Summary
B0603551
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
NEW TENANT FINISH
NEW SANDWICH SHOP
12/06/2006
02/05/2007
08/04/2007
04/16/2007
Locations
Contacts
VALOR CONSTRUCTION INC, Address:5602 E 139TH ST  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 210, Phone:(816) 645-2336  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/24/2007 10/29/2010
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - ICC/ANSI A117.1-1998 603.3 - Mirrors shall be mounted with the bottom edge of the reflecting surface 40 inches maximum above the floor or ground.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - 2003 IBC 1014.1 - Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1. The occupant load of the space exceeds the value in Table 1014.1. 2. The common path of egress travel exceeds the limitations of Section 1013.3. 3. Where required by Sections 1014.3, 1014.4 and 1014.5.
Correction

Codes Administration - Information on doors 3 and 4 indicates that the door hardware is existing but the doors are new.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of notification appliances.
Correction

Fire Department- Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Fire Department- IFC 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- Confirm occupant load and provide second exit as needed per Codes Admin.
Correction

Codes Administration - 2002 NEC 422.31.B - Applicances rated over 300 volt-amperes or 1/8 horsepower. For permanently connected appliances rated over 300 volt-amperes or 1/8 hp, the branch-circuit switch or circuit breaker shall be permitted to serve as the disconnecting means where the switch or circuit breaker is within sight from the appliance or is capable of being locked in the open position.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $406.63 $406.63 Paid 02/05/2007
89 Sewer Tap Fees $240.00 $240.00 Paid 02/05/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 02/13/2007
Correction
Corrective Action Required
02/13/2007
INSPECTION CANCELLED INSPECTION CANCELLED
Underslab Plumbing Inspection - Commercial Passed 02/14/2007
Correction
Resolved
02/14/2007
None
Correction
Resolved
02/14/2007
INSPECTION CANCELLED
Electrical Service Inspection Passed 02/14/2007
Correction
Resolved
02/14/2007
None RELEASE ELECT.
All Rough Inspection - Commercial Partial 02/20/2007
Correction
Partial Correction
02/20/2007
None WALLS ONLY APPROVED
Correction
Partial Correction
02/20/2007
None WALLS ONLY APPROVED
Correction
Partial Correction
02/20/2007
None WALLS ONLY APPROVED. OK TO ROCK WALLS ONLY.
All Rough Inspection - Commercial Partial 02/22/2007
Correction
Partial Correction
02/22/2007
None WALLS ONLY APPROVED
Correction
Partial Correction
02/22/2007
None SCREW INSPECTION EAST WALL APPROVED.
Gas Service Inspection - Commercial Passed 03/01/2007
Correction
Resolved
03/01/2007
None GAS APPROVED TEST PRESSURE 20 PSI RELEASE GAS
Gas Piping Inspection - Commercial Passed 03/01/2007
Above Ceiling Inspection Failed 03/13/2007
Correction
Corrective Action Required
03/13/2007
LIGHTING WHIPS LIGHTING HAS YET TO BE INSTALLED - ELECTRICAL WHIPS ARE EXPOSED Bathrooms
Correction
Corrective Action Required
03/13/2007
SECURE WIRING WAITING FOR TABLES TO BE SET FOR LOCATION OF LIGHTING CUSTOMER SEATING
Correction
Corrective Action Required
03/13/2007
OPEN J-BOXES 1 - ABOVE FURNAVE WEST SIDE - IN HALLWAY 2 - ABOVE DIVIDING WALL SEPERATING FOOD PREP AREA AND EMPLOYEE WORK AREA CUSTOMER AREA
Correction
Partial Correction
03/13/2007
None OK TO COVER - NE AREA OF BUILDING FOOD PREP AREA
Above Ceiling Inspection Failed 03/14/2007
Correction
Corrective Action Required
03/14/2007
NOT READY
Correction
Corrective Action Required
03/14/2007
SECURE WIRING WAITING FOR TABLES TO BE SET FOR LOCATION OF LIGHTING CUSTOMER SEATING
Correction
Corrective Action Required
03/14/2007
OPEN J-BOXES 1 - ABOVE FURNAVE WEST SIDE - IN HALLWAY 2 - ABOVE DIVIDING WALL SEPERATING FOOD PREP AREA AND EMPLOYEE WORK AREA CUSTOMER AREA
Correction
Partial Correction
03/14/2007
None OK TO COVER - NE AREA OF BUILDING FOOD PREP AREA
Above Ceiling Inspection Passed 03/15/2007
Correction
Resolved
03/15/2007
NOT READY
Correction
Resolved
03/15/2007
LIGHTING WHIPS Bathrooms
Correction
Resolved
03/15/2007
SECURE WIRING CUSTOMER SEATING
Correction
Resolved
03/15/2007
OPEN J-BOXES CUSTOMER AREA
Correction
Resolved
03/15/2007
None FOOD PREP AREA
All Rough Inspection - Commercial Passed 03/15/2007
Correction
Resolved
03/15/2007
None
Correction
Resolved
03/15/2007
None
Correction
Resolved
03/15/2007
None
Correction
Resolved
03/15/2007
None
Occupancy Inspection - Codes Commercial Failed 03/15/2007
Correction
Corrective Action Required
03/15/2007
Electrical Listing & Labeling (IRC) LABEL BREAKERS SERVICE PANEL
Correction
Corrective Action Required
03/15/2007
ADDRESS ADDRESS REQUIRED ON BACK DOOR BACK DOOR
Correction
Corrective Action Required
03/15/2007
Kitchen Receptacles (IRC) KITCHEN OUTLETS REQUIRED TO BE GFCI PROTECTED KITCHEN
Correction
Corrective Action Required
03/15/2007
HEALTH DEPT. REQUIREMENTS OBTAIN JACKSON COUNTY HEALTH DEPARTMENT APPROVAL PRIOR TO OPENING.
Correction
Corrective Action Required
03/15/2007
Electrical Equipment Mounting (IRC) EMERGENCY LIGHT NOT WORKING. Kitchen
Occupancy Inspection - Codes Commercial Partial 03/16/2007
Correction
Resolved
03/16/2007
Electrical Listing & Labeling (IRC) SERVICE PANEL
Correction
Resolved
03/16/2007
ADDRESS BACK DOOR
Correction
Resolved
03/16/2007
Kitchen Receptacles (IRC) KITCHEN
Correction
Corrective Action Required
03/16/2007
HEALTH DEPT. REQUIREMENTS OBTAIN JACKSON COUNTY HEALTH DEPARTMENT APPROVAL PRIOR TO OPENING.
Correction
Resolved
03/16/2007
Electrical Equipment Mounting (IRC) Kitchen
Correction
Corrective Action Required
03/16/2007
FIRE DEPT REQUIREMENTS COMPLY WITH FIRE DEPT. REQUIREMENTS
Occupancy Inspection - Codes Commercial Passed 04/13/2007
Correction
Resolved
04/13/2007
HEALTH DEPT. REQUIREMENTS
Correction
Resolved
04/13/2007
FIRE DEPT REQUIREMENTS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents