 - Retaining walls which are over 4 feet in height measured from the bottom of the footing to the top of the wall of the wall shall be designed and sealed by a professional engineer or architect registered in the State of Missouri. In addition, the building official may waive the requirements for a permit or engineered drawings for walls over 4 feet in height if it is deemed unnecessary to require such submittals due to the location and type of wall to be installed.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-168 A - Footing and foundation inspections shall be made after excavations for footings are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place before inspection. Materials for the foundation shall be on the job, except where concrete is ready mixed in accordance with ASTM C 94; the concrete need not be on the job.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-930 - All dwellings shall have a controlled method of water disposal from the roofs that will collect and discharge all roof drainage to the ground at least 3 feet from the foundation walls or to an approved drainage system.
Correction

Codes Administration - 2003 IRC 311.5.2 - Headroom. The minimum headroom in all parts of the stairway shall not be less than 6 feet 8 inches measured vertically from the sloped plane adjoining the tread nosing or from the floor surface of the landing or platform.
Correction

Codes Administration - 2003 IRC 401.3 - Drainage. Surface drainage shall be diverted to a storm sewer conveyance or other approved point of collection so as to not create a hazard. Lots shall be graded so as to drain surface water away from foundation walls. The grade away from foundation wall shall fall a minimum of 6 inches with the first 10 feet. Exception: Where lot lines, walls, slopes or other physical barriers prohibit 6 inches of fall within 10 feet, drains or swales shall be provided to ensure drainage away from the structure.
Correction

Codes Administration - 2003 IRC 403.1.6 - Foundation anchorage. When braced wall panels are supported directly on continous foundations, the wall wood sill plate or cold-formed steel bottom track shall be anchored to the foundation in accordance with this section. The wood sole plate at exterior walls in monolithic slabs and wood sill plate shall be anchored to the foundation with anchor bolts spaced a maximum of 6 feet (1829 mm) on center. There shall be a minimum of two bolts per plate section with one bolt located not more than 12 inches (305 mm) or less than seven bolt diameters from each end of the plate section. In Seismic Design Categories D1 and D2, anchor bolts shall also be spaced at 6 feet (1829 mm) on center and located with 12 inches (305 mm) from the ends of the plate section at interior braced wall lines when required by Section R602.10.9 to be supported on a continous foundation. Bolts shall be at least 1/2 inch (12.7 mm) in diameter and shall extend a minimum of 7 inches (178 mm) into masonry or concrete. Interior bearing wall sole plates on monolithic slab foundations shall be positively anchored with approved fasteners. A nut and washer shall be tightened on each bolt to the plate. Sills and sole plates shall be protected against decay and termites wher required by Sections R318 and R319. Cold-formed steel framing systems shall be fastened to the wood sill plates or anchored directly to the foundation as required in Section R505.3.1 or R603.1.1. Exceptions: 1. Foundation anchor straps, space as required to provide equivalent anchorage to 1/2-inch-diameter (12.7 mm) anchor bolts. 2. Walls 24 inches total in length or shorter connecting offset braced wall panels shall be anchored to the foundation with a minimum of one anchor bolt located in the center third of the plate section and shall be attached to adjacent braced wall panels per Figure R602.10.5 at corners. 3. Walls 12 inches total length or shorter connecting offset braced wall panels shall be permitted to be connected to the foundation without anchor bolts. The wall shall be attached to adjacent braced wall panels per Figure 602.10.5. As amended by the City of Lee's Summit.
Correction

Codes Administration - 2003 IRC 407.1.7.3 - Foundation elevation. On graded sites, the top of any exterior foundation shall extend aboe the elevation of the street gutter at point of discharge or the inlet of an approved drainage device a minimum of 12 inches plus 2 percent. Alternate elevations are permitted sublect to the approval of the building official, provided it can be demonstrated tha required drainage to the point of discharge and away from the structure is provided at all locations on the site.
