Summary
B0700382
Building Permit - Residential
Certificate of Occupancy
MONTICELLO HOMES LLC
NEW SINGLE FAMILY
HOUSE AND DECK(S)
03/05/2007
03/07/2007
01/27/2010
05/10/2011
Locations
Contacts
AFC HEATING & COOLING INC, Address:824 NW MAIN ST  
PARAGON ELECTRIC, Address:1500 E 40 HWY  
CENTURY PLUMBING, Address:14001 CENTURY LANE  
MONTICELLO HOMES LLC, Address:PO BOX 7005  
MONTICELLO HOMES LLC, Address:623 NE LONE HILL DR  
ABRAMOVITZ TONI TRUST, Address:53 C NE SIENA PLACE  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/03/2007 10/29/2010
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration- Bedrooms located in basements shall have at least one operable window or door approved for emergency escape which opens to the exterior. All escape or rescue windows shall have a minimum net clear openable area of 5.7 square feet. The net clear openable height shall be 24 inches. The minimum net clear openable width shall be 20 inches. The finished sill height shall not exceed 44 inches above the finished floor. (UBC Section 1204).
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - The holder of this permit agrees and understands that only persons authorized per LSCO 7-130 are permitted to perform electrical, plumbing or mechanical work authorized by this permit.
Correction

In a combined effort with both the R-4, and the R-7 School Districts the City of Lee's Summit is working together to educate the development community on a new program, the "Lee's Summit Voluntary Residential Development Surcharge". This is a program, which will help raise capital to build new schools for our community. Brochures are available at the front counter of both the Planning and Development and the Codes Administration departments. You can also find more information on the City of Lee's Summit web site at lees-summit.mo.us. (For more information please contact the Board of Education at 986-2400).
Correction

CA - If decks are not shown on plot plans submitted at the time of permit application for the structure, and decks are proposed to be installed prior to occupancy, a separate approval and permit is required prior to construction of such deck(s).
Correction

CA - The holder of this permit agrees and understands that the work authorized by this permit shall be performed in accordance with the 2003 International Residential Code as amended by Chapter 7 of the Lee's Summit Code of Ordinances.
Correction

All residential projects applied for after May 6, 2006 shall have a maximum stair rise of 7-3/4 inches and a minimum tread depth of 10". This project was applied for after May 6, 2006 and therefore must comply with this requirement.
Correction

CA - LSCO 7-122 - Any excavation for foundations and/or footings of buildings and structures shall be backfilled within twenty-eight (28) days from the date of permit issuance unless otherwise approved by the building official.
Correction

CA - LSCO 7-128 (a)1 - Retaining walls which are over 4 feet in height measured from the bottom of the footing to the top of the wall of the wall shall be designed and sealed by a professional engineer or architect registered in the State of Missouri. In addition, the building official may waive the requirements for a permit or engineered drawings for walls over 4 feet in height if it is deemed unnecessary to require such submittals due to the location and type of wall to be installed.
Correction

CA - LSCO 7-168 A - Footing and foundation inspections shall be made after excavations for footings are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place before inspection. Materials for the foundation shall be on the job, except where concrete is ready mixed in accordance with ASTM C 94; the concrete need not be on the job.
Correction

Codes Administration - 2003 IRC 407.1.7.3 - Foundation elevation. On graded sites, the top of any exterior foundation shall extend aboe the elevation of the street gutter at point of discharge or the inlet of an approved drainage device a minimum of 12 inches plus 2 percent. Alternate elevations are permitted sublect to the approval of the building official, provided it can be demonstrated tha required drainage to the point of discharge and away from the structure is provided at all locations on the site.
Correction

