Summary
B0700488
Building Permit - Commercial
Final Completion
DACUR INVESTMENT COMPANY INC
ALTERATION COMMERCIAL
WHITE BOX & REM SIBILITY **drawing in permit file
03/15/2007
03/21/2007
09/13/2008
05/16/2008
Locations
Contacts
CHARLES F CURRY CO, Address:6323 GEORGE  
SIEGER ELECTRIC, INC, Address:4020 E 137TH TERR, SUITE 100  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/11/2007 10/29/2010
Correction

CA - ICC/ANSI A117.1-1998 603.3 - Mirrors shall be mounted with the bottom edge of the reflecting surface 40 inches maximum above the floor or ground.
Correction

CA - ANSI A117.1 1998 604.3.1 - Size. Clearance around the water closet shall be 60 inches minimum, measured perpendicular from the side wall, and 56 inches minimum, measured perpendicular from the rear wall. No other fixtures or obstructions shall be within the water closet clearance.
Correction

CA - ANSI A117.1 1998 604.5.1 - Side Wall. Side wall grab bars shall be 42 inches long minimum, 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall.
Correction

CA - ANSI A117.1 1998 604.5.2 - Rear Wall. The rear wall grab bar shall be 24 inches long minimum, centered on the water closet. Where space permits, the bar shall be 36 inches long minim, with the additional length provided on the transfer side of the water closet.
Correction

CA - ANSI A117.1 1998 606.2 - Clear Floor or Ground Space (lavatories and sinks). A clear floor or ground space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided.
Correction

CA - ANSI A117.1 1998 606.3 - Height and Clearanse. The front of lavatories and sinks shall be 34 inches maximum above the floor or ground, measured to the higher of the fixture rim or counter surface.
Correction

CA - ANSI A117.1 1998 606.6 - Exposed Pipes and Surfaces. Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact. There shall be no sharp or abrasive surfaces under lavatories and sinks.
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - ANSI A117.1-1998 404.2.3 - Clear width. Doorways shall have a clear opening of 32 inches minimum. Clear opening of doorways with swinging doors shall be measured between the face of door and stop, with the door open 90 degrees. Openings more than 24 inches deep shall provide a clear opening of 36 inches minimum. There shall be no projections into the clear opening width lower than 34 inches above the floor or ground. Projections into the minim clear opening width more than 34 inches and up to 80 inches above the floor or ground are permitted but shall not exceed 4 inches.
Correction

CA - ANSI A117.1-1998 606.4 - Faucets. Faucets shall comply with Section 309. Hand-operated, self-closing faucets shall remain open for 10 seconds minimum.
Correction