Correction

Codes Administration - 2003 IRC 405.1 - Concrete or masonry foundations. Drains shall be provided around all concrete or masonry foundations that retain earth and enclose habitable or usable spaces located below grade. Drainage tiles, gravel or crushed stone drains, perforated pipe or other approved systems or materials shall be installed at or below the area to be protected and shall discharge by gravity or mechanical means into an approved drainage system. Gravel or crushed stone drains shall extend at least 1 foot beyond the outside edge of the footing and 6 inches above the top of the footing and be covered with an approved filter membrane material. The top of open joints of drain tiles shall be protected with strips of building paper, and the drainage tiles or perforated pipe shall be placed on a mimum of 2 inches of washed gravel or crushed rock at lease on sieve size larger than the tile joint openings or perforation and covered with not less than 6 inches of the same material.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - The holder of this permit agrees and understands that only persons authorized per LSCO 7-130 are permitted to perform electrical, plumbing or mechanical work authorized by this permit.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,028.45 $1,028.45 Paid 04/02/2007
84 Water Meters $125.00 $125.00 Paid 04/02/2007
85 Water Taps $2,734.00 $2,734.00 Paid 04/02/2007
89 Sewer Tap Fees $600.00 $600.00 Paid 04/02/2007
91 EFHB Maybrook Water Shed $852.20 $852.20 Paid 04/02/2007
Right of Way Permit $35.00 $35.00 Paid 04/02/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 04/06/2007
Correction
Resolved
04/06/2007
R403.1.4 Footing Depth (IRC)
Correction
Resolved
04/06/2007
R403.1.1 Minimum size of footings (IRC)
Correction
Resolved
04/06/2007
R403.1 Footing support (IRC)
Correction
Resolved
04/06/2007
LSCO 7-921 Column Pad Reinforcement (IRC)
Correction
Resolved
04/06/2007
LSCO 7-920 Footing Reinforcement (IRC)
Erosion Control Inspection Residential Failed 04/19/2007
Correction
Resolved
04/19/2007
LSCO5029XX2 Tracking Mud, Debris
Correction
Corrective Action Required
04/19/2007
LSCO 5029 XX Erosion Control INADEQUATE EROSION CONTROL 2 DAYS TO COMPLY
Underslab Plumbing Inspection - Residential Passed 04/19/2007
Erosion Control Inspection Residential Failed 04/24/2007
Correction
Corrective Action Required
04/24/2007
LSCO 5029 XX Erosion Control INADEQUATE EROSION CONTROL NO FURTHER INSPECTIONS UNTIL COMPLIANT 2ND NOTICE
Sewer Service Inspection - R Passed 04/24/2007
Sewer Service Inspection - Residential Request Complete 4/24/2007 4/24/2007 04/24/2007
Water Service Inspection - R Passed 04/26/2007
Correction
Resolved
04/26/2007
NONE None
Water Service Inspection - Residential Request Complete 4/26/2007 4/26/2007 04/26/2007
All Rough Inspection - Residential Failed 07/12/2007
Correction
Corrective Action Required
07/12/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) LATERIAL BRACE REAR I BEAM NORTH SIDE REAR BEAM BSMT
Correction
Corrective Action Required
07/12/2007
R802.3 Roof Framing (Details) (IRC) PROVIDE PLANS ON ENGINEERED ROOF FOR TILE ROOF TILE ROOF
Correction
Corrective Action Required
07/12/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) JOIST HANGER TJI JOIST WHERE REQUIRED NORTH WEST SIDE
Correction
Corrective Action Required
07/12/2007
R403.1.6 Foundation Anchor Bolts (IRC) INSTALL BOLTS AND NUTS EAST SOUTH WALL BSMT WALLS
Correction
Corrective Action Required
07/12/2007
R602.6.1 Top Plate Drilling & Notching (IRC) HVAC CHASE TIE PLATE LINE IN HALL. SUPPORT CUT CEILING JOIST HALL SIDE 2ND FLOOR HALL
