Permit Application Status

B0700146


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0700146
Building Permit - Commercial
Certificate of Occupancy
SOUTHSIDE PLAZA LLC
CHANGE OF TENANT
TENANT FINISH
01/24/2007
05/09/2007
01/23/2008
08/01/2007
Locations
Contacts
ABELN & ASSOCIATES ARCHITECTS PC, Address:11020 KING ST SUITE 360  
ROCKY FORD ACRES CONSTRUCTION, Address:32000 MAJOR RD  
CROSS ELECTRIC, Address:P.O. BOX 1891  
COPPER CRAFT PLUMBING, INC., Address:PO BOX 32581  
LMC MECHANICAL LLC, Address:PO BOX 134  
SOUTHSIDE PLAZA LLC, Address:215 W 77TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/03/2007 10/29/2010
Correction

Codes Administration - 2003 IBC 1007.1 - Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1014.1 or 1018.1 from any accessible space, each accessible portoin of the space shall be served by not less than two accessible means of egress.
Correction

Codes Administration - 2003 IBC 1008.1.4 - Floor elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit veritical in 12 units horizontal (2-percent slope).
Correction

Codes Administration - 2003 IBC 1008.1.5 - Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is the greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches (178 mm). When the landing serves an occupant load of 50 or more, doors in any position shall not reduce the landings to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches (1118 mm).
Correction

Codes Administration - 2003 IBC 1016.1 - Construction. Corridors shall be fire-resistance rated in accordance with Table 1016.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partitions.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.5.
Correction

Fire Department- The half door and wall in room 109 does not meet the exceptions for a child care facility to be classified as a group E occupancy. For a group I-4 occupancy IFC Section 903.2.5 requires that the I portion of the building be provided with an automatic fire sprinkler system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-1300.
Correction

Fire Department- [M] 610.2 Where required. AType I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Correction

Fire Department- 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45 720 mm) where: 1. The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.
Correction

Fire Department- 1023.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way. Exception: Where access to a public way cannot be provided, a safe dispersal area shall be provided where all of the following are met: 1. The area shall be of a size to accommodate at least 5 square feet (0.28 m2) for each person. 2. The area shall be located on the same property at least 50 feet (15 240 mm) away from the building requiring egress. 3. The area shall be permanently maintained and identified as a safe dispersal area. 4. The area shall be provided with a safe and unobstructed path of travel from the building.
Correction

Codes Administration - The Code Review Data indicates that the Occupancy Type is an E. This requires that all rooms with children under the age of 2.5 years of age to have direct access to the exterior. Room 109 does not meet this requirement.
Correction

Codes Administration - The Code Review Data uses occupant load factors of 35 and 45. These numbers are not in Table 1004.1.2 of the 2003 IBC.
Correction

Codes Administration - I am unable to locate information on the gate hardware.
Correction

Codes Administration - The mechanical plans reference a letter regarding the use of the kitchen. I am unable to locate the letter.
Correction