Codes Administration - 2003 IRC 405.1 - Concrete or masonry foundations. Drains shall be provided around all concrete or masonry foundations that retain earth and enclose habitable or usable spaces located below grade. Drainage tiles, gravel or crushed stone drains, perforated pipe or other approved systems or materials shall be installed at or below the area to be protected and shall discharge by gravity or mechanical means into an approved drainage system. Gravel or crushed stone drains shall extend at least 1 foot beyond the outside edge of the footing and 6 inches above the top of the footing and be covered with an approved filter membrane material. The top of open joints of drain tiles shall be protected with strips of building paper, and the drainage tiles or perforated pipe shall be placed on a mimum of 2 inches of washed gravel or crushed rock at lease on sieve size larger than the tile joint openings or perforation and covered with not less than 6 inches of the same material.
Correction

CA - LSCO 7-930 - All dwellings shall have a controlled method of water disposal from the roofs that will collect and discharge all roof drainage to the ground at least 3 feet from the foundation walls or to an approved drainage system.
Correction

Codes Administration - 2003 IRC 311.5.2 - Headroom. The minimum headroom in all parts of the stairway shall not be less than 6 feet 8 inches measured vertically from the sloped plane adjoining the tread nosing or from the floor surface of the landing or platform.
Correction

Codes Administration - 2003 IRC 401.3 - Drainage. Surface drainage shall be diverted to a storm sewer conveyance or other approved point of collection so as to not create a hazard. Lots shall be graded so as to drain surface water away from foundation walls. The grade away from foundation wall shall fall a minimum of 6 inches with the first 10 feet. Exception: Where lot lines, walls, slopes or other physical barriers prohibit 6 inches of fall within 10 feet, drains or swales shall be provided to ensure drainage away from the structure.
Correction