Correction
Corrective Action Required
07/12/2007
R602.6 Stud Drilling and Notching (IRC) CUT PLATES AT RETURN AIR, INSTALL DSTUD UNDER JOIST AND DBL STUD UNDER DBL JOIST MSTR CLOSET / GARAGE WALL GARAGE WALL
Correction
Corrective Action Required
07/12/2007
R802.3.1 Ceiling Joist & Rafter Connections (IRC) JOIST HANGER CEILING JOIST IN GREATROOM NO BEARING GREATROOM
Correction
Corrective Action Required
07/12/2007
NONE None NOT COMPLETE CHECK ALL
Correction
Corrective Action Required
07/12/2007
M1307.1 Appliance Installation Per Manufacturer's Instructions (IRC) NAIL FIREPLACE FLANG
Correction
Corrective Action Required
07/12/2007
E3804.7 Electrical in Air Handling Spaces (IRC) 1/2 BATH WALL. GREAT ROOM WALL 1ST FLOOR
Correction
Corrective Action Required
07/12/2007
LSCO 7-903 Bathroom ventilation (IRC) VENT ALL FANS
Correction
Corrective Action Required
07/12/2007
R502.5 (1,2) Girder and Header Spans INSTALL HEADER FOR ATTIC ACCESS. NORTH 2ND FLOOR BED
Correction
Corrective Action Required
07/12/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) REAR WALL AT DBL 2X10 IN CEILING MSTR BED
Correction
Corrective Action Required
07/12/2007
R602.8 Fireblocking (IRC) 1. FLUE CHASE GARAGE WALL. 2 TUB TRAPS. 3. 2ND FLOOR SHOWER. 4. FIR OUT GARAGE BEAM POST
Correction
Corrective Action Required
07/12/2007
M1306.1 Appliance Clearance to Unprotected Combustible Construction (IRC) FLUE CLEARANCE TO 2X4 GARAGE FLUE CHASE
Correction
Corrective Action Required
07/12/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) SUPPORT 2X10 @ FLUE CHASE HEADER GARAGE @ FLUE CHASE
Electrical Service Inspection Failed 07/12/2007
Correction
Corrective Action Required
07/12/2007
NONE None NOT INSTALLED
Gas Service Inspection - Residential Passed 07/12/2007
Correction
Resolved
07/12/2007
NONE None
Gas Piping Inspection - Residential Passed 07/12/2007
Correction
Resolved
07/12/2007
NONE None
All Rough Inspection - Residential Failed 07/16/2007
Correction
Corrective Action Required
07/16/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) SUPPORT 2X10 @ FLUE CHASE HEADER **KEEP STUDS AT EVERY 16" OC. TOP PLATE CANNOT SPAN THAT MUCH WITH GIVEN LOAD** GARAGE @ FLUE CHASE
Correction
Resolved
07/16/2007
M1306.1 Appliance Clearance to Unprotected Combustible Construction (IRC)
Correction
Corrective Action Required
07/16/2007
R602.8 Fireblocking (IRC) 1. FLUE CHASE GARAGE WALL. 4. FIR OUT GARAGE BEAM POST
Correction
Resolved
07/16/2007
R502.6 Bearing (Joist/Beam Girder) (IRC)
Correction
Resolved
07/16/2007
R502.5 (1,2) Girder and Header Spans
Correction
Corrective Action Required
07/16/2007
LSCO 7-903 Bathroom ventilation (IRC) VENT ALL FANS
Correction
Corrective Action Required
07/16/2007
E3804.7 Electrical in Air Handling Spaces (IRC) 1/2 BATH WALL. GREAT ROOM WALL **UNBLOCK RETURN AIR PATH** 1ST FLOOR
Correction
Corrective Action Required
07/16/2007
M1307.1 Appliance Installation Per Manufacturer's Instructions (IRC) NAIL FIREPLACE FLANG
Correction
Corrective Action Required
07/16/2007
NONE None ***PLEASE ADDRESS FOLLOWING: 1. PROVIDE FULL SUPPORT UNDER I BEAM AND LVL BEAM IN MASTER BEDROOM. A SINGLE JACK STUD DIRECTLY UNDERNEATH THE BEAMS CANNOT CARRY THAT MUCH LOAD. 2. BLOCK UNDER POINT LOADS. 3. BRACE LVL BEAM ENDS ABOVE KITCHEN/DINING*** NOT COMPLETE CHECK ALL
Correction
Resolved
07/16/2007
R802.3.1 Ceiling Joist & Rafter Connections (IRC)
Correction
Resolved
07/16/2007
R602.6 Stud Drilling and Notching (IRC)
Correction
Resolved
07/16/2007
R602.6.1 Top Plate Drilling & Notching (IRC)
Correction
Corrective Action Required
07/16/2007