Fire Department- Indicate the location of the sprinkler riser room.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,021.25 $1,021.25 Paid 05/09/2007
89 Sewer Tap Fees $810.00 $810.00 Paid 05/09/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 05/23/2007
Correction
Resolved
05/23/2007
UNDER-SLAB DWV PIPING OK TO COVER WHEN READY
Gas Piping Inspection - Commercial Passed 05/29/2007
Gas Service Inspection - Commercial Passed 05/29/2007
Correction
Resolved
05/29/2007
TEST PRESSURE LEVEL RELEASE GAS SERVICE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Gas Service Inspection - Commercial Passed 05/30/2007
Rough Plumbing Inspection - Commercial Failed 06/12/2007
Correction
Resolved
06/12/2007
None ABOVE-CEILING PLUMBING APPROVED
Correction
Corrective Action Required
06/12/2007
MISC -SECURE WATER PEX LINES AT MIDWALL -INSTALL NAILGUARDS-PROTECT PVC FROM DAMAGE DO NOT ROCK WALLS
All Rough Inspection - Commercial Passed 06/20/2007
Correction
Resolved
06/20/2007
SECURING OF ELECTRICAL RECEPTACLE BOXES
Correction
Resolved
06/20/2007
PROTECTION OF PVC PIPING FROM PENETRATION
Rough Plumbing Inspection - Commercial Passed 06/20/2007
Correction
Resolved
06/20/2007
None
Correction
Resolved
06/20/2007
MISC
Rated Assembly Inspection Not Ready 06/22/2007
Correction
Corrective Action Required
06/22/2007
UL 453 RATED WALL ENSURE FASTENER SPACING IS PER UL 453 REQUEST INSPECTION PER LAYER AS COMPLETED
Correction
Corrective Action Required
06/22/2007
UL 419 RATED WALLS ENSURE FASTENER SPACING IS PER UL 419 (8" O/C AT PERIMETER; 12" O/C IN FIELD). CLOSE ALL OPENINGS TO WITHIN FIRE CAULKING GAP. NOT READY FOR INSPECITON SOME GWB NOT COMPLETED
Rated Assembly Inspection Partial 06/25/2007
Correction
Partial Correction
06/25/2007
UL 453 RATED WALL 1ST LAYER 5/8" TYPE X GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 06/26/2007
Rated Assembly Inspection Partial 06/27/2007
Correction
Partial Correction
06/27/2007
UL 453 RATED WALL 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 5/8" TYPE X GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Resolved
06/27/2007
UL 419 RATED WALLS ABOVE-CEILING INSPECTION OK TO TAPE/MUD/FIRE-CAULK ENSURE FIRE-TIGHT BEFORE
Rated Assembly Inspection Passed 07/10/2007
Correction
Resolved
07/10/2007
UL 453 RATED WALL
Correction
Resolved
07/10/2007
UL 419 RATED WALLS
Above Ceiling Inspection Not Ready 07/10/2007
Correction
Corrective Action Required
07/10/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS
Above Ceiling Inspection Not Ready 07/16/2007
Correction
Corrective Action Required
07/16/2007
READINESS FOR INSPECTION REQUEST CANCELED BY P.H.
Above Ceiling Inspection Partial 07/17/2007
Correction
Resolved
07/17/2007
READINESS FOR INSPECTION
Correction
Partial Correction
07/17/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS ALL EXCEPT 106; 115; LEAVE OUT ONE TILE ACCESS TO SEE ISOLATION OF COPPER WATER LINE FROM STEEL BAR JOISTS OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 07/24/2007
Correction
Partial Correction
07/24/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS ALL EXCEPT 115 AND ONE TILE @ 106 OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Passed 07/25/2007
Correction
Resolved
07/25/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS ALL INCLUDING 115 AND 106 OK TO COVER WHEN READY SPACES LISTED BELOW:
Occupancy Inspection - Codes Commercial Failed 07/26/2007
Correction
Resolved
07/26/2007
ACCESS TO FLOOR-MOUNTED FURNACE NOT >= 36" PER IFGC ALLOWED AS EXCEPTION
Correction
Resolved
07/26/2007
USE / OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FOR BUSINESS NO PUBLIC ENTRY
Correction
Corrective Action Required
07/26/2007
LABELING OF ELECTRICAL SERVICE METER DURABLE/PERMANENT ADDRESS IDENTIFICATION
Correction
Corrective Action Required
07/26/2007
IDENTIFICATION OF GAS SERVICE ENTRY TO SERVICE SIDE ENTRY PIPE (NOT ON METER) APPLY ADDRESS TAGS/LABELS DURABLE/PERMANENT
Correction
Corrective Action Required
07/26/2007
SMOKE SEALS AT RATED DOORS SOME INCOMPLETE SOME NOT ADHERED
Correction
Corrective Action Required
07/26/2007
Receive Water Utilities Approval
Correction
Corrective Action Required
07/26/2007
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Passed 07/30/2007
Correction
Resolved
07/30/2007
Receive Fire Department approval OK PER JOE DIR 7/30/07
Correction
Resolved
07/30/2007
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
07/30/2007
SMOKE SEALS AT RATED DOORS
Correction
Resolved
07/30/2007
IDENTIFICATION OF GAS SERVICE ENTRY IN PROGRESS
Correction
Resolved
07/30/2007
LABELING OF ELECTRICAL SERVICE METER IN PROGRESS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home