Codes Administration - 2003 IRC 403.1.6 - Foundation anchorage. When braced wall panels are supported directly on continous foundations, the wall wood sill plate or cold-formed steel bottom track shall be anchored to the foundation in accordance with this section. The wood sole plate at exterior walls in monolithic slabs and wood sill plate shall be anchored to the foundation with anchor bolts spaced a maximum of 6 feet (1829 mm) on center. There shall be a minimum of two bolts per plate section with one bolt located not more than 12 inches (305 mm) or less than seven bolt diameters from each end of the plate section. In Seismic Design Categories D1 and D2, anchor bolts shall also be spaced at 6 feet (1829 mm) on center and located with 12 inches (305 mm) from the ends of the plate section at interior braced wall lines when required by Section R602.10.9 to be supported on a continous foundation. Bolts shall be at least 1/2 inch (12.7 mm) in diameter and shall extend a minimum of 7 inches (178 mm) into masonry or concrete. Interior bearing wall sole plates on monolithic slab foundations shall be positively anchored with approved fasteners. A nut and washer shall be tightened on each bolt to the plate. Sills and sole plates shall be protected against decay and termites wher required by Sections R318 and R319. Cold-formed steel framing systems shall be fastened to the wood sill plates or anchored directly to the foundation as required in Section R505.3.1 or R603.1.1. Exceptions: 1. Foundation anchor straps, space as required to provide equivalent anchorage to 1/2-inch-diameter (12.7 mm) anchor bolts. 2. Walls 24 inches total in length or shorter connecting offset braced wall panels shall be anchored to the foundation with a minimum of one anchor bolt located in the center third of the plate section and shall be attached to adjacent braced wall panels per Figure R602.10.5 at corners. 3. Walls 12 inches total length or shorter connecting offset braced wall panels shall be permitted to be connected to the foundation without anchor bolts. The wall shall be attached to adjacent braced wall panels per Figure 602.10.5. As amended by the City of Lee's Summit.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $678.93 $678.93 Paid 03/07/2007
84 Water Meters $125.00 $125.00 Paid 03/07/2007
85 Water Taps $2,734.00 $2,734.00 Paid 03/07/2007
89 Sewer Tap Fees $450.00 $450.00 Paid 03/07/2007
91 EFHB Maybrook Water Shed $639.15 $639.15 Paid 03/07/2007
Right of Way Permit $35.00 $35.00 Paid 03/07/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 03/08/2007
Correction
Resolved
03/08/2007
NONE None -PERIMETER FOOTING, 4 BASEMENT COLUMN PADS, 2 GARAGE PADS FOR SUPPORTING GARAGE SLAB-APPROVED
Correction
Resolved
03/08/2007
R403.1.4 Footing Depth (IRC)
Correction
Resolved
03/08/2007
R403.1.1 Minimum size of footings (IRC)
Correction
Resolved
03/08/2007
R403.1 Footing support (IRC)
Correction
Resolved
03/08/2007
LSCO 7-921 Column Pad Reinforcement (IRC)
Correction
Resolved
03/08/2007
LSCO 7-920 Footing Reinforcement (IRC)
Foundation Inspection - Residential Partial 03/13/2007
Correction
Partial Correction
03/13/2007
MISC INSTALLATION PER DESIGN EXTRA BARS ADDED TO SATISFY DESIGN. ADDED BARS TIED ONLY AT TOP HORIZONTAL. PROVIDE SEALED ENGINEER'S LETTER FOR APPROVAL. POUR AT YOUR OWN RISK.
Miscellaneous Inspection Failed 03/16/2007
Correction
Corrective Action Required
03/16/2007
R325 Premises Identification (IRC) PROPERTY MUST BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS
Erosion Control Inspection Residential Failed 03/16/2007
Correction