R403.1.6 Foundation Anchor Bolts (IRC) INSTALL BOLTS AND NUTS EAST SOUTH WALL **BY WALKOUT DOOR** BSMT WALLS
Correction
Corrective Action Required
07/16/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) JOIST HANGER TJI JOIST WHERE REQUIRED NORTH WEST SIDE
Correction
Corrective Action Required
07/16/2007
R802.3 Roof Framing (Details) (IRC) PROVIDE PLANS ON ENGINEERED ROOF FOR TILE ROOF TILE ROOF
Correction
Corrective Action Required
07/16/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) LATERIAL BRACE REAR I BEAM NORTH SIDE HMMM....??? DO NOT ROCK. OK TO INSULATE REAR BEAM BSMT
All Rough Inspection - Residential Failed 07/18/2007
Correction
Resolved
07/18/2007
R502.6 Bearing (Joist/Beam Girder) (IRC)
Correction
Resolved
07/18/2007
R602.8 Fireblocking (IRC)
Correction
Resolved
07/18/2007
LSCO 7-903 Bathroom ventilation (IRC)
Correction
Resolved
07/18/2007
E3804.7 Electrical in Air Handling Spaces (IRC)
Correction
Resolved
07/18/2007
M1307.1 Appliance Installation Per Manufacturer's Instructions (IRC)
Correction
Resolved
07/18/2007
NONE None NOT COMPLETE CHECK ALL
Correction
Resolved
07/18/2007
R403.1.6 Foundation Anchor Bolts (IRC)
Correction
Corrective Action Required
07/18/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) JOIST HANGER TJI JOIST WHERE REQUIRED *INCORRECT HANGERS INSTALLATION* NORTH WEST SIDE
Correction
Resolved
07/18/2007
R802.3 Roof Framing (Details) (IRC)
Correction
Corrective Action Required
07/18/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) LATERIAL BRACE REAR I BEAM NORTH SIDE HMMM....??? OK TO ROCK. OK TO INSULATE REAR BEAM BSMT
Miscellaneous Inspection Failed 07/26/2007
Correction
Corrective Action Required
07/26/2007
R325 Premises Identification (IRC) PROPERTY TO BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS
All Rough Inspection - Residential Failed 07/26/2007
Correction
Corrective Action Required
07/26/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) JOIST HANGER TJI JOIST WHERE REQUIRED *INCORRECT HANGERS INSTALLATION* SOLID BLOCKING & COMPLETION OF NAILING REQUIRED BASEMENT ABOVE ELEC. PANEL
Correction
Resolved
07/26/2007
R502.6 Bearing (Joist/Beam Girder) (IRC) OK TO ROCK. OK TO INSULATE
Correction
Corrective Action Required
07/26/2007
R602.6 Stud Drilling and Notching (IRC) STUD OVERDRILLED. PROVIDE STUD SHOE OR REPLACE STUD Basement LEFT OF PANEL
Electrical Service Inspection Failed 07/26/2007
Correction
Corrective Action Required
07/26/2007
NONE None - PROVIDE WIRE CLAMPS AT WIRES EXITING PANEL. - GROUND TO WATER CONNECTION CLAMP MUST BE AL/CU LISTED. (COMBINATION COPPER/ALLUMINIMUM) BASEMENT
Miscellaneous Inspection Failed 07/31/2007
Correction
Corrective Action Required
07/31/2007
R325 Premises Identification (IRC) PROPERTY TO BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS NO FURTHER INSPECTIONS UNTIL COMPLIANT 2ND NOTICE
Electrical Service Inspection Failed 07/31/2007
Correction
Corrective Action Required
07/31/2007
NONE None - PROVIDE WIRE CLAMPS AT WIRES EXITING PANEL. - GROUND TO WATER CONNECTION CLAMP MUST BE AL/CU LISTED. (COMBINATION COPPER/ALLUMINIMUM) BASEMENT
Electrical Service Inspection Passed 08/01/2007
Correction
Resolved
08/01/2007
NONE None
Driveway Inspection Passed 08/02/2007
Sidewalk Inspection Passed 08/02/2007
Miscellaneous Inspection Passed 10/07/2008
Correction
Resolved
10/07/2008
R325 Premises Identification (IRC)
Erosion Control Inspection Residential Passed 10/07/2008
Correction
Resolved
10/07/2008
LSCO 5029 XX Erosion Control INADEQUATE EROSION CONTROL NO FURTHER INSPECTIONS UNTIL COMPLIANT 2ND NOTICE
All Rough Inspection - Residential Passed 10/07/2008
Correction
Resolved
10/07/2008