Codes Administration - 2003 IBC 1103.1 - Where required. Buildings and structures, temporary or permanent, includeing their associated sites and facilities, shall be accessible to persons with physical disablilities.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $65.98 $65.98 Paid 03/21/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 03/28/2007
Correction
Partial Correction
03/28/2007
ROUGH-IN @ EXISTING EXTERIOR WALLS + RESTROOMS RESTROOMS NOT READY FOR INSPECTION UNTIL ELECTRICAL WORK IS COMPLETED. CALL WHEN READY. NO ISSUES FOUND AT GWB LAMINATED EXTERIOR WALLS
Above Ceiling Inspection Failed 01/03/2008
Correction
Corrective Action Required
01/03/2008
ELECTRICAL JUNCTION BOX ABOVE WEST RESTROOM NOT CLOSED
Correction
Corrective Action Required
01/03/2008
ELECTRICAL JUNCTION BOX OUTSIDE/ABOVE RESTROOM DOORS UNUSED OPEN'G NOT PLUGGED
Correction
Corrective Action Required
01/03/2008
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE WITH TWO FULL WRAPS MINIMUM. NOT FOUND INSTALLED TWO TIES PER FIXTURE
Correction
Corrective Action Required
01/03/2008
INSTALLATION OF MC ELECTRICAL CABLE NEC 300-11 & 334-10 [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG] NOTE: BATWINGS OK TO SUPPORT, BUT NOT APPROVED TO SECURE CABLE. NOT SECURELY FASTENED WITHIN 12" OF BOXES
Correction
Corrective Action Required
01/03/2008
LOW-VOLTAGE ELECTRICAL CABLE IN ABOVE-CEILING PLENUM SPACE REMOVE OR PROVIDE PLENUM-RATED LISTING
Correction
Corrective Action Required
01/03/2008
HVAC SUPPLY AIR DUCT INSULATION INSULATION INCOMPLETE
Correction
Corrective Action Required
01/03/2008
INSTALLATION OF WATER HEATER 1) EXPANSION TANK? 2) TPR DRAIN? PROVIDE MANUFACTURER INSTALLATION INSTRUCTIONS
Correction
Corrective Action Required
01/03/2008
COMBUSTIBLE ABS PLUMBING PIPE IN INTERSTITIAL SPACE NOT ALLOWED ABOVE CEILING HVAC RETURN AIR PLENUM
Correction
Corrective Action Required
01/03/2008
APPROVAL OF WALL FRAMING AND IN-WALL SYSTEMS RESTROOM WALLS WERE NOT READY FOR INSPECTION. NOW ARE COVERED WITHOUT RECORDED APPROVAL. LOCATION OF SOUTH WALLS NOT PER APPROVED DRAWING. ELECTRICAL SERVICE PANEL NOT ALLOWED INSIDE RESTROOM. RESOLVE BEFORE REQUESTING ABOVE-CEILING RE-INSPECTION. NO FULL APPROVAL RECORDED SEE 3/28/07 INSPECTION
All Rough Inspection - Commercial Passed 02/07/2008
Correction
Resolved
02/07/2008
ROUGH-IN @ EXISTING EXTERIOR WALLS + RESTROOMS
Above Ceiling Inspection Partial 02/07/2008
Correction
Resolved
02/07/2008
ELECTRICAL JUNCTION BOX ABOVE WEST RESTROOM
Correction
Resolved
02/07/2008
ELECTRICAL JUNCTION BOX OUTSIDE/ABOVE RESTROOM DOORS
Correction
Resolved
02/07/2008
SEISMIC TIES AT LAY-IN ELECTRICAL LIGHTING FIXTURES
Correction
Resolved
02/07/2008
INSTALLATION OF MC ELECTRICAL CABLE
Correction
Resolved
02/07/2008
LOW-VOLTAGE ELECTRICAL CABLE IN ABOVE-CEILING PLENUM SPACE
Correction
Resolved
02/07/2008
HVAC SUPPLY AIR DUCT INSULATION
Correction
Corrective Action Required
02/07/2008
INSTALLATION OF WATER HEATER TPR DRAIN TO DISCHARGE PER IPC
Correction
Resolved
02/07/2008
COMBUSTIBLE ABS PLUMBING PIPE IN INTERSTITIAL SPACE HVAC RETURN AIR NOW DUCTED
Correction
Partial Correction
02/07/2008
APPROVAL OF WALL FRAMING AND IN-WALL SYSTEMS REGARDING INCOMPASSING ELECT PANEL WITHIN RESTROOM CONTINGENT ON APPROVAL OF CMR TO BE SUBMITTED
Correction
Partial Correction
02/07/2008
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY EXCEPT @ W.H. TPR DRAIN
Miscellaneous Inspection Passed 02/22/2008
Above Ceiling Inspection Passed 02/28/2008
Correction
Resolved
02/28/2008
INSTALLATION OF WATER HEATER TPR DRAIN TO DISCHARGE PER IPC
Correction
Resolved
02/28/2008
APPROVAL OF WALL FRAMING AND IN-WALL SYSTEMS REGARDING INCOMPASSING ELECT PANEL WITHIN RESTROOM CMR SUBMITTED / APPROVED
Correction
Resolved
02/28/2008
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS
Occupancy Inspection - Codes Commercial Failed 03/17/2008
Correction
Corrective Action Required
03/17/2008
Receive Fire Department approval CONTACT CPT DIR WHEN ADDRESS IS AFFIXED
Correction
Corrective Action Required
03/17/2008
INSTALLATION OF ELECTRICAL RECEPTACLES MAKE ALL SOLID/TIGHT; THEN INSTALL FACE PLATES SOME NOT MOUNTED SOLID AND/OR TIGHT TO BOX
Correction
Partial Correction
03/17/2008
USE / OCCUPANCY APPROVAL STATUS UNTIL APPROVED. DO NOT OBSTRUCT ANY ELECTRICAL RECEPTACLES -- YET TO BE RE-INSPECTED. OK TO SET UP FOR BUSINESS NO PUBLIC ENTRY
Occupancy Inspection - Codes Commercial Failed 03/20/2008
Correction
Resolved
03/20/2008
Receive Fire Department approval PER CPT JOE DIR 3/19/08
Occupancy Inspection - Codes Commercial Passed 05/15/2008
Correction
Resolved
05/15/2008
INSTALLATION OF ELECTRICAL RECEPTACLES
Correction
Resolved
05/15/2008
USE / OCCUPANCY APPROVAL STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home