Corrective Action Required
03/16/2007
LSCO5029XX2 Tracking Mud, Debris STREET CLEANUP REQUIRED INCLUDING CLEANOUT OF STORM INLET. 2 DAYS TO COMPLY
Correction
Corrective Action Required
03/16/2007
LSCO 5029 XX Erosion Control DEFICIENT EROSION CONTROL. PROVIDE AT REAR OF LOT AS WELL. 2 DAYS TO COMPLY
Electrical Service Inspection Failed 03/16/2007
Correction
Corrective Action Required
03/16/2007
E3507.1 System Service Ground (IRC) WATER PIPE WILL NOT BE ALLOWED FOR GROUND DUE TO PEX PIPING. 2 RODS, 6' APART WILL BE REQUIRED.
Water Service Inspection - R Partial 03/16/2007
Correction
Partial Correction
03/16/2007
NONE None TO METER SITE
Sewer Service Inspection - R Passed 03/16/2007
Sewer Service Inspection - Residential Request Complete 3/16/2007 3/16/2007 03/16/2007
Water Service Inspection - Residential Request Complete 3/16/2007 3/16/2007 03/16/2007
Water Service Inspection - R Passed 03/19/2007
Correction
Resolved
03/19/2007
NONE None
Water Service Inspection - Residential Request Complete 3/19/2007 3/19/2007 03/19/2007
Foundation Inspection - Residential Passed 03/20/2007
Correction
Resolved
03/20/2007
MISC INSTALLATION PER DESIGN ALTERNATE TIES IN REBAR PER DESIGN APPROVED PER LETTER DATED 3/13/07
Miscellaneous Inspection Failed 04/02/2007
Correction
Corrective Action Required
04/02/2007
R325 Premises Identification (IRC) PROPERTY MUST BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS NO FURTHER INSPECTIONS UNTIL COMPLIANT 2ND NOTICE
Erosion Control Inspection Residential Failed 04/02/2007
Correction
Corrective Action Required
04/02/2007
LSCO 5029 XX Erosion Control DEFICIENT EROSION CONTROL. PROVIDE AT REAR OF LOT AS WELL. NO FURTHER INSPECTIONS UNTIL COMPLIANT 2ND NOTICE
Correction
Resolved
04/02/2007
LSCO5029XX2 Tracking Mud, Debris
Underslab Plumbing Inspection - Residential Passed 04/02/2007
Miscellaneous Inspection Failed 05/21/2007
Correction
Corrective Action Required
05/21/2007
R325 Premises Identification (IRC) PROPERTY MUST BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS NO FURTHER INSPECTIONS UNTIL COMPLIANT IF NOT COMPLETE BY 5/23/07 STOP WORK ORDER WILL BE PLACED 3RD NOTICE
Erosion Control Inspection Residential Failed 05/21/2007
Correction
Corrective Action Required
05/21/2007
LSCO 5029 XX Erosion Control DEFICIENT EROSION CONTROL. PROVIDE AT REAR OF LOT AS WELL. NO FURTHER INSPECTIONS UNTIL COMPLIANT IF NOT COMPLETE BY 5/23/07 STOP WORK ORDER WILL BE PLACED 3RD NOTICE
Piers/Caissons Inspection - Residential Passed 05/21/2007
Correction
Resolved
05/21/2007
NONE None 2 PIERS
Erosion Control Inspection Residential Failed 05/24/2007
Correction
Corrective Action Required
05/24/2007
LSCO 5029 XX Erosion Control DEFICIENT EROSION CONTROL AT FRONT OF LOT 2 DAYS TO COMPLY
Miscellaneous Inspection Passed 06/01/2007
Correction
Resolved
06/01/2007
R325 Premises Identification (IRC)
Erosion Control Inspection Residential Failed 06/01/2007
Correction
Corrective Action Required
06/01/2007
LSCO 5029 XX Erosion Control REPAIR DAMAGED/OVER-RUN SILT FENCE AT REAR OF LOT 2 DAYS TO COMPLY
Correction
Resolved
06/01/2007
LSCO5029XX2 Tracking Mud, Debris
All Rough Inspection - Residential Not Ready 06/01/2007
Correction
Corrective Action Required
06/01/2007
R802.7.1 Rafter Cutting & Notching (IRC) PROVIDE STUDS FOR FULL BEARING AT CUT RAFTERS ON LEFT HAND SIDE OF EXTERIOR WALL. MAINTAIN ACCESS TO ABOVE DECK FOR ELECTRICAL INSPECTION DURING ALL-ROUGH ABOVE DECK
Erosion Control Inspection Residential Failed 06/04/2007
Correction
Corrective Action Required
06/04/2007