R502.6 Bearing (Joist/Beam Girder) (IRC)
Correction
Resolved
10/07/2008
R602.6 Stud Drilling and Notching (IRC)
Occupancy Inspection - Codes Residential Failed 10/07/2008
Correction
Corrective Action Required
10/07/2008
MISC PAINT EXTERIOR GAS SERVICE PIPING
Correction
Corrective Action Required
10/07/2008
MISC SEAL EXTERIOR -SEAL FRONT GARAGE LUMINAIRES -SEAL ABOVE A/C DISCONNECTS -SEAL ALL EXTERIOR WALL PENETRATIONS
Correction
Corrective Action Required
10/07/2008
E4204.1 IRC Separation from other conductors. SEPARATE LOW VOLTAGE FROM POWER FIREPLACE SWITCHBOX
Correction
Corrective Action Required
10/07/2008
MISC INSTALL LOCK DEVICES FOR BREAKERS OVEN AND COOKTOP BREAKERS
Correction
Corrective Action Required
10/07/2008
LSCO 7-907 Garage Separation (IRC) INSTALL 5/8" GYPSUM BOARD UNDER GARAGE WALL CANTILEVER
Correction
Corrective Action Required
10/07/2008
MISC GARAGE STAIR RISER HEIGHTS SHORTEST AND HIGHEST RISERS SHALL BE WITHIN 3/8" IN HEIGHT
Correction
Corrective Action Required
10/07/2008
LSCO 7-216 Guards (IBC) GUARD SHALL BE MIN 36". STAIR TO 2ND FL
Correction
Corrective Action Required
10/07/2008
R317.1 Smoke Alarms (IRC) INSTALL SMOKE DETECTOR PER CODE FRONT BEDROOM
Correction
Corrective Action Required
10/07/2008
E3903.11 Fixtures in Clothes Closets INSTALL FLOURESCENT LUMINAIRE IN CLOSET. LESS THAN 12" CLEARANCE TO SHELF FRONT BEDROOM CLOSET
Correction
Corrective Action Required
10/07/2008
MISC A/C BREAKER SIZE SHALL BE PER LABEL REPLACE BOTH A/C BREAKERS WITH 20 AND 40 AMP BREAKERS
Correction
Corrective Action Required
10/07/2008
MISC REMOVE FOAM ABOVE SERVICE PANEL REMOVE FOAM WHERE ALL CONDUCTORS PENETRATE THROUGH TOP PLATE. POTENTIAL FOR HEAT BUILD-UP
Correction
Corrective Action Required
10/07/2008
MISC HANGING WIRE IN BASEMENT COMPLETE CIRCUIT TO KITCHEN ISLAND OR REMOVE OR TERMINATE
Correction
Corrective Action Required
10/07/2008
MISC DECK DEFICIENCIES 1. DECK PIERS NOT INSPECTED&APPROVED 2. CEDAR POST SHALL NOT BE BURIED IN CONCRETE IN CONTACT WITH SOIL
Occupancy Inspection - Codes Residential Failed 12/24/2008
Correction
Resolved
12/24/2008
MISC DECK DEFICIENCIES
Correction
Resolved
12/24/2008
MISC PAINT EXTERIOR GAS SERVICE PIPING
Correction
Resolved
12/24/2008
MISC SEAL EXTERIOR
Correction
Resolved
12/24/2008
E4204.1 IRC Separation from other conductors.
Correction
Resolved
12/24/2008
MISC INSTALL LOCK DEVICES FOR BREAKERS
Correction
Resolved
12/24/2008
LSCO 7-907 Garage Separation (IRC)
Correction
Resolved
12/24/2008
MISC GARAGE STAIR RISER HEIGHTS
Correction
Resolved
12/24/2008
LSCO 7-216 Guards (IBC)
Correction
Resolved
12/24/2008
R317.1 Smoke Alarms (IRC)
Correction
Corrective Action Required
12/24/2008
E3903.11 Fixtures in Clothes Closets INSTALL FLOURESCENT LUMINAIRE IN CLOSET. LESS THAN 12" CLEARANCE TO SHELF ***LOW VOLTAGE HALOGEN LAMP FIXTURE DOES NOT MEET CODE REQUIREMENT*** FRONT BEDROOM CLOSET
Correction
Corrective Action Required
12/24/2008
MISC A/C BREAKER SIZE SHALL BE PER LABEL REPLACE BOTH A/C BREAKERS WITH 20 AND 40 AMP BREAKERS ***INSTALL GE BRAND BREAKERS***
Correction
Resolved
12/24/2008
MISC REMOVE FOAM ABOVE SERVICE PANEL
Correction
Resolved
12/24/2008
MISC HANGING WIRE IN BASEMENT
Occupancy Inspection - Codes Residential Failed 12/31/2008
Correction
Corrective Action Required
12/31/2008
Misc- No Access Provided
Occupancy Inspection - Codes Residential Passed 01/05/2009
Correction
Resolved
01/05/2009
E3903.11 Fixtures in Clothes Closets
Correction
Resolved
01/05/2009
MISC A/C BREAKER SIZE SHALL BE PER LABEL
Correction
Resolved
01/05/2009
Misc- No Access Provided
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home