Permit Application Status

B0700409


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0700409
Building Permit - Commercial
Certificate of Occupancy
BHUMIKA LLC
NEW TENANT FINISH
TENANT FINISH
03/07/2007
03/22/2007
12/25/2007
07/02/2007
Locations
Contacts
J & N UTILITIES, Address:PO BOX 1284  
SHUKLA AND ASSOCIATES, Address:3693 W 129TH PLACE  
D M A ELECTRIC, Address:7468 W 162ND TR  
A.B. MAY SALES AND SERVICE, Address:2017 W 104TH STREET  
SHUKLA AND ASSOCIATES, Address:3693 W 129TH PLACE  
BHUMIKA LLC, Address:3151 NE CARNEGIE DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/18/2007 10/29/2010
Correction

Codes Administration - ANSI A117.1-1998 804.7.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer space 54 inches maximum above the floor or ground. The clear floor or ground space shall be positioned for a parallel approach to the space dedicated to a refrigerator/freezer with the centerline of the clear floor or ground space offset 24 inches maximum from the centerline of the dedicated space.
Correction

CA - ANSI A117.1-1998 606.5 - Bowl depth. Sinks shall be 6.5 inches deep maximum. Multiple compartment sinks shall have at least one compartment complying with this requirement.
Correction

Codes Administration - 2003 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.5.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-1300.
Correction

Codes Administration - As this building has one main entrance and multiple tenants, a suite number will need to be assigned to each tenant space.
Correction

Codes Administration - 2002 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13 (A) and (B).
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

Codes Administration - 2003 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $483.56 $483.56 Paid 03/22/2007
89 Sewer Tap Fees $450.00 $450.00 Paid 03/22/2007
91 EFHB Maybrook Water Shed $639.15 $639.15 Paid 03/22/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 03/23/2007
All Rough Inspection - Commercial Failed 04/06/2007
Correction
Corrective Action Required
04/06/2007
BRANCH CIRCUITS TO ALL PATIENT EXAM ROOMS PROVIDE AC/MC WITH OUTER SHEATHING SUITABLE AS EQUIPMENT GROUNDING
Correction
Corrective Action Required
04/06/2007
PROVIDE BLOCKINGS FOR GRIP BARS IN RESTROOMS
Correction
Corrective Action Required
04/06/2007
Water/DWV Preotection Against Physical Damage (IRC) PROTECT PVC FROM NAIL DAMAGE-ALL EXAM ROOMS AND RESTROOMS
Correction
Corrective Action Required
04/06/2007
None DO NOT ROCK
All Rough Inspection - Commercial Passed 04/10/2007
Correction
Resolved
04/10/2007
BRANCH CIRCUITS TO ALL PATIENT EXAM ROOMS
Correction
Resolved
04/10/2007
PROVIDE BLOCKINGS FOR GRIP BARS IN RESTROOMS
Correction
Resolved
04/10/2007
Water/DWV Preotection Against Physical Damage (IRC)
Correction
Resolved
04/10/2007
None OK TO ROCK
Above Ceiling Inspection Failed 05/21/2007
Correction
Corrective Action Required
05/21/2007
WIRING SUPPORT SECURE MC CABLE TO STRUCTURE WITHIN 12" OF JUNCTION BOXES & MAX. 6' O.C. USE APPROVED FASTENING DEVICES THROUGHOUT
Correction
Corrective Action Required
05/21/2007
EXHAUST FAN CROSS-CONTAMINATION PROVIDE VERIFICATION THAT EXHAUST FANS HAVE INTEGRAL BACK DRAFT DAMPERS RESTROOMS
Correction
Corrective Action Required
05/21/2007
PLENUM RATINGS 1- REMOVE PAPER FROM EXTERIOR WALL INSULATION 2- PROVIDE VERIFICATION OF DUCT INSULATION FIRE & SMOKE RATINGS THROUGHOUT
Correction
Corrective Action Required
05/21/2007
DUCT SUPPORT SUPPORT FLEXIBLE DUCTWORK AT MAX. 5' SPACING WITH MINIMUM 1-1/2" STRAPS THROUGHOUT
Correction
Corrective Action Required
05/21/2007
PIPE INSULATION COMPLETE WATER PIPE INSULATION ELECTRICAL ROOM ABOVE PANEL P1
Correction
Corrective Action Required
05/21/2007
None DO NOT COVER
Above Ceiling Inspection Partial 05/24/2007
Correction
Resolved
05/24/2007
WIRING SUPPORT
Correction
Resolved
05/24/2007
EXHAUST FAN CROSS-CONTAMINATION
Correction
Resolved
05/24/2007
DUCT SUPPORT
Correction
Resolved
05/24/2007
PIPE INSULATION
Correction
Partial Correction
05/24/2007
None APPROVED TO COVER CONTINGENT UPON RECEIPT & ACCEPTANCE OF FIRE/SMOKE RATINGS OF DUCT INSULATION
Above Ceiling Inspection Passed 06/19/2007
Correction
Resolved
06/19/2007
PLENUM RATINGS MOVED TO FINAL
Correction
Resolved
06/19/2007
None APPROVED TO COVER CONTINGENT UPON RECEIPT & ACCEPTANCE OF FIRE/SMOKE RATINGS OF DUCT INSULATION VIOLATION MOVED TO FINAL
Occupancy Inspection - Codes Commercial Failed 06/19/2007
Correction
Corrective Action Required
06/19/2007
NO-SMOKING SIGNAGE ORDINANCE PROVIDE NO-SMOKING DECAL/STICKER AT BUILDING ENTRANCES
Correction
Corrective Action Required
06/19/2007
EXTERIOR GFCI RECEPTACLE NON-FUNCTIONAL EXTERIOR
Correction
Corrective Action Required
06/19/2007
ADA REQUIREMENTS ALL PIPING UNDER SINKS TO BE INSULATED RESTROOMS
Correction
Resolved
06/19/2007
30 DAY TCO
Occupancy Inspection - Codes Commercial Passed 06/29/2007
Correction
Resolved
06/29/2007
NO-SMOKING SIGNAGE ORDINANCE
Correction
Resolved
06/29/2007
EXTERIOR GFCI RECEPTACLE NON-FUNCTIONAL
Correction
Resolved
06/29/2007
ADA REQUIREMENTS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home