LSCO 5029 XX Erosion Control REPAIR DAMAGED/OVER-RUN SILT FENCE AT REAR OF LOT NO FURTHER INSPECTIONS UNTIL COMPLIANT 2ND NOTICE
Erosion Control Inspection Residential Passed 06/21/2007
Correction
Resolved
06/21/2007
LSCO 5029 XX Erosion Control
Electrical Service Inspection Failed 06/21/2007
Correction
Corrective Action Required
06/21/2007
E3507.1 System Service Ground (IRC) WATER PIPE WILL NOT BE ALLOWED FOR GROUND DUE TO PEX PIPING. 2 RODS, 6' APART WILL BE REQUIRED.
Correction
Corrective Action Required
06/21/2007
MISC GROUND SERVICE CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUNDED SERVICE CONDUCTOR @ SERVICE DISCONNECT.
All Rough Inspection - Residential Failed 06/21/2007
Correction
Corrective Action Required
06/21/2007
MISC FIREBLOCKING -FB ALL BASEMENT FURRED WALL SPACE EVERY 10 FT HORIZONTALLY AND AT CEILING INTERSECTION WITH CEILING JOISTS SPACE AND FUR-DOWN CEILING SPACE BASEMENT
Correction
Corrective Action Required
06/21/2007
R403.1.6 Foundation Anchor Bolts (IRC) ANCHOR WITHIN 12" OF BASEMENT WALKOUT DOOR
Correction
Corrective Action Required
06/21/2007
MISC INSTALL WYE FITTING OR LONG SWEEP FITTING AT WASTER STACK CONNECTION TO SEWER, IN WASTE PUMP RM
Correction
Corrective Action Required
06/21/2007
NONE None OKAY TO INSULATE, DO NOT ROCK
Correction
Corrective Action Required
06/21/2007
MISC SUPPORT BASEMENT FUR-DOWN CEILING STRAP CEILING JOISTS HEADER RIM TO STRUCTURE MEMBERS. BENDING NAILS AROUND I BEAM BOTTOM FLANGE IS NOT ADEQUATE. @ STAIR BOTTOM LANDING, ALONG LENGTH OF BUILDING
Correction
Corrective Action Required
06/21/2007
E3304.9 Prevent Physical Damage (IRC) PROTECT NM CABLE AT MASTERBATH SINK WALL
Correction
Corrective Action Required
06/21/2007
LSCO 7-903 Bathroom ventilation (IRC) CONNECT BATHFAN TO DUCT-FRONT BEDROOM BATHROOM
Correction
Corrective Action Required
06/21/2007
MISC FIREBLOCKING -FB FIREPLACE SPACE FROM ATTIC, USING MIN 3/4" SHEATHING, 1/2" SHEETROCK, METAL SHEET, 1/4" CONCRETE, OR OTHER APPROVED MOETHOD. DON'T USE 7/16" SIDING -FB MASTERBATH WALL FROM ATTIC 1ST FLOOR
Correction
Corrective Action Required
06/21/2007
MISC COMPLETE FUROUT AT B-VENT-KITCHEN PANTRY
Correction
Corrective Action Required
06/21/2007
MISC STRAP KITCHEN WALL TOP PLATE @ PVC
Correction
Corrective Action Required
06/21/2007
MISC NAIL WALL CORNER STUDS AT NE KITCHEN CORNER
Correction
Corrective Action Required
06/21/2007
R602.6 Stud Drilling and Notching (IRC) INSTALL STUD SHOES AT: LAUNDRY, KITCHEN SINK WALL
Correction
Corrective Action Required
06/21/2007
MISC SUPPORT ENTRANCE CLOSET FLOOR
Gas Piping Inspection - Residential Passed 06/21/2007
Gas Service Inspection - Residential Failed 06/21/2007
Correction
Corrective Action Required
06/21/2007
M2416.4.1 Gas Test Pressure (IRC) PROVIDE MIN 10 PSI
Erosion Control Inspection Residential Passed 06/25/2007
All Rough Inspection - Residential Failed 06/25/2007
Correction
Resolved
06/25/2007
R802.7.1 Rafter Cutting & Notching (IRC) ABOVE DECK
Correction
Resolved
06/25/2007
MISC SUPPORT ENTRANCE CLOSET FLOOR
Correction
Resolved
06/25/2007
R602.6 Stud Drilling and Notching (IRC)
Correction
Resolved
06/25/2007
MISC NAIL WALL CORNER STUDS AT NE KITCHEN CORNER
Correction
Resolved
06/25/2007
MISC STRAP KITCHEN WALL TOP PLATE @ PVC
Correction
Resolved
06/25/2007
MISC COMPLETE FUROUT AT B-VENT-KITCHEN PANTRY
Correction
Resolved
06/25/2007
MISC FIREBLOCKING 1ST FLOOR
Correction
Resolved
06/25/2007
LSCO 7-903 Bathroom ventilation (IRC)
Correction
Resolved
06/25/2007
E3304.9 Prevent Physical Damage (IRC)
Correction
Resolved
06/25/2007
MISC SUPPORT BASEMENT FUR-DOWN CEILING
Correction
Resolved
06/25/2007
MISC FIREBLOCKING BASEMENT
Correction
Resolved
06/25/2007
R403.1.6 Foundation Anchor Bolts (IRC)
Correction
Corrective Action Required
06/25/2007
MISC INSTALL WYE FITTING OR LONG SWEEP FITTING AT WASTER STACK CONNECTION TO SEWER, IN WASTE PUMP RM. 4 INCH CLEAN OUT REQUIRED.
Correction
Corrective Action Required
06/25/2007
NONE None OKAY ROCK
Electrical Service Inspection Failed 06/25/2007
Correction
Corrective Action Required
06/25/2007
E3507.1 System Service Ground (IRC) WATER PIPE WILL NOT BE ALLOWED FOR GROUND DUE TO PEX PIPING. 2 RODS, 6' APART WILL BE REQUIRED.
Gas Service Inspection - Residential Passed 06/28/2007
Correction
Resolved
06/28/2007
M2416.4.1 Gas Test Pressure (IRC) APPROVED FOR GAS SERVICE RELEASE
Driveway Inspection Passed 07/19/2007
Miscellaneous Inspection Failed 12/20/2007
Correction
Corrective Action Required
12/20/2007
R325 Premises Identification (IRC) PROPERTY TO BE IDENTIFIABLE FROM STREET FOR ALL INSPECTIONS
All Rough Inspection - Residential Failed 12/20/2007
Correction
Corrective Action Required
12/20/2007
MISC INSTALL WYE FITTING OR LONG SWEEP FITTING AT WASHER STACK CONNECTION TO SEWER, IN WASTE PUMP RM. 4 INCH CLEAN OUT REQUIRED. LEAVE EXPOSED FOR INSPECTION AT FINAL
Correction
Corrective Action Required
12/20/2007
NONE None OKAY ROCK
Correction
Corrective Action Required
12/20/2007
Misc- No Access Provided
Miscellaneous Inspection Passed 12/28/2007
Correction
Resolved
12/28/2007
R325 Premises Identification (IRC)
All Rough Inspection - Residential Passed 12/28/2007
Correction
Resolved
12/28/2007
MISC INSTALL WYE FITTING OR LONG SWEEP FITTING
Correction
Resolved
12/28/2007
NONE None OKAY ROCK
Correction
Resolved
12/28/2007
Misc- No Access Provided
Electrical Service Inspection Passed 12/28/2007
Correction
Resolved
12/28/2007
E3507.1 System Service Ground (IRC)
Correction
Resolved
12/28/2007
MISC GROUND SERVICE
Sidewalk Inspection Passed 08/03/2009
Occupancy Inspection - Codes Residential Failed 5/2/2011 at 12:00 AM 05/02/2011
Misc
Corrective Action Required
05/02/2011
PROVIDE DECK BOTTOM STAIR LANDING
Misc
Corrective Action Required
05/02/2011
SECURE LFNC A/C CONDUIT
Misc
Corrective Action Required
05/02/2011
SECURE NM CABLE WITHIN 8" OF HYDROTUB PUMP RECEPTACLE
Misc
Corrective Action Required
05/02/2011
CONNECT COOKTOP FMC CONDUIT TO COOKTOP. FITTING IS NOT CONNECTED TO COOKTOP. MAKE SURE TO BOND METAL J-BOX
Misc
Corrective Action Required
05/02/2011
RECEPTACLE IN GRINDER PUMP ROOM MUST BE GFCI
Misc
Corrective Action Required
05/02/2011
FOR GRINDER PUMP, INSTALL GATE VALVE ABOVE CHECK VALVE
Misc
Corrective Action Required
05/02/2011
INSTALL ANTI-BACKFLOW DEVICE AT HOSE BIBB INSIDE GRINDER RM
Occupancy Inspection - Codes Residential Full C of O 5/10/2011 at 12:00 AM 05/10/2011
Misc
Resolved
05/10/2011
PROVIDE DECK BOTTOM STAIR LANDING
Misc
Resolved
05/10/2011
SECURE LFNC A/C CONDUIT
Misc
Resolved
05/10/2011
SECURE NM CABLE WITHIN 8" OF HYDROTUB PUMP RECEPTACLE
Misc
Resolved
05/10/2011
CONNECT COOKTOP FMC CONDUIT TO COOKTOP. FITTING IS NOT CONNECTED TO COOKTOP. MAKE SURE TO BOND METAL J-BOX
Misc
Resolved
05/10/2011
RECEPTACLE IN GRINDER PUMP ROOM MUST BE GFCI
Misc
Resolved
05/10/2011
FOR GRINDER PUMP, INSTALL GATE VALVE ABOVE CHECK VALVE
Misc
Resolved
05/10/2011
INSTALL ANTI-BACKFLOW DEVICE AT HOSE BIBB INSIDE GRINDER RM
Documents & Images
Date Uploaded File Type Document Name
11/18/2010 Plans 20101118103846140.pdf
05/02/2011 Letter Inspection Summary
05/10/2011 Letter Field Certificate of Occupancy
05/11/2011 Letter Final Certificate of Occupancy
06/01/2011 Final Plot Plan